-- Ingrasys USHA MIB
|
||
|
-- MIB for Uninterruptible Power Supplies
|
||
|
--
|
||
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) ingrasys(2468)
|
||
|
-- product(1) webAppliance(2) upsAgent(1) usha(1)
|
||
|
-- ==============================================================================================
|
||
|
---
|
||
|
--- Revision History
|
||
|
---
|
||
|
--- v0.80 17-Apr-2000 Johnny Lin/Allion
|
||
|
--- Created
|
||
|
--
|
||
|
--- v0.81 27-Apr-2000 Johnny Lin/Allion
|
||
|
--- Add upsTest objects 8, 9 and 10
|
||
|
--- v1.00 09-Oct-2000 Johnny Lin/Allion
|
||
|
--- Fix the problems that HPOV6.0 cann't read this
|
||
|
--- mib file due to some incorrect ','
|
||
|
--- Change upsControlEvent from DisplayString to
|
||
|
--- enum INTEGER
|
||
|
--- v1.01 25-Oct-2001 Johnny Lin/Allion
|
||
|
--- Change ENTERPRISE name from usha to ushap
|
||
|
--- Add "usha" in every trap event name
|
||
|
--- Change object (usha, upsObjects, upsTraps) name from usha to ushap
|
||
|
---
|
||
|
--- v1.02 30-Oct-2001 Kenneth/Allion
|
||
|
--- 1. Import PositiveInteger and NonNegativeInteger from RFC-1628.
|
||
|
--- 2. Fixed: The final item of SYNTAX must not have a comma ending.
|
||
|
--- 3. Correct upsInputmandatory to upsInputCurrent.
|
||
|
--- 4. Correct upsOutputmandatory to upsOutputCurrent.
|
||
|
--- 5. Correct upsBypassmandatory to upsBypassCurrent.
|
||
|
--- 6. Fixed: SYNTAX "DisplayString" must use "SIZE()" to define its range
|
||
|
--- 7. Change BatteryTestScheduleEntry to UpsBatteryTestScheduleEntry
|
||
|
--- 8. Fixed some SYNTAX error :
|
||
|
--- Exp: Change "SYNTAX upsControlWeeklyScheduleEntry" to "SYNTAX
|
||
|
--- UpsControlWeeklyScheduleEntry". And it can avoid conflict
|
||
|
--- between names.
|
||
|
---
|
||
|
--- v1.03 28-Dec-2001 Johnny/Allion
|
||
|
--- 1. Add Simplified Chinese support for agentConfigDefaultLanguage
|
||
|
---
|
||
|
--- v1.04 03-Jan-2002 Johnny/Allion
|
||
|
--- 1. Fixed some typo
|
||
|
---
|
||
|
--- v1.05 16-Jul-2003 Johnny/Ingrasys
|
||
|
--- 1. Fixed errors of
|
||
|
--- "mconfigUnmpEvent" for "upsBatteryTestScheduleEntry"
|
||
|
--- "mconfigUnmpEvent" for "shutdownParametersEntry"
|
||
|
--- "mconfigScheduleIndex" for "upsControlWeeklyScheduleEntry"
|
||
|
--- "mconfigScheduleIndex" for "upsControlSpecialScheduleEntry"
|
||
|
---
|
||
|
--- 2. Change "read/write" to "read-write" of Access table for
|
||
|
--- some NMS which may not accept '/' within MIB file.
|
||
|
---
|
||
|
--- v2.00b1 20-Feb-2004 Johnny/Ingrasys
|
||
|
--- 1. Add EMD support, include emdStatus, emdConfig, and traps
|
||
|
---
|
||
|
---
|
||
|
--- v2.01 16-Jul-2004 Johnny/Ingrasys
|
||
|
--- 1. Change all traps Enterprise from ushap to upsTraps
|
||
|
---
|
||
|
---
|
||
|
--- v2.02 05-Jan-2007 Kevin/Ingrasys
|
||
|
--- 1. Modified MIB error issuse for http://www.simpleweb.org/ietf/mibs/validate/ web site
|
||
|
--- 2. Included RFC1628.MIB
|
||
|
---
|
||
|
--- v2.03 5-Jan-2007 Kevin/Ingrasys
|
||
|
--- 1. Modified MIB error issue for http://www.simpleweb.org/ietf/mibs/validate/ web side.
|
||
|
---
|
||
|
--- v2.04 20-Sep-2007 Kevin/Ingrasys
|
||
|
--- 1. Added IpAddress type.
|
||
|
---
|
||
|
--- v2.05 23-Jan-2008 Kenneth/Ingrasys
|
||
|
--- 1. Add upsBatteryTestScheduleSpecialDay and upsBatteryTestScheduleTestWithTime to upsBatteryTestScheduleTable.
|
||
|
--- 2. Add emdTemperatureOverThreshold(7), emdAlarm1(8) and emdAlarm2(9) to upsControlEvent.
|
||
|
--- 3. Add timeOfConnectionTime and timeOfConnectionTimeout to upsDevicesTable.
|
||
|
--- 4. Change "allion" string to "ingrasys".
|
||
|
--- 5. change for http://wwwsnmp.cs.utwente.nl/ietf/mibs/validate/ Level:4
|
||
|
--- 6. Change "shutdownParametersEntry/ShutdownParametersEntry" strings to "upsControlShutdownParametersEntry/UpsControlShutdownParametersEntry".
|
||
|
---
|
||
|
--- v2.06 04-Feb-2008 Figo/Ingrasys
|
||
|
--- 1. Fixed MIB Object description(upsControlWeeklyShutdownTime upsControlWeeklyRestartTime upsControlSpecialShutdownTime upsControlSpecialRestartTime) to hh:mm format.
|
||
|
---
|
||
|
--- v2.07 25-Feb-2008 Figo/Ingrasys
|
||
|
--- 1. Change upsBatteryTestScheduleTable order list.
|
||
|
---
|
||
|
--- v2.08 30-May-2008 Figo/Ingrasys
|
||
|
--- 1. Fixed upsBatteryGroupSecondsOnBattery DESCRIPTION"0 shall be returned if the unit is not on battery power.".
|
||
|
---
|
||
|
--- v2.09 02-Sep-2008 Figo/Ingrasys
|
||
|
--- 1. Change "ushaUpsOverTemperature" and "ushaUpsOverLoad" trap level from "WARNING" to "SEVERE".
|
||
|
--- 2. Add Q6 warning code definition in trap group.
|
||
|
---
|
||
|
--- v2.10 16-Sep-2008 Figo/Ingrasys
|
||
|
--- 1. Rearrange order for Q6 warning code in trap group.
|
||
|
--- 2. Define Q6 warning code recover trap.
|
||
|
---
|
||
|
--- v2.11 23-Sep-2008 Figo/Ingrasys
|
||
|
--- 1. Modified trap1~38 description in coincidence with FW.
|
||
|
---
|
||
|
|
||
|
USHA-MIB DEFINITIONS ::= BEGIN
|
||
|
|
||
|
IMPORTS
|
||
|
enterprises,Counter,IpAddress
|
||
|
FROM RFC1155-SMI
|
||
|
OBJECT-TYPE
|
||
|
FROM RFC-1212
|
||
|
DisplayString
|
||
|
FROM RFC1213-MIB
|
||
|
TRAP-TYPE
|
||
|
FROM RFC-1215
|
||
|
PositiveInteger,NonNegativeInteger
|
||
|
FROM UPS-MIB;
|
||
|
|
||
|
ingrasys OBJECT IDENTIFIER ::= { enterprises 2468 }
|
||
|
product OBJECT IDENTIFIER ::= { ingrasys 1 }
|
||
|
upsAgent OBJECT IDENTIFIER ::= { product 2 }
|
||
|
ushap OBJECT IDENTIFIER ::= { upsAgent 1 }
|
||
|
upsObjectGroup OBJECT IDENTIFIER ::= { ushap 1 }
|
||
|
upsTrapGroup OBJECT IDENTIFIER ::= { ushap 2 }
|
||
|
|
||
|
upsIdentGroup OBJECT IDENTIFIER ::= { upsObjectGroup 1 }
|
||
|
upsBatteryGroup OBJECT IDENTIFIER ::= { upsObjectGroup 2 }
|
||
|
upsInputGroup OBJECT IDENTIFIER ::= { upsObjectGroup 3 }
|
||
|
upsOutputGroup OBJECT IDENTIFIER ::= { upsObjectGroup 4 }
|
||
|
upsBypassGroup OBJECT IDENTIFIER ::= { upsObjectGroup 5 }
|
||
|
upsTestGroup OBJECT IDENTIFIER ::= { upsObjectGroup 6 }
|
||
|
upsControlGroup OBJECT IDENTIFIER ::= { upsObjectGroup 7 }
|
||
|
upsConfigGroup OBJECT IDENTIFIER ::= { upsObjectGroup 8 }
|
||
|
upsClients OBJECT IDENTIFIER ::= { upsObjectGroup 9 }
|
||
|
agentConfig OBJECT IDENTIFIER ::= { upsObjectGroup 10 }
|
||
|
emdStatus OBJECT IDENTIFIER ::= { upsObjectGroup 11 }
|
||
|
emdConfig OBJECT IDENTIFIER ::= { upsObjectGroup 12 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- upsIdentification
|
||
|
--
|
||
|
-- All objects in this group except for upsIdentGroupName and
|
||
|
-- upsIdentGroupAttachedDevices are set at device initialization
|
||
|
-- and remain static.
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsIdentGroupManufacturer OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..31))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name of the UPS manufacturer."
|
||
|
::= { upsIdentGroup 1 }
|
||
|
|
||
|
upsIdentGroupModel OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..63))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The UPS Model designation."
|
||
|
::= { upsIdentGroup 2 }
|
||
|
|
||
|
upsIdentGroupUPSFirmwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (0..63))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The UPS firmware/software version(s). This variable
|
||
|
may or may not have the same value as
|
||
|
upsIdentGroupAgentSoftwareVersion in some implementations."
|
||
|
::= { upsIdentGroup 3 }
|
||
|
|
||
|
upsIdentGroupAgentSoftwareVersion OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..31))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The USHA software/firmware version. This variable may or
|
||
|
may not have the same value as
|
||
|
upsIdentGroupUPSSoftwareVersion in some implementations."
|
||
|
::= { upsIdentGroup 4 }
|
||
|
|
||
|
upsIdentGroupName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..31))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A string identifying the UPS. This object should be
|
||
|
set by the administrator."
|
||
|
::= { upsIdentGroup 5 }
|
||
|
|
||
|
upsIdentGroupAttachedDevices OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..63))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A string identifying the devices attached to the
|
||
|
output(s) of the UPS. This object should be set by
|
||
|
the administrator."
|
||
|
::= { upsIdentGroup 6 }
|
||
|
|
||
|
upsIdentGroupUpsSerialNumber OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..15))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The UPS serial no."
|
||
|
::= { upsIdentGroup 7 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- upsBatteryGroup
|
||
|
--
|
||
|
-- The Battery group.
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsBatteryGroupStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(1),
|
||
|
batteryNormal(2),
|
||
|
batteryLow(3),
|
||
|
batteryDepleted(4),
|
||
|
batteryDischarging(5),
|
||
|
batteryFailure(6)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The indication of the status in the UPS system's batteries."
|
||
|
::= { upsBatteryGroup 1 }
|
||
|
|
||
|
upsBatteryGroupSecondsOnBattery OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"If the unit is on battery power, the elapsed time
|
||
|
since the UPS last switched to battery power, or the
|
||
|
time since the network management subsystem was last
|
||
|
restarted, whichever is less. 0 shall be returned
|
||
|
if the unit is not on battery power."
|
||
|
::= { upsBatteryGroup 2 }
|
||
|
|
||
|
upsBatteryGroupEstimatedMinutesRemaining OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"An estimate of the time to battery charge depletion
|
||
|
under the present load conditions if the utility power
|
||
|
is off and remains off, or if it were to be lost and
|
||
|
remain off."
|
||
|
::= { upsBatteryGroup 3 }
|
||
|
|
||
|
upsBatteryGroupEstimatedChargeRemaining OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"An estimate of the battery charge remaining expressed
|
||
|
as a percent of full charge."
|
||
|
::= { upsBatteryGroup 4 }
|
||
|
|
||
|
upsBatteryGroupVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The magnitude of the present battery voltage in 0.1 Volt DC."
|
||
|
::= { upsBatteryGroup 5 }
|
||
|
|
||
|
upsBatteryGroupMandatory OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
-- "0.1 Amp DC"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present battery mandatory."
|
||
|
::= { upsBatteryGroup 6 }
|
||
|
|
||
|
upsBatteryGroupTemperature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
-- "degrees 0.1 Centigrade"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The ambient temperature at or near the UPS Battery
|
||
|
casing."
|
||
|
::= { upsBatteryGroup 7 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- upsInputGroup
|
||
|
--
|
||
|
-- Input group.
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsInputGroupLineBads OBJECT-TYPE
|
||
|
SYNTAX Counter
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A count of the number of times the input entered an
|
||
|
out-of-tolerance condition as defined by the
|
||
|
manufacturer. This count is incremented by one each
|
||
|
time the input transitions from zero out-of-tolerance
|
||
|
lines to one or more input lines out-of-tolerance."
|
||
|
::= { upsInputGroup 1 }
|
||
|
|
||
|
upsInputGroupNumLines OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The number of input lines utilized in this device.
|
||
|
This variable indicates the number of rows in the
|
||
|
input table."
|
||
|
::= { upsInputGroup 2 }
|
||
|
|
||
|
upsInputGroupTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsInputGroupEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of input table entries. The number of entries
|
||
|
is given by the value of upsInputGroupNumLines."
|
||
|
::= { upsInputGroup 3 }
|
||
|
|
||
|
upsInputGroupEntry OBJECT-TYPE
|
||
|
SYNTAX UpsInputGroupEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"An entry containing information applicable to a
|
||
|
particular input line."
|
||
|
INDEX { upsInputGroupLineIndex }
|
||
|
::= { upsInputGroupTable 1 }
|
||
|
|
||
|
UpsInputGroupEntry ::=
|
||
|
SEQUENCE {
|
||
|
upsInputGroupLineIndex PositiveInteger,
|
||
|
upsInputGroupFrequency NonNegativeInteger,
|
||
|
upsInputGroupVoltage NonNegativeInteger,
|
||
|
upsInputGroupCurrent NonNegativeInteger,
|
||
|
upsInputGroupTruePower NonNegativeInteger,
|
||
|
upsInputGroupVoltageMax NonNegativeInteger,
|
||
|
upsInputGroupVoltageMin NonNegativeInteger
|
||
|
}
|
||
|
|
||
|
upsInputGroupLineIndex OBJECT-TYPE
|
||
|
SYNTAX PositiveInteger (0..65535)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index of UpsInputGroupEntry."
|
||
|
::= { upsInputGroupEntry 1 }
|
||
|
|
||
|
upsInputGroupFrequency OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
-- "0.1 Hertz"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present input frequency."
|
||
|
::= { upsInputGroupEntry 2 }
|
||
|
|
||
|
upsInputGroupVoltage OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The input utility line voltage in 0.1 volts."
|
||
|
::= { upsInputGroupEntry 3 }
|
||
|
|
||
|
upsInputGroupCurrent OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The magnitude of the present input current in 0.1 A."
|
||
|
::= { upsInputGroupEntry 4 }
|
||
|
|
||
|
upsInputGroupTruePower OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
-- "Watts"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The magnitude of the present input true power."
|
||
|
::= { upsInputGroupEntry 5 }
|
||
|
|
||
|
upsInputGroupVoltageMax OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The maximum utility line voltage in 0.1 VAC for last 1 minute."
|
||
|
::= { upsInputGroupEntry 6 }
|
||
|
|
||
|
upsInputGroupVoltageMin OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The minimum utility line voltage in 0.1 VAC for last 1 minute."
|
||
|
::= { upsInputGroupEntry 7 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- upsOutputGroup
|
||
|
--
|
||
|
-- Output group
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsOutputGroupSource OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
other(1),
|
||
|
none(2),
|
||
|
normal(3),
|
||
|
bypass(4),
|
||
|
battery(5),
|
||
|
booster(6),
|
||
|
reducer(7)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present source of output power. The enumeration
|
||
|
none(2) indicates that there is no source of output
|
||
|
power (and therefore no output power), for example,
|
||
|
the system has opened the output breaker."
|
||
|
::= { upsOutputGroup 1 }
|
||
|
|
||
|
upsOutputGroupFrequency OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The current output frequency of the UPS system in 0.1 of HZ."
|
||
|
::= { upsOutputGroup 2 }
|
||
|
|
||
|
upsOutputGroupNumLines OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The number of output lines utilized in this device.
|
||
|
This variable indicates the number of rows in the
|
||
|
output table."
|
||
|
::= { upsOutputGroup 3 }
|
||
|
|
||
|
upsOutputGroupTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsOutputGroupEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of output table entries. The number of
|
||
|
entries is given by the value of upsOutputGroupNumLines."
|
||
|
::= { upsOutputGroup 4 }
|
||
|
|
||
|
upsOutputGroupEntry OBJECT-TYPE
|
||
|
SYNTAX UpsOutputGroupEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"An entry containing information applicable to a
|
||
|
particular output line."
|
||
|
INDEX { upsOutputGroupLineIndex }
|
||
|
::= { upsOutputGroupTable 1 }
|
||
|
|
||
|
UpsOutputGroupEntry ::=
|
||
|
SEQUENCE {
|
||
|
upsOutputGroupLineIndex PositiveInteger,
|
||
|
upsOutputGroupVoltage NonNegativeInteger,
|
||
|
upsOutputGroupCurrent NonNegativeInteger,
|
||
|
upsOutputGroupPower NonNegativeInteger,
|
||
|
upsOutputGroupPercentLoad INTEGER
|
||
|
}
|
||
|
|
||
|
upsOutputGroupLineIndex OBJECT-TYPE
|
||
|
SYNTAX PositiveInteger (0..65535)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The output line identifier."
|
||
|
::= { upsOutputGroupEntry 1 }
|
||
|
|
||
|
upsOutputGroupVoltage OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The output voltage of the UPS system in 0.1 volts."
|
||
|
::= { upsOutputGroupEntry 2 }
|
||
|
|
||
|
upsOutputGroupCurrent OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The output current of the UPS system in 0.1 Amps."
|
||
|
::= { upsOutputGroupEntry 3 }
|
||
|
|
||
|
upsOutputGroupPower OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
-- "Watts"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present output true power."
|
||
|
::= { upsOutputGroupEntry 4 }
|
||
|
|
||
|
upsOutputGroupPercentLoad OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The percentage of the UPS power capacity presently
|
||
|
being used on this output line, i.e., the greater of
|
||
|
the percent load of true power capacity and the
|
||
|
percent load of VA."
|
||
|
::= { upsOutputGroupEntry 5 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- upsBypassGroup
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsBypassGroupFrequency OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present bypass frequency."
|
||
|
::= { upsBypassGroup 1 }
|
||
|
|
||
|
upsBypassGroupNumLines OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The number of bypass lines utilized in this device.
|
||
|
This entry indicates the number of rows in the bypass
|
||
|
table."
|
||
|
::= { upsBypassGroup 2 }
|
||
|
|
||
|
upsBypassGroupTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsBypassGroupEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of bypass table entries. The number of
|
||
|
entries is given by the value of upsBypassGroupNumLines."
|
||
|
::= { upsBypassGroup 3 }
|
||
|
|
||
|
upsBypassGroupEntry OBJECT-TYPE
|
||
|
SYNTAX UpsBypassGroupEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"An entry containing information applicable to a
|
||
|
particular bypass input."
|
||
|
INDEX { upsBypassGroupLineIndex }
|
||
|
::= { upsBypassGroupTable 1 }
|
||
|
|
||
|
UpsBypassGroupEntry ::=
|
||
|
SEQUENCE {
|
||
|
upsBypassGroupLineIndex PositiveInteger,
|
||
|
upsBypassGroupVoltage NonNegativeInteger,
|
||
|
upsBypassGroupCurrent NonNegativeInteger,
|
||
|
upsBypassGroupPower NonNegativeInteger
|
||
|
}
|
||
|
|
||
|
upsBypassGroupLineIndex OBJECT-TYPE
|
||
|
SYNTAX PositiveInteger (0..65535)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The bypass line identifier."
|
||
|
::= { upsBypassGroupEntry 1 }
|
||
|
|
||
|
upsBypassGroupVoltage OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present bypass voltage."
|
||
|
::= { upsBypassGroupEntry 2 }
|
||
|
|
||
|
upsBypassGroupCurrent OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present bypass current."
|
||
|
::= { upsBypassGroupEntry 3 }
|
||
|
|
||
|
upsBypassGroupPower OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
-- "Watts"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The present true power conveyed by the bypass."
|
||
|
::= { upsBypassGroupEntry 4 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- upsTestGroup
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsTestBatteryTestSettingTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The object specify the test time for battery test."
|
||
|
::= { upsTestGroup 1 }
|
||
|
|
||
|
upsBatteryTest OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
none(1),
|
||
|
battTest10sec(2),
|
||
|
battTestUntilLow(3),
|
||
|
battTestWithTime(4),
|
||
|
battTestCancelTest(5),
|
||
|
battTestClearInfo(6)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"This object specify the battery test type and initiate
|
||
|
battery test. If battTestWithTime selected, the test
|
||
|
time is refer to upsTestBatteryTestTime."
|
||
|
::= { upsTestGroup 2 }
|
||
|
|
||
|
upsTestBatteryTestResult OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
donePassed(1),
|
||
|
doneWarning(2),
|
||
|
doneError(3),
|
||
|
aborted(4),
|
||
|
inProgress(5),
|
||
|
noTestsInitiated(6)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The results of the current or last UPS diagnostics
|
||
|
test performed. The values for donePassed(1),
|
||
|
doneWarning(2), and doneError(3) indicate that the
|
||
|
test completed either successfully, with a warning, or
|
||
|
with an error, respectively. The value aborted(4) is
|
||
|
returned for tests which are aborted by setting the
|
||
|
value of upsTestId to upsTestAbortTestInProgress.
|
||
|
Tests which have not yet concluded are indicated by
|
||
|
inProgress(5). The value noTestsInitiated(6)
|
||
|
indicates that no previous test results are available,
|
||
|
such as is the case when no tests have been run since
|
||
|
the last reinitialization of the network management
|
||
|
subsystem and the system has no provision for non-
|
||
|
volatile storage of test results."
|
||
|
::= { upsTestGroup 3 }
|
||
|
|
||
|
upsTestBatteryTestStartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(1..19))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The value of the time the test in progress was initiated,
|
||
|
or, if no test is in progress, the time the previous test
|
||
|
was initiated. If the value of upsTestBatteryTestResult
|
||
|
is noTestsInitiated(6), upsTestStartTime has the value
|
||
|
01/01/1970 00:00:00."
|
||
|
::= { upsTestGroup 4 }
|
||
|
|
||
|
upsTestBatteryTestElapsedTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(11..11))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The amount of time, in TimeTicks, since the test in
|
||
|
progress was initiated, or, if no test is in progress,
|
||
|
the previous test took to complete. If the value of
|
||
|
upsTestResultsSummary is noTestsInitiated(6),
|
||
|
upsTestElapsedTime has the value 00:00:00.00."
|
||
|
::= { upsTestGroup 5 }
|
||
|
|
||
|
upsBatteryTestScheduleTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsBatteryTestScheduleEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Table which describes the schedule for automatically battery
|
||
|
test."
|
||
|
::= { upsTestGroup 6 }
|
||
|
|
||
|
upsBatteryTestScheduleEntry OBJECT-TYPE
|
||
|
SYNTAX UpsBatteryTestScheduleEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION ""
|
||
|
INDEX { upsBatteryTestScheduleIndex }
|
||
|
::= { upsBatteryTestScheduleTable 1 }
|
||
|
|
||
|
UpsBatteryTestScheduleEntry ::= SEQUENCE {
|
||
|
upsBatteryTestScheduleIndex
|
||
|
INTEGER,
|
||
|
upsBatteryTestScheduleDay
|
||
|
INTEGER,
|
||
|
upsBatteryTestScheduleTime
|
||
|
DisplayString,
|
||
|
upsBatteryTestScheduleType
|
||
|
INTEGER,
|
||
|
upsBatteryTestScheduleTestWithTime
|
||
|
INTEGER,
|
||
|
upsBatteryTestScheduleSpecialDay
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
upsBatteryTestScheduleIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (0..65535)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index of battery test scheduled."
|
||
|
::= { upsBatteryTestScheduleEntry 1 }
|
||
|
|
||
|
upsBatteryTestScheduleDay OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
sunday(1),
|
||
|
monday(2),
|
||
|
tuesday(3),
|
||
|
wednesday(4),
|
||
|
thursday(5),
|
||
|
friday(6),
|
||
|
saturday(7),
|
||
|
specialDay(8),
|
||
|
none(9)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The weekday on which the UPS should start battery test."
|
||
|
::= { upsBatteryTestScheduleEntry 2 }
|
||
|
|
||
|
upsBatteryTestScheduleTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(5..5))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time that the battery test will be initiated in hh:mm format."
|
||
|
::= { upsBatteryTestScheduleEntry 3 }
|
||
|
|
||
|
upsBatteryTestScheduleType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
none(1),
|
||
|
battTest10sec(2),
|
||
|
battTestUntilLow(3),
|
||
|
battTestWithTime(4)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The type of battery test."
|
||
|
::= { upsBatteryTestScheduleEntry 4 }
|
||
|
|
||
|
upsBatteryTestScheduleTestWithTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
supported(1),
|
||
|
notSupported(2)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The battTestWithTime of battery test is supported or not."
|
||
|
::= { upsBatteryTestScheduleEntry 5 }
|
||
|
|
||
|
upsBatteryTestScheduleSpecialDay OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(10..10))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The special day that the battery test will be initiated in dd/mm/yyyy format."
|
||
|
::= { upsBatteryTestScheduleEntry 6 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- upsControlGroup
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsControlUpsShutdownDelay OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The delay in seconds the UPS remains on after being told
|
||
|
to turn off."
|
||
|
::= { upsControlGroup 1 }
|
||
|
|
||
|
upsControlUpsSleepTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time in minutes for the UPS to go to sleep when
|
||
|
instructed. When in sleep mode, the UPS will not provide
|
||
|
output power regardless of the input line state. Once the
|
||
|
specified time has elapsed, output power will be restored.
|
||
|
|
||
|
This is a configuration setting. The UPS will not go to
|
||
|
sleep until told to do so by the manager from a management
|
||
|
station.
|
||
|
|
||
|
Any input value is allowed, however the UPS only recognizes
|
||
|
0 - 9999 minutes in one minute increments.
|
||
|
|
||
|
If the provided value is higher than the highest acceptable
|
||
|
value, the highest acceptable value is used."
|
||
|
::= { upsControlGroup 2 }
|
||
|
|
||
|
upsControlUpsOnOffControl OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
turnUpsOff(1),
|
||
|
putUpsToSleep(2),
|
||
|
turnOnUpsOrCancelShutdown(3),
|
||
|
none(4)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Setting this variable to control UPS output status.
|
||
|
turnUpsOff(1) will set UPS turn off output after
|
||
|
upsControlUpsShutdownDelay period expired.
|
||
|
putUpsToSleep(2) will set UPS turn off output after
|
||
|
upsControlUpsShutdownDelay period expired, UPS output
|
||
|
will stay off with the period defined by
|
||
|
upsControlUpsSleepTime, then turn output on.
|
||
|
turnOnUpsOrCancelShutdown(3) can used to turn on UPS
|
||
|
output, or cancel any shutdown process."
|
||
|
::= { upsControlGroup 3 }
|
||
|
|
||
|
upsControlShutdownParametersTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsControlShutdownParametersEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Table which describes the parametes for shutdown process
|
||
|
when shutdown event occurs"
|
||
|
::= { upsControlGroup 4 }
|
||
|
|
||
|
upsControlShutdownParametersEntry OBJECT-TYPE
|
||
|
SYNTAX UpsControlShutdownParametersEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION ""
|
||
|
INDEX { upsControlEvent }
|
||
|
::= { upsControlShutdownParametersTable 1 }
|
||
|
|
||
|
UpsControlShutdownParametersEntry ::= SEQUENCE {
|
||
|
upsControlEvent INTEGER,
|
||
|
upsControlEventStatus INTEGER,
|
||
|
upsControlDelay INTEGER,
|
||
|
upsControlFirstWarning INTEGER,
|
||
|
upsControlWarningInterval INTEGER
|
||
|
}
|
||
|
|
||
|
upsControlEvent OBJECT-TYPE
|
||
|
-- SYNTAX DisplayString
|
||
|
SYNTAX INTEGER {
|
||
|
acFail(1),
|
||
|
batteryLow (2),
|
||
|
upsOverload (3),
|
||
|
upsOverTempeature (4),
|
||
|
weeklySchedule (5),
|
||
|
specialDaySchedule (6),
|
||
|
emdTemperatureOverThreshold (7),
|
||
|
emdAlarm1 (8),
|
||
|
emdAlarm2 (9)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" The shutdown event identification "
|
||
|
::= { upsControlShutdownParametersEntry 1 }
|
||
|
|
||
|
upsControlEventStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
-- enable(1),
|
||
|
-- disable(2)
|
||
|
disable(1),
|
||
|
warning(2),
|
||
|
clientShutdown(3),
|
||
|
upsTurnOff(4)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Status of the corresponding shutdown Event.
|
||
|
When set to disable(), shutdown process will not start when
|
||
|
corresponding event occured."
|
||
|
::= { upsControlShutdownParametersEntry 2 }
|
||
|
|
||
|
upsControlDelay OBJECT-TYPE
|
||
|
SYNTAX INTEGER (0..10080)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The Delay after the occurance of the curresponding shutdown
|
||
|
event that USHA should issue shutdown request to
|
||
|
connected clients. For WeeklyScheduledShutdown and
|
||
|
SpecialScheduledShutdown, this is the time before the
|
||
|
configured Shutdowntime when USHA will start sending the
|
||
|
warning message to the connected clients. The value is in
|
||
|
units of minutes."
|
||
|
::= { upsControlShutdownParametersEntry 3 }
|
||
|
|
||
|
upsControlFirstWarning OBJECT-TYPE
|
||
|
SYNTAX INTEGER (0..3600)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The delay after the occurance of the curresponding shutdown
|
||
|
event that the USHA will start sending the warning
|
||
|
message to the connected clients. The value is in units of
|
||
|
seconds"
|
||
|
::= { upsControlShutdownParametersEntry 4 }
|
||
|
|
||
|
upsControlWarningInterval OBJECT-TYPE
|
||
|
SYNTAX INTEGER (0..3600)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The frequency of sending warning messages to the connected
|
||
|
clients when the curresponding shutdown event occurs.
|
||
|
The value is in units of seconds."
|
||
|
::= { upsControlShutdownParametersEntry 5 }
|
||
|
|
||
|
upsControlWeeklyScheduleTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsControlWeeklyScheduleEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The table to schedule shutting down the ups by weekly."
|
||
|
::= { upsControlGroup 5 }
|
||
|
|
||
|
upsControlWeeklyScheduleEntry OBJECT-TYPE
|
||
|
SYNTAX UpsControlWeeklyScheduleEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The entries for each day."
|
||
|
INDEX { upsControlWeeklyIndex }
|
||
|
::= {upsControlWeeklyScheduleTable 1 }
|
||
|
|
||
|
UpsControlWeeklyScheduleEntry ::= SEQUENCE {
|
||
|
upsControlWeeklyIndex
|
||
|
INTEGER,
|
||
|
upsControlWeeklyShutdownDay
|
||
|
INTEGER,
|
||
|
upsControlWeeklyShutdownTime
|
||
|
DisplayString,
|
||
|
upsControlWeeklyRestartDay
|
||
|
INTEGER,
|
||
|
upsControlWeeklyRestartTime
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
upsControlWeeklyIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (0..65535)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index of scheduled events."
|
||
|
::= { upsControlWeeklyScheduleEntry 1 }
|
||
|
|
||
|
upsControlWeeklyShutdownDay OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
sunday(1),
|
||
|
monday(2),
|
||
|
tuesday(3),
|
||
|
wednesday(4),
|
||
|
thursday(5),
|
||
|
friday(6),
|
||
|
saturday(7),
|
||
|
none(8)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The weekday on which the UPS should shut down."
|
||
|
::= { upsControlWeeklyScheduleEntry 2 }
|
||
|
|
||
|
upsControlWeeklyShutdownTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(5..5))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time that the process of shutting down the UPS will be initiated
|
||
|
in hh:mm format."
|
||
|
::= { upsControlWeeklyScheduleEntry 3 }
|
||
|
|
||
|
upsControlWeeklyRestartDay OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
sunday(1),
|
||
|
monday(2),
|
||
|
tuesday(3),
|
||
|
wednesday(4),
|
||
|
thursday(5),
|
||
|
friday(6),
|
||
|
saturday(7),
|
||
|
none(8)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The weekday on which the UPS should restart"
|
||
|
|
||
|
::= { upsControlWeeklyScheduleEntry 4 }
|
||
|
|
||
|
upsControlWeeklyRestartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(5..5))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time the UPS will restart in hh:mm format."
|
||
|
::= { upsControlWeeklyScheduleEntry 5 }
|
||
|
|
||
|
upsControlSpecialScheduleTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsControlSpecialScheduleEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The table to schedule shutting down the ups."
|
||
|
::= { upsControlGroup 6 }
|
||
|
|
||
|
upsControlSpecialScheduleEntry OBJECT-TYPE
|
||
|
SYNTAX UpsControlSpecialScheduleEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The entries for each day."
|
||
|
INDEX { upsControlSpecialIndex }
|
||
|
::= {upsControlSpecialScheduleTable 1 }
|
||
|
|
||
|
UpsControlSpecialScheduleEntry ::= SEQUENCE {
|
||
|
upsControlSpecialIndex
|
||
|
INTEGER,
|
||
|
upsControlSpecialShutdownDay
|
||
|
DisplayString,
|
||
|
upsControlSpecialShutdownTime
|
||
|
DisplayString,
|
||
|
upsControlSpecialRestartDay
|
||
|
DisplayString,
|
||
|
upsControlSpecialRestartTime
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
upsControlSpecialIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (0..65535)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index of scheduled events."
|
||
|
::= { upsControlSpecialScheduleEntry 1 }
|
||
|
|
||
|
upsControlSpecialShutdownDay OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(10..10))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The date on which the UPS should shut down in dd/mm/yyyy
|
||
|
format."
|
||
|
::= { upsControlSpecialScheduleEntry 2 }
|
||
|
|
||
|
upsControlSpecialShutdownTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(5..5))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time that the process of shutting down the UPS will be initiated
|
||
|
in hh:mm format"
|
||
|
::= { upsControlSpecialScheduleEntry 3 }
|
||
|
|
||
|
upsControlSpecialRestartDay OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(10..10))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The date on which the UPS should restart in dd/mm/yyyy format"
|
||
|
|
||
|
::= { upsControlSpecialScheduleEntry 4 }
|
||
|
|
||
|
upsControlSpecialRestartTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(5..5))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time the UPS will restart in hh:mm format."
|
||
|
::= { upsControlSpecialScheduleEntry 5 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- upsConfigGroup
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsConfigGroupInputVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The magnitude of the nominal input voltage. On those
|
||
|
systems which support read-write access to this
|
||
|
object, if there is an attempt to set this variable to
|
||
|
a value that is not supported, the request must be
|
||
|
rejected and the agent shall respond with an
|
||
|
appropriate error message, i.e., badValue for SNMPv1,
|
||
|
or inconsistentValue for SNMPv2."
|
||
|
::= { upsConfigGroup 1 }
|
||
|
|
||
|
upsConfigGroupInputFreq OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The nominal input frequency. On those systems which
|
||
|
support read-write access to this object, if there is
|
||
|
an attempt to set this variable to a value that is not
|
||
|
supported, the request must be rejected and the agent
|
||
|
shall respond with an appropriate error message, i.e.,
|
||
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
||
|
::= { upsConfigGroup 2 }
|
||
|
|
||
|
upsConfigGroupOutputVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The magnitude of the nominal output voltage. On
|
||
|
those systems which support read-write access to this
|
||
|
object, if there is an attempt to set this variable to
|
||
|
a value that is not supported, the request must be
|
||
|
rejected and the agent shall respond with an
|
||
|
appropriate error message, i.e., badValue for SNMPv1,
|
||
|
or inconsistentValue for SNMPv2."
|
||
|
::= { upsConfigGroup 3 }
|
||
|
|
||
|
upsConfigGroupOutputFreq OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The nominal output frequency. On those systems which
|
||
|
support read-write access to this object, if there is
|
||
|
an attempt to set this variable to a value that is not
|
||
|
supported, the request must be rejected and the agent
|
||
|
shall respond with an appropriate error message, i.e.,
|
||
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
||
|
::= { upsConfigGroup 4 }
|
||
|
|
||
|
upsConfigGroupOutputVA OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
-- "Volt-Amps"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The magnitude of the nominal Volt-Amp rating."
|
||
|
::= { upsConfigGroup 5 }
|
||
|
|
||
|
upsConfigGroupOutputPower OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
-- "Watts"
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The magnitude of the nominal true power rating."
|
||
|
::= { upsConfigGroup 6 }
|
||
|
|
||
|
upsConfigGroupOverTemperatureSetPoint OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger (10..70)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The maximum temperature allowed before the UPS
|
||
|
operation temperature is too high."
|
||
|
::= { upsConfigGroup 7 }
|
||
|
|
||
|
upsConfigGroupOverLoadSetPoint OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger (0..120)
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The maximum output load allowed before the load is
|
||
|
too high for UPS operation."
|
||
|
::= { upsConfigGroup 8 }
|
||
|
|
||
|
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- upsClients
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
upsClientsConnectedNum OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The count of clients which have resgistered for UPS
|
||
|
shutdown control."
|
||
|
::= { upsClients 1 }
|
||
|
|
||
|
upsDevicesTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF UpsDevicesEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The devices powered by UPS and registered to USHA"
|
||
|
-- INDEX { indexOfDevice }
|
||
|
::= { upsClients 2 }
|
||
|
|
||
|
upsDevicesEntry OBJECT-TYPE
|
||
|
SYNTAX UpsDevicesEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The devices protected by USHA"
|
||
|
-- INDEX { trapsIndex}
|
||
|
INDEX { indexOfDevice}
|
||
|
::= { upsDevicesTable 1 }
|
||
|
|
||
|
UpsDevicesEntry ::=
|
||
|
SEQUENCE {
|
||
|
indexOfDevice
|
||
|
NonNegativeInteger,
|
||
|
addrOfDevice
|
||
|
IpAddress,
|
||
|
nameOfDevice
|
||
|
DisplayString,
|
||
|
timeOfConnection
|
||
|
DisplayString,
|
||
|
timeOfConnectionTime
|
||
|
DisplayString,
|
||
|
timeOfConnectionTimeout
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
indexOfDevice OBJECT-TYPE
|
||
|
SYNTAX NonNegativeInteger
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index of the device that is plugged into the UPS."
|
||
|
::= { upsDevicesEntry 1 }
|
||
|
|
||
|
addrOfDevice OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The ip address of the device."
|
||
|
::= { upsDevicesEntry 2 }
|
||
|
|
||
|
nameOfDevice OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..31))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The name/description of the device plugged into the UPS."
|
||
|
::= { upsDevicesEntry 3 }
|
||
|
|
||
|
timeOfConnection OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The device registered to USHA"
|
||
|
::= { upsDevicesEntry 4 }
|
||
|
|
||
|
timeOfConnectionTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The device registered time to USHA."
|
||
|
::= { upsDevicesEntry 5 }
|
||
|
|
||
|
timeOfConnectionTimeout OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The device timeout counter. Unit: 10 seconds"
|
||
|
::= { upsDevicesEntry 6 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- agentConfig
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
agentConfigIpaddress OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" The ip address that NMS can identify the managed
|
||
|
device"
|
||
|
::= { agentConfig 1}
|
||
|
|
||
|
agentConfigGateway OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" The default gateway that allow device managed
|
||
|
through routers "
|
||
|
::= { agentConfig 2}
|
||
|
|
||
|
agentConfigSubnetMask OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" Internet address subnet mask"
|
||
|
::= { agentConfig 3}
|
||
|
|
||
|
agentConfigDate OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (10..10))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The date in agent, format is (dd/mm/yyyy)"
|
||
|
::= { agentConfig 4}
|
||
|
|
||
|
agentConfigTime OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (8..8))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time in agent, format is (hh:mm:ss)"
|
||
|
::= { agentConfig 5}
|
||
|
|
||
|
agentConfigPrimaryTimeServer OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The primary time server is responsible for sending the
|
||
|
correct time to the agent."
|
||
|
::= { agentConfig 6 }
|
||
|
|
||
|
agentConfigSecondaryTimeServer OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The secondary time server is responsible for sending the
|
||
|
correct time to the agent."
|
||
|
::= { agentConfig 7 }
|
||
|
|
||
|
agentConfigHistoryLogFrequency OBJECT-TYPE
|
||
|
SYNTAX INTEGER (5..28800) -- in seconds
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The frequency of the updation of the history log. The value
|
||
|
is in seconds"
|
||
|
::= { agentConfig 8 }
|
||
|
|
||
|
agentConfigExtHistoryLogFrequency OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..10080) -- in minutes
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The ups parameters are sampled at the rate governed by the
|
||
|
mconfigHistroyLogFrequency. These sampled values are further
|
||
|
conslidated over period of time which is determined by this
|
||
|
object."
|
||
|
::= { agentConfig 9 }
|
||
|
|
||
|
agentConfigPollRate OBJECT-TYPE
|
||
|
SYNTAX INTEGER (1..999) -- in seconds
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
" The frequency that proxy agent polls the connected
|
||
|
UPS in JBUS protocol. (unit : second)"
|
||
|
::= { agentConfig 10}
|
||
|
|
||
|
agentConfigBaudRate OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The serial port communication speed. only 9600 allowed"
|
||
|
::= { agentConfig 11}
|
||
|
|
||
|
agentConfigDhcpStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable DHCP/BootP capability"
|
||
|
::= { agentConfig 12}
|
||
|
|
||
|
agentConfigTelnetStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable telnet access"
|
||
|
::= { agentConfig 13}
|
||
|
|
||
|
agentConfigTftpStatue OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable network upgrade capability"
|
||
|
::= { agentConfig 14}
|
||
|
|
||
|
agentConfigResetToDefault OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
reset(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Reset all parameters of USHA to default value"
|
||
|
::= { agentConfig 15}
|
||
|
|
||
|
agentConfigRestart OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
restart(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Restart USHA"
|
||
|
::= { agentConfig 16}
|
||
|
|
||
|
agentConfigClearAgentLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
clear(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Clear agent log data"
|
||
|
::= { agentConfig 17}
|
||
|
|
||
|
agentConfigClearEventLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
clear(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Clear event log data"
|
||
|
::= { agentConfig 18}
|
||
|
|
||
|
agentConfigClearExtHistoryLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
clear(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Clear extented history log data"
|
||
|
::= { agentConfig 19}
|
||
|
|
||
|
agentConfigClearHistoryLog OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
clear(1),
|
||
|
nothing(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Clear history log data"
|
||
|
::= { agentConfig 20}
|
||
|
|
||
|
agentConfigTrapRetryCount OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The count of repeat traps to send to NMS before trap
|
||
|
acknowledge received."
|
||
|
::= { agentConfig 21}
|
||
|
|
||
|
agentConfigTrapRetryTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The time between retry traps sned to NMS."
|
||
|
::= { agentConfig 22}
|
||
|
|
||
|
agentConfigTrapAckSignature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The signature of trap acknowledge."
|
||
|
::= { agentConfig 23}
|
||
|
|
||
|
agentConfigMibVersion OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The version of MIB spec."
|
||
|
::= { agentConfig 24 }
|
||
|
|
||
|
agentConfigTrapsReceiversTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF AgentConfigTrapsReceiversEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of managers to send traps to. The number of
|
||
|
entries is given by the value of agentConfigNumTrapReceivers"
|
||
|
::= { agentConfig 25}
|
||
|
|
||
|
agentConfigTrapsReceiversEntry OBJECT-TYPE
|
||
|
SYNTAX AgentConfigTrapsReceiversEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The managers to send traps to."
|
||
|
INDEX { trapsIndex}
|
||
|
::= { agentConfigTrapsReceiversTable 1 }
|
||
|
|
||
|
AgentConfigTrapsReceiversEntry ::=
|
||
|
SEQUENCE {
|
||
|
trapsIndex
|
||
|
INTEGER,
|
||
|
trapsReceiverAddr
|
||
|
IpAddress,
|
||
|
receiverCommunityString
|
||
|
DisplayString,
|
||
|
receiverNmsType
|
||
|
INTEGER,
|
||
|
receiverSeverityLevel
|
||
|
INTEGER,
|
||
|
receiverDescription
|
||
|
DisplayString
|
||
|
}
|
||
|
|
||
|
trapsIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER (0..65535)
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index to a trap receiver entry."
|
||
|
::= { agentConfigTrapsReceiversEntry 1 }
|
||
|
|
||
|
trapsReceiverAddr OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The IP address of the manager to send a trap to."
|
||
|
::= { agentConfigTrapsReceiversEntry 2 }
|
||
|
|
||
|
receiverCommunityString OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..19))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The community name to use in the trap when
|
||
|
sent to the manager."
|
||
|
::= { agentConfigTrapsReceiversEntry 3 }
|
||
|
|
||
|
receiverNmsType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
none(1),
|
||
|
rfc1628-trap(2),
|
||
|
usha-trap(3)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The trap group that NMS desired."
|
||
|
::= { agentConfigTrapsReceiversEntry 4 }
|
||
|
|
||
|
receiverSeverityLevel OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
informational(1),
|
||
|
warning(2),
|
||
|
severe(3)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The severity level of traps to be received by this manager."
|
||
|
::= { agentConfigTrapsReceiversEntry 5 }
|
||
|
|
||
|
receiverDescription OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..31))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Description of trap receivers"
|
||
|
::= { agentConfigTrapsReceiversEntry 6 }
|
||
|
|
||
|
agentConfigAccessControlTable OBJECT-TYPE
|
||
|
SYNTAX SEQUENCE OF AgentConfigAccessControlEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"A list of managers which can access USHA with private
|
||
|
community string."
|
||
|
::= { agentConfig 26}
|
||
|
|
||
|
agentConfigAccessControlEntry OBJECT-TYPE
|
||
|
SYNTAX AgentConfigAccessControlEntry
|
||
|
ACCESS not-accessible
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The managers."
|
||
|
INDEX { trapsIndex}
|
||
|
::= { agentConfigAccessControlTable 1 }
|
||
|
|
||
|
AgentConfigAccessControlEntry ::=
|
||
|
SEQUENCE {
|
||
|
accessIndex
|
||
|
INTEGER,
|
||
|
accessControlAddr
|
||
|
IpAddress,
|
||
|
accessCommunityString
|
||
|
DisplayString,
|
||
|
accessControlMode
|
||
|
INTEGER
|
||
|
}
|
||
|
|
||
|
accessIndex OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The index to a access control entry."
|
||
|
::= { agentConfigAccessControlEntry 1 }
|
||
|
|
||
|
accessControlAddr OBJECT-TYPE
|
||
|
SYNTAX IpAddress
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The IP address of the manager to access USHA"
|
||
|
::= { agentConfigAccessControlEntry 2 }
|
||
|
|
||
|
accessCommunityString OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..19))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The community name to use in the manager when
|
||
|
access USHA"
|
||
|
::= { agentConfigAccessControlEntry 3 }
|
||
|
|
||
|
accessControlMode OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
readOnly (1),
|
||
|
readWrite (2),
|
||
|
notAccess (3)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Access type, only read/Write access type can change parameter
|
||
|
of USHA"
|
||
|
::= { agentConfigAccessControlEntry 4 }
|
||
|
|
||
|
agentConfigDefaultLanguage OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
auto(1),
|
||
|
english(2),
|
||
|
traditionalChinese(3),
|
||
|
simplifiedChinese(4)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The default languauge for browser, when set to auto(1)
|
||
|
USHA will send page in the language depends on the
|
||
|
request language of browser."
|
||
|
::= { agentConfig 27 }
|
||
|
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- emdStatus
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
emdSatatusEmdType OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknown(1),
|
||
|
disabled(2),
|
||
|
emdHT(3),
|
||
|
emdT(4)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The type of EMD plugged into the port."
|
||
|
::= { emdStatus 1}
|
||
|
|
||
|
emdSatatusTemperature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The measurement of EMD temperature, in 0.1 degree"
|
||
|
::= { emdStatus 2}
|
||
|
|
||
|
emdSatatusHumidity OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The measurement of EMD humidity, in 0.1 degree"
|
||
|
::= { emdStatus 3}
|
||
|
|
||
|
emdSatatusAlarm1 OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknow(1),
|
||
|
disabled(2),
|
||
|
active(3),
|
||
|
inactive(4)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The EMD alarm-1 status"
|
||
|
::= { emdStatus 4}
|
||
|
|
||
|
emdSatatusAlarm2 OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
unknow(1),
|
||
|
disabled(2),
|
||
|
active(3),
|
||
|
inactive(4)
|
||
|
}
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The EMD alarm-2 status"
|
||
|
::= { emdStatus 5}
|
||
|
|
||
|
|
||
|
-- ===========================================================================
|
||
|
--
|
||
|
-- emdConfig
|
||
|
--
|
||
|
-- ===========================================================================
|
||
|
|
||
|
usahEmdConfigEmdConfig OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
auto(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Enable or disable to detect presence of EMD"
|
||
|
::= { emdConfig 1}
|
||
|
|
||
|
emdConfigEmdName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Description of EMD"
|
||
|
::= { emdConfig 2}
|
||
|
|
||
|
emdConfigTemperature OBJECT IDENTIFIER ::= { emdConfig 3 }
|
||
|
|
||
|
emdConfigTempName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Description of EMD temperature sensor"
|
||
|
::= { emdConfigTemperature 1}
|
||
|
|
||
|
emdConfigTempHighSetPoint OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point for high temperature warning, in degrees"
|
||
|
::= { emdConfigTemperature 2}
|
||
|
|
||
|
emdConfigTempHighStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"To enable/disable high set point check with emd temperature."
|
||
|
::= { emdConfigTemperature 3}
|
||
|
|
||
|
emdConfigTempLowSetPoint OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point for low temperature warning, in degrees"
|
||
|
::= { emdConfigTemperature 4}
|
||
|
|
||
|
emdConfigTempLowStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"To enable/disable low set point check with emd temperature."
|
||
|
::= { emdConfigTemperature 5}
|
||
|
|
||
|
emdConfigTempOffset OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The offset to calibrate temperature of EMD, in degrees"
|
||
|
::= { emdConfigTemperature 6}
|
||
|
|
||
|
emdConfigHumidity OBJECT IDENTIFIER ::= { emdConfig 4 }
|
||
|
|
||
|
emdConfigHumidityName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Description of EMD humidity sensor"
|
||
|
::= { emdConfigHumidity 1}
|
||
|
|
||
|
emdConfigHumidityHighSetPoint OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point for high humidity warning, in %"
|
||
|
::= { emdConfigHumidity 2}
|
||
|
|
||
|
emdConfigHumidityLowStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"To enable/disable high set point check with emd humidity."
|
||
|
::= { emdConfigHumidity 3}
|
||
|
|
||
|
emdConfigHumidityLowSetPoint OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The set point for low humidity warning, in %"
|
||
|
::= { emdConfigHumidity 4}
|
||
|
|
||
|
emdConfigHumidityHighStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
enabled(1),
|
||
|
disabled(2)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"To enable/disable low set point check with emd humidity."
|
||
|
::= { emdConfigHumidity 5}
|
||
|
|
||
|
emdConfigHumidityOffset OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The offset to calibrate humidity of EMD, in %"
|
||
|
::= { emdConfigHumidity 6}
|
||
|
|
||
|
emdConfigAlarm1 OBJECT IDENTIFIER ::= { emdConfig 5 }
|
||
|
|
||
|
emdConfigAlarm1Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Description of EMD alarm-1"
|
||
|
::= { emdConfigAlarm1 1}
|
||
|
|
||
|
emdConfigAlarm1Type OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
nomralOpen(2),
|
||
|
normalClose(3)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The alarm-1 operation type"
|
||
|
::= { emdConfigAlarm1 2 }
|
||
|
|
||
|
emdConfigAlarm2 OBJECT IDENTIFIER ::= { emdConfig 6 }
|
||
|
|
||
|
emdConfigAlarm2Name OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE(0..15))
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Description of EMD alarm-2"
|
||
|
::= { emdConfigAlarm2 1}
|
||
|
|
||
|
emdConfigAlarm2Type OBJECT-TYPE
|
||
|
SYNTAX INTEGER {
|
||
|
disabled(1),
|
||
|
nomralOpen(2),
|
||
|
normalClose(3)
|
||
|
}
|
||
|
ACCESS read-write
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The alarm-1 operation type"
|
||
|
::= { emdConfigAlarm2 2 }
|
||
|
|
||
|
-- ===========================================================================
|
||
|
-- upsTrapGroup
|
||
|
--
|
||
|
-- Traps group
|
||
|
-- ===========================================================================
|
||
|
|
||
|
-- This section defines the well-known notifications sent by
|
||
|
-- UPS agents.
|
||
|
-- Care must be taken to insure that no particular notification
|
||
|
-- is sent to a single receiving entity more often than once
|
||
|
-- every five seconds.
|
||
|
|
||
|
ushaPowerRestored TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Utility power has been restore."
|
||
|
::= 1
|
||
|
|
||
|
ushaPowerFail TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Utility power not available."
|
||
|
::= 2
|
||
|
|
||
|
ushaReturnFromLowBattery TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS has return from a low battery condition."
|
||
|
::= 3
|
||
|
|
||
|
ushaLowBattery TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"SEVERE: The UPS batteries are low and will soon be exhausted."
|
||
|
::= 4
|
||
|
|
||
|
ushaUpsOk TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The ups is working fine."
|
||
|
::= 5
|
||
|
|
||
|
ushaUpsFailed TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"SEVERE: The ups is not working fine."
|
||
|
::= 6
|
||
|
|
||
|
ushaUpsNotOnBattery TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS is not on battery power."
|
||
|
::= 7
|
||
|
|
||
|
ushaUpsOnBattery TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
upsBatteryGroupEstimatedChargeRemaining,
|
||
|
upsBatteryGroupVoltage,
|
||
|
upsBatteryGroupSecondsOnBattery
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"WARNING: The UPS has switched to battery backup power."
|
||
|
::= 8
|
||
|
|
||
|
ushaTestOver TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
upsBatteryTest,
|
||
|
upsTestBatteryTestSettingTime,
|
||
|
upsTestBatteryTestResult,
|
||
|
upsTestBatteryTestStartTime,
|
||
|
upsTestBatteryTestElapsedTime
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The testing of UPS is completed."
|
||
|
::= 9
|
||
|
|
||
|
ushaTestInProgress TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The testing is going on ups."
|
||
|
::= 10
|
||
|
|
||
|
ushaBypassOn TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS has enabled bypass."
|
||
|
::= 11
|
||
|
|
||
|
ushaUpsOnline TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS is not on Bypass and return to normal status."
|
||
|
::= 12
|
||
|
|
||
|
ushaCommunicationLost TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"SEVERE: Communication to the UPS has been lost."
|
||
|
::= 13
|
||
|
|
||
|
ushaCommunicationEstablished TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Communication with the UPS has been established."
|
||
|
::= 14
|
||
|
|
||
|
ushaUpsGoingDown TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: The ups has been given shutdown command."
|
||
|
::= 15
|
||
|
|
||
|
ushaUpsTurnedOff TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: UPS turn off."
|
||
|
::= 16
|
||
|
|
||
|
ushaUpsSleeping TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
upsControlUpsSleepTime
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: UPS has entered sleep mode."
|
||
|
::= 17
|
||
|
|
||
|
ushaUpsWokeUp TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS woke up from sleep mode."
|
||
|
::= 18
|
||
|
|
||
|
ushaUpsRebooted TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS is reboot."
|
||
|
::= 19
|
||
|
|
||
|
ushaUpsShutdownCancelled TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS shutdown process had been cancelled."
|
||
|
::= 20
|
||
|
|
||
|
ushaUpsNotOverTemperature TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
upsBatteryGroupTemperature,
|
||
|
upsConfigGroupOverTemperatureSetPoint
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS internal temperature return to normal."
|
||
|
::= 21
|
||
|
|
||
|
ushaUpsOverTemperature TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
upsBatteryGroupTemperature,
|
||
|
upsConfigGroupOverTemperatureSetPoint
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"SEVERE: The UPS temperature is too high."
|
||
|
::= 22
|
||
|
|
||
|
ushaUpsNotOverLoad TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
upsOutputGroupPercentLoad,
|
||
|
upsConfigGroupOverLoadSetPoint
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: The UPS load return from overload."
|
||
|
::= 23
|
||
|
|
||
|
ushaUpsOverLoad TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
upsOutputGroupPercentLoad,
|
||
|
upsConfigGroupOverLoadSetPoint
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"SEVERE: The UPS is overload."
|
||
|
::= 24
|
||
|
|
||
|
ushaUpsModuleInserted TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: UPS Battery Module plug-in."
|
||
|
::= 25
|
||
|
|
||
|
ushaUpsModuleRemoved TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: UPS Battery Module unplug."
|
||
|
::= 26
|
||
|
|
||
|
emdTemperatureNotHigh TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusTemperature,
|
||
|
emdConfigTempHighSetPoint,
|
||
|
emdConfigTempName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: EMD Temperature not over high Set point."
|
||
|
::= 27
|
||
|
|
||
|
emdTemperatureTooHigh TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusTemperature,
|
||
|
emdConfigTempHighSetPoint,
|
||
|
emdConfigTempName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"WARNING: EMD Temperature over high Set point."
|
||
|
::= 28
|
||
|
|
||
|
emdTemperatureNotLow TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusTemperature,
|
||
|
emdConfigTempLowSetPoint,
|
||
|
emdConfigTempName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: EMD Temperature not under low Set point."
|
||
|
::= 29
|
||
|
|
||
|
emdTemperatureTooLow TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusTemperature,
|
||
|
emdConfigTempLowSetPoint,
|
||
|
emdConfigTempName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"WARNING: EMD Temperature under low Set point."
|
||
|
::= 30
|
||
|
|
||
|
emdHumidityNotHigh TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusHumidity,
|
||
|
emdConfigHumidityHighSetPoint,
|
||
|
emdConfigHumidityName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: EMD Humidity not over high Set point."
|
||
|
::= 31
|
||
|
|
||
|
emdHumidityTooHigh TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusHumidity,
|
||
|
emdConfigHumidityHighSetPoint,
|
||
|
emdConfigHumidityName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"WARNING: EMD Humidity over high Set point."
|
||
|
::= 32
|
||
|
|
||
|
emdHumidityNotLow TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusHumidity,
|
||
|
emdConfigHumidityLowSetPoint,
|
||
|
emdConfigHumidityName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: EMD Humidity not under low Set point."
|
||
|
::= 33
|
||
|
|
||
|
emdHumidityTooLow TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdSatatusHumidity,
|
||
|
emdConfigHumidityLowSetPoint,
|
||
|
emdConfigHumidityName
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"WARNING: EMD Humidity under low Set point."
|
||
|
::= 34
|
||
|
|
||
|
emdAlarm1Normal TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdConfigAlarm1Type,
|
||
|
emdConfigAlarm1Name
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: EMD Alarm-1 not active."
|
||
|
::= 35
|
||
|
|
||
|
emdAlarm1Active TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdConfigAlarm1Type,
|
||
|
emdConfigAlarm1Name
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"WARNING: EMD Alarm-1 activated."
|
||
|
::= 36
|
||
|
|
||
|
emdAlarm2Normal TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdConfigAlarm2Type,
|
||
|
emdConfigAlarm2Name
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: EMD Alarm-2 not active."
|
||
|
::= 37
|
||
|
|
||
|
emdAlarm2Active TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
VARIABLES {
|
||
|
emdConfigAlarm2Type,
|
||
|
emdConfigAlarm2Name
|
||
|
}
|
||
|
DESCRIPTION
|
||
|
"WARNING: EMD Alarm-2 activated."
|
||
|
::= 38
|
||
|
|
||
|
ushaUpsInternalwarning TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Internal warning."
|
||
|
::= 39
|
||
|
|
||
|
ushaUpsReturnFromInternalwarning TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Internal warning."
|
||
|
::= 40
|
||
|
|
||
|
ushaUpsEPOActive TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: EPO Active."
|
||
|
::= 41
|
||
|
|
||
|
ushaUpsReturnFromEPOActive TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from EPO Active."
|
||
|
::= 42
|
||
|
|
||
|
ushaUpsModuleUnlock TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Module Unlock."
|
||
|
::= 43
|
||
|
|
||
|
ushaUpsReturnFromModuleUnlock TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Module Unlock."
|
||
|
::= 44
|
||
|
|
||
|
ushaUpsMain1Neutralloss TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Main 1 Neutral loss."
|
||
|
::= 45
|
||
|
|
||
|
ushaUpsReturnFromMain1Neutralloss TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Main 1 Neutral loss."
|
||
|
::= 46
|
||
|
|
||
|
ushaUpsMain1phaseerror TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Main 1 phase error."
|
||
|
::= 47
|
||
|
|
||
|
ushaUpsReturnFromMain1phaseerror TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Main 1 phase error."
|
||
|
::= 48
|
||
|
|
||
|
ushaUpsSitefault TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Site fault."
|
||
|
::= 49
|
||
|
|
||
|
ushaUpsReturnFromSitefault TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Site fault."
|
||
|
::= 50
|
||
|
|
||
|
ushaUpsBypassAbnormal TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Bypass Abnormal."
|
||
|
::= 51
|
||
|
|
||
|
ushaUpsReturnFromBypassAbnormal TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Bypass Abnormal."
|
||
|
::= 52
|
||
|
|
||
|
ushaUpsBypassPhaseError TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Bypass Phase Error."
|
||
|
::= 53
|
||
|
|
||
|
ushaUpsReturnFromBypassPhaseError TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Bypass Phase Error."
|
||
|
::= 54
|
||
|
|
||
|
ushaUpsBatteryOpen TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Battery Open."
|
||
|
::= 55
|
||
|
|
||
|
ushaUpsReturnFromBatteryOpen TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Battery Open."
|
||
|
::= 56
|
||
|
|
||
|
ushaUpsBatteryOverCharge TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Battery Over Charge."
|
||
|
::= 57
|
||
|
|
||
|
ushaUpsReturnFromBatteryOverCharge TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Battery Over Charge."
|
||
|
::= 58
|
||
|
|
||
|
ushaUpsBatteryReverse TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Battery Reverse."
|
||
|
::= 59
|
||
|
|
||
|
ushaUpsReturnFromBatteryReverse TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Battery Reverse."
|
||
|
::= 60
|
||
|
|
||
|
ushaUpsOverloadforewarning TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Overload forewarning."
|
||
|
::= 61
|
||
|
|
||
|
ushaUpsReturnFromOverloadforewarning TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Overload forewarning."
|
||
|
::= 62
|
||
|
|
||
|
ushaUpsOverloadWarning TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Overload Warning."
|
||
|
::= 63
|
||
|
|
||
|
ushaUpsReturnFromOverloadWarning TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Overload Warning."
|
||
|
::= 64
|
||
|
|
||
|
ushaUpsFanLock TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Fan Lock."
|
||
|
::= 65
|
||
|
|
||
|
ushaUpsReturnFromFanLock TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Fan Lock."
|
||
|
::= 66
|
||
|
|
||
|
ushaUpsMaintaincoverisopen TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Maintain cover is open."
|
||
|
::= 67
|
||
|
|
||
|
ushaUpsReturnFromMaintaincoverisopen TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Maintain cover is open."
|
||
|
::= 68
|
||
|
|
||
|
ushaUpsChargerfault TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Charger fault."
|
||
|
::= 69
|
||
|
|
||
|
ushaUpsReturnFromChargerfault TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Charger fault."
|
||
|
::= 70
|
||
|
|
||
|
ushaUpsModulelocationerror TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Module location error."
|
||
|
::= 71
|
||
|
|
||
|
ushaUpsReturnFromModulelocationerror TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Module location error."
|
||
|
::= 72
|
||
|
|
||
|
ushaUpsTurnonabnormal TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Turn on abnormal."
|
||
|
::= 73
|
||
|
|
||
|
ushaUpsReturnFromTurnonabnormal TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Turn on abnormal."
|
||
|
::= 74
|
||
|
|
||
|
ushaUpsRedundancyloss TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Redundancy loss."
|
||
|
::= 75
|
||
|
|
||
|
ushaUpsReturnFromRedundancyloss TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Redundancy loss."
|
||
|
::= 76
|
||
|
|
||
|
ushaUpsHotSwapActived TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Hot Swap Actived."
|
||
|
::= 77
|
||
|
|
||
|
ushaUpsReturnFromHotSwapActived TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Hot Swap Actived."
|
||
|
::= 78
|
||
|
|
||
|
ushaUpsBatteryInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Battery Inform."
|
||
|
::= 79
|
||
|
|
||
|
ushaUpsReturnFromBatteryInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Battery Inform."
|
||
|
::= 80
|
||
|
|
||
|
ushaUpsInspectionInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Inspection Inform."
|
||
|
::= 81
|
||
|
|
||
|
ushaUpsReturnFromInspectionInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Inspection Inform."
|
||
|
::= 82
|
||
|
|
||
|
ushaUpsGuaranteeInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Guarantee Inform."
|
||
|
::= 83
|
||
|
|
||
|
ushaUpsReturnFromGuaranteeInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Guarantee Inform."
|
||
|
::= 84
|
||
|
|
||
|
ushaUpsTemperatureLow TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Temperature Low."
|
||
|
::= 85
|
||
|
|
||
|
ushaUpsReturnFromTemperatureLow TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Temperature Low."
|
||
|
::= 86
|
||
|
|
||
|
ushaUpsTemperatureHigh TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Temperature High."
|
||
|
::= 87
|
||
|
|
||
|
ushaUpsReturnFromTemperatureHigh TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Temperature High."
|
||
|
::= 88
|
||
|
|
||
|
ushaUpsBatteryOverTemperature TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Battery Over Temperature."
|
||
|
::= 89
|
||
|
|
||
|
ushaUpsReturnFromBatteryOverTemperature TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Battery Over Temperature."
|
||
|
::= 90
|
||
|
|
||
|
ushaUpsFanMaintainInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Fan Maintain Inform."
|
||
|
::= 91
|
||
|
|
||
|
ushaUpsReturnFromFanMaintainInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Fan Maintain Inform."
|
||
|
::= 92
|
||
|
|
||
|
ushaUpsBusCapacitanceMaintainInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: Bus Capacitance Maintain Inform."
|
||
|
::= 93
|
||
|
|
||
|
ushaUpsReturnFromBusCapacitanceMaintainInform TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from Bus Capacitance Maintain Inform."
|
||
|
::= 94
|
||
|
|
||
|
ushaUpsSystemOverCapacity TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"WARNING: System Over Capacity."
|
||
|
::= 95
|
||
|
|
||
|
ushaUpsReturnFromSystemOverCapacity TRAP-TYPE
|
||
|
ENTERPRISE upsTrapGroup
|
||
|
DESCRIPTION
|
||
|
"INFORMATION: Return from System Over Capacity."
|
||
|
::= 96
|
||
|
|
||
|
END
|