mirror of
https://github.com/librenms/librenms.git
synced 2024-10-07 16:52:45 +00:00
newdevice: Added detection for DPS Telecom NetGuardian (#7326)
* newdevice: Added detection for DPS Telecom NetGuardian
This commit is contained in:
committed by
Søren Rosiak
parent
2115a1c6d1
commit
838f91a18a
BIN
html/images/logos/dpstelecom.png
Normal file
BIN
html/images/logos/dpstelecom.png
Normal file
Binary file not shown.
After Width: | Height: | Size: 18 KiB |
BIN
html/images/os/dpstelecom.png
Normal file
BIN
html/images/os/dpstelecom.png
Normal file
Binary file not shown.
After Width: | Height: | Size: 2.0 KiB |
45
includes/definitions/discovery/netguardian.yaml
Normal file
45
includes/definitions/discovery/netguardian.yaml
Normal file
@@ -0,0 +1,45 @@
|
|||||||
|
mib: DPS-MIB-CG-V1
|
||||||
|
modules:
|
||||||
|
sensors:
|
||||||
|
voltage:
|
||||||
|
data:
|
||||||
|
-
|
||||||
|
oid: cgStringChannels
|
||||||
|
value: cgStrVoltage
|
||||||
|
num_oid: .1.3.6.1.4.1.2682.2.1.1.4.
|
||||||
|
descr: 'Battery string {{ $index }}'
|
||||||
|
index: 'cgStrVoltage.{{ $index }}'
|
||||||
|
-
|
||||||
|
oid: cgBatteryChannels
|
||||||
|
value: cgVoltage
|
||||||
|
num_oid: .1.3.6.1.4.1.2682.2.2.1.4.
|
||||||
|
descr: 'Battery {{ $index }}'
|
||||||
|
index: 'cgVoltage.{{ $index }}'
|
||||||
|
current:
|
||||||
|
data:
|
||||||
|
-
|
||||||
|
oid: cgStringChannels
|
||||||
|
value: cgStrCurrent
|
||||||
|
num_oid: .1.3.6.1.4.1.2682.2.1.1.5.
|
||||||
|
descr: 'Battery string {{ $index }}'
|
||||||
|
index: 'cgStrCurrent.{{ $index }}'
|
||||||
|
temperature:
|
||||||
|
data:
|
||||||
|
-
|
||||||
|
oid: cgStringChannels
|
||||||
|
value: cgStrTempA
|
||||||
|
num_oid: .1.3.6.1.4.1.2682.2.1.1.6.
|
||||||
|
descr: 'Battery string {{ $index }}'
|
||||||
|
index: 'cgStrTempA.{{ $index }}'
|
||||||
|
-
|
||||||
|
oid: cgStringChannels
|
||||||
|
value: cgStrTempB
|
||||||
|
num_oid: .1.3.6.1.4.1.2682.2.1.1.7.
|
||||||
|
descr: 'Battery string {{ $index }}'
|
||||||
|
index: 'cgStrTempB.{{ $index }}'
|
||||||
|
-
|
||||||
|
oid: cgBatteryChannels
|
||||||
|
value: cgTemperature
|
||||||
|
num_oid: .1.3.6.1.4.1.2682.2.2.1.5.
|
||||||
|
descr: 'Battery {{ $index }}'
|
||||||
|
index: 'cgTemperature.{{ $index }}'
|
12
includes/definitions/netguardian.yaml
Normal file
12
includes/definitions/netguardian.yaml
Normal file
@@ -0,0 +1,12 @@
|
|||||||
|
os: netguardian
|
||||||
|
text: 'DPS Telecom NetGuardian'
|
||||||
|
type: appliance
|
||||||
|
icon: dpstelecom
|
||||||
|
group: dpstelecom
|
||||||
|
over:
|
||||||
|
- { graph: device_bits, text: 'Device Traffic' }
|
||||||
|
- { graph: device_processor, text: 'CPU Usage' }
|
||||||
|
- { graph: device_mempool, text: 'Memory Usage' }
|
||||||
|
discovery:
|
||||||
|
- sysObjectId:
|
||||||
|
- .1.3.6.1.4.1.2682
|
29
includes/polling/os/netguardian.inc.php
Normal file
29
includes/polling/os/netguardian.inc.php
Normal file
@@ -0,0 +1,29 @@
|
|||||||
|
<?php
|
||||||
|
/**
|
||||||
|
* netguardian.inc.php
|
||||||
|
*
|
||||||
|
* LibreNMS OS poller module for DPS Telecom NetGuardian
|
||||||
|
*
|
||||||
|
* This program is free software: you can redistribute it and/or modify
|
||||||
|
* it under the terms of the GNU General Public License as published by
|
||||||
|
* the Free Software Foundation, either version 3 of the License, or
|
||||||
|
* (at your option) any later version.
|
||||||
|
*
|
||||||
|
* This program is distributed in the hope that it will be useful,
|
||||||
|
* but WITHOUT ANY WARRANTY; without even the implied warranty of
|
||||||
|
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE.See the
|
||||||
|
* GNU General Public License for more details.
|
||||||
|
*
|
||||||
|
* You should have received a copy of the GNU General Public License
|
||||||
|
* along with this program. If not, see <http://www.gnu.org/licenses/>.
|
||||||
|
*
|
||||||
|
* @package LibreNMS
|
||||||
|
* @link http://librenms.org
|
||||||
|
* @copyright 2017 Neil Lathwood
|
||||||
|
* @author Neil Lathwood <gh+n@laf.io>
|
||||||
|
*/
|
||||||
|
|
||||||
|
$netguardian_tmp = snmp_get_multi_oid($device, 'dpsRTUModel.0 dpsRTUFirmwareVersion.0', '-OQs', 'DPS-MIB-V38');
|
||||||
|
$version = $data['dpsRTUFirmwareVersion.0'];
|
||||||
|
$hardware = $data['dpsRTUModel.0'];
|
||||||
|
unset($netguardian_tmp);
|
262
mibs/dpstelecom/DPS-MIB-CG-V1
Normal file
262
mibs/dpstelecom/DPS-MIB-CG-V1
Normal file
@@ -0,0 +1,262 @@
|
|||||||
|
-- Title: DPS_CG.MIB
|
||||||
|
-- Version: v1.0 for SNMPv2c
|
||||||
|
--
|
||||||
|
-- Copyright @ 2013 DPS Inc. All Rights Reserved
|
||||||
|
--
|
||||||
|
-- This MIB defines objects to support Cellguard Battery System Monitoring on DPS Products.
|
||||||
|
--
|
||||||
|
--
|
||||||
|
|
||||||
|
DPS-MIB-CG-V1 DEFINITIONS ::= BEGIN
|
||||||
|
|
||||||
|
IMPORTS
|
||||||
|
DisplayString
|
||||||
|
FROM SNMPv2-TC
|
||||||
|
enterprises
|
||||||
|
FROM RFC1155-SMI
|
||||||
|
MODULE-IDENTITY,
|
||||||
|
NOTIFICATION-TYPE,
|
||||||
|
OBJECT-TYPE,
|
||||||
|
Integer32
|
||||||
|
FROM SNMPv2-SMI;
|
||||||
|
|
||||||
|
dpsCellguard MODULE-IDENTITY
|
||||||
|
LAST-UPDATED "201310181200Z" --October 18th, 2013 12:00 PDT
|
||||||
|
ORGANIZATION "DPS Telecom"
|
||||||
|
CONTACT-INFO "DPS Support Team
|
||||||
|
Web http://dpstele.com/support
|
||||||
|
E-Mail support@dpstele.com
|
||||||
|
Phone (559)454-1600"
|
||||||
|
DESCRIPTION "MIB for Cellguard BSM support on DPS Products"
|
||||||
|
|
||||||
|
REVISION "201310181200Z" --October 18th, 2013 12:00 PDT
|
||||||
|
DESCRIPTION "First Revision (CTS)"
|
||||||
|
|
||||||
|
::= { dpsInc 2 }
|
||||||
|
|
||||||
|
dpsInc OBJECT IDENTIFIER ::= {enterprises 2682}
|
||||||
|
|
||||||
|
--Table for accessing string measurement values
|
||||||
|
|
||||||
|
cgStringChannels OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF CgStringEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Holds information on Cellguard battery strings."
|
||||||
|
::= {dpsCellguard 1}
|
||||||
|
|
||||||
|
cgStringEntry OBJECT-TYPE
|
||||||
|
SYNTAX CgStringEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Information about a particular string."
|
||||||
|
INDEX {cgStrNumber}
|
||||||
|
::= {cgStringChannels 1}
|
||||||
|
|
||||||
|
CgStringEntry ::= SEQUENCE { cgStrNumber Integer32,
|
||||||
|
cgStrEnabled INTEGER,
|
||||||
|
cgStrStatus DisplayString,
|
||||||
|
cgStrVoltage DisplayString,
|
||||||
|
cgStrCurrent DisplayString,
|
||||||
|
cgStrTempA DisplayString,
|
||||||
|
cgStrTempB DisplayString,
|
||||||
|
cgStrConductance DisplayString,
|
||||||
|
cgStrLife DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
cgStrNumber OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (1..6)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "String number (1-6)"
|
||||||
|
::= {cgStringEntry 1}
|
||||||
|
|
||||||
|
cgStrEnabled OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { disabled (0),
|
||||||
|
enabled (1)
|
||||||
|
}
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Enable status of string"
|
||||||
|
::= {cgStringEntry 2}
|
||||||
|
|
||||||
|
cgStrStatus OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The alarm status of the string."
|
||||||
|
::= {cgStringEntry 3}
|
||||||
|
|
||||||
|
cgStrVoltage OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The voltage measurement of the string."
|
||||||
|
::= {cgStringEntry 4}
|
||||||
|
|
||||||
|
cgStrCurrent OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The current measurement of the string."
|
||||||
|
::= {cgStringEntry 5}
|
||||||
|
|
||||||
|
cgStrTempA OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Temperature sensor A measurement."
|
||||||
|
::= {cgStringEntry 6}
|
||||||
|
|
||||||
|
cgStrTempB OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Temperature sensor B measurement."
|
||||||
|
::= {cgStringEntry 7}
|
||||||
|
|
||||||
|
cgStrConductance OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The average conductance measurement of the string."
|
||||||
|
::= {cgStringEntry 8}
|
||||||
|
|
||||||
|
cgStrLife OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The average battery capacity of the string."
|
||||||
|
::= {cgStringEntry 9}
|
||||||
|
|
||||||
|
|
||||||
|
--Table for accessing battery measurement values
|
||||||
|
|
||||||
|
cgBatteryChannels OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF CgBatteryEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Holds information on batteries."
|
||||||
|
::= {dpsCellguard 2}
|
||||||
|
|
||||||
|
cgBatteryEntry OBJECT-TYPE
|
||||||
|
SYNTAX CgBatteryEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Information about a particular battery."
|
||||||
|
INDEX {cgStringNumber, cgBatteryNumber}
|
||||||
|
::= {cgBatteryChannels 1}
|
||||||
|
|
||||||
|
CgBatteryEntry ::= SEQUENCE { cgStringNumber INTEGER,
|
||||||
|
cgBatteryNumber INTEGER,
|
||||||
|
cgStatus DisplayString,
|
||||||
|
cgVoltage DisplayString,
|
||||||
|
cgTemperature DisplayString,
|
||||||
|
cgStrapResist DisplayString,
|
||||||
|
cgConductance DisplayString,
|
||||||
|
cgBatteryLife DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
cgStringNumber OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (1..6)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "String number (1-6)"
|
||||||
|
::= {cgBatteryEntry 1}
|
||||||
|
|
||||||
|
cgBatteryNumber OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (1..240)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Battery number (1-240)"
|
||||||
|
::= {cgBatteryEntry 2}
|
||||||
|
|
||||||
|
cgStatus OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The alarm status of the battery."
|
||||||
|
::= {cgBatteryEntry 3}
|
||||||
|
|
||||||
|
cgVoltage OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The voltage measurement of the battery."
|
||||||
|
::= {cgBatteryEntry 4}
|
||||||
|
|
||||||
|
cgTemperature OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The temperature measurement of the battery."
|
||||||
|
::= {cgBatteryEntry 5}
|
||||||
|
|
||||||
|
cgStrapResist OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The strap resistance measurement."
|
||||||
|
::= {cgBatteryEntry 6}
|
||||||
|
|
||||||
|
cgConductance OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The conductance measurement of the battery."
|
||||||
|
::= {cgBatteryEntry 7}
|
||||||
|
|
||||||
|
cgBatteryLife OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The capacity of the battery."
|
||||||
|
::= {cgBatteryEntry 8}
|
||||||
|
|
||||||
|
-- TRAP definitions
|
||||||
|
|
||||||
|
cellguardTrap OBJECT IDENTIFIER ::= {dpsCellguard 8000}
|
||||||
|
|
||||||
|
cgAlarmTrap NOTIFICATION-TYPE
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION
|
||||||
|
"Alarm info from Cellguard system."
|
||||||
|
::= { cellguardTrap 1 }
|
||||||
|
|
||||||
|
cgTrapType OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { unknown (0),
|
||||||
|
voltage (1),
|
||||||
|
current (2),
|
||||||
|
temperature (3),
|
||||||
|
strapResistance (4),
|
||||||
|
life (5),
|
||||||
|
conductance (6)
|
||||||
|
}
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION
|
||||||
|
"Trap threshold type."
|
||||||
|
::= { cellguardTrap 2 }
|
||||||
|
|
||||||
|
cgTrapStatus OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { noAlarm (0),
|
||||||
|
minorUnder (1),
|
||||||
|
minorOver (2),
|
||||||
|
majorUnder (3),
|
||||||
|
majorOver (4),
|
||||||
|
notDetected (5)
|
||||||
|
}
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION
|
||||||
|
"Trap threshold status."
|
||||||
|
::= { cellguardTrap 3 }
|
||||||
|
|
||||||
|
cgTrapValue OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Trap most recent measurement reading."
|
||||||
|
::= {cellguardTrap 4}
|
||||||
|
|
||||||
|
END
|
773
mibs/dpstelecom/DPS-MIB-V38
Normal file
773
mibs/dpstelecom/DPS-MIB-V38
Normal file
@@ -0,0 +1,773 @@
|
|||||||
|
-- Title: DPS_V41.MIB
|
||||||
|
-- Version: v4.1
|
||||||
|
--
|
||||||
|
-- Copyright @ 1997-2004 DPS Inc. All Rights Reserved
|
||||||
|
--
|
||||||
|
-- This MIB defines objects for the DPS products.
|
||||||
|
--
|
||||||
|
--
|
||||||
|
|
||||||
|
DPS-MIB-V38 DEFINITIONS ::= BEGIN
|
||||||
|
|
||||||
|
IMPORTS
|
||||||
|
DisplayString,
|
||||||
|
sysDescr,
|
||||||
|
sysLocation
|
||||||
|
FROM RFC1213-MIB
|
||||||
|
OBJECT-TYPE
|
||||||
|
FROM RFC1212-MIB
|
||||||
|
enterprises
|
||||||
|
FROM RFC1155-SMI
|
||||||
|
TRAP-TYPE
|
||||||
|
FROM RFC-1215;
|
||||||
|
|
||||||
|
dpsInc OBJECT IDENTIFIER ::= {enterprises 2682}
|
||||||
|
|
||||||
|
dpsAlarmControl OBJECT IDENTIFIER ::= {dpsInc 1}
|
||||||
|
|
||||||
|
tmonXM OBJECT IDENTIFIER ::= {dpsAlarmControl 1}
|
||||||
|
|
||||||
|
tmonIdent OBJECT IDENTIFIER ::= {tmonXM 1}
|
||||||
|
|
||||||
|
tmonIdentManufacturer OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The TMON/XM Unit manufacturer."
|
||||||
|
::= {tmonIdent 1}
|
||||||
|
|
||||||
|
tmonIdentModel OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The TMON/XM model designation."
|
||||||
|
::= {tmonIdent 2}
|
||||||
|
|
||||||
|
tmonIdentSoftwareVersion OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The TMON/XM SNMP Agent software version."
|
||||||
|
::= {tmonIdent 3}
|
||||||
|
|
||||||
|
tmonAlarmTable OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF TMonAlarmEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "A table of TMon Alarm-specific information."
|
||||||
|
::= {tmonXM 2}
|
||||||
|
|
||||||
|
tmonAlarmEntry OBJECT-TYPE
|
||||||
|
SYNTAX TMonAlarmEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Information about a particular TMon alarm."
|
||||||
|
INDEX {tmonAIndex}
|
||||||
|
::= {tmonAlarmTable 1}
|
||||||
|
|
||||||
|
TMonAlarmEntry ::= SEQUENCE { tmonAIndex INTEGER,
|
||||||
|
tmonASite DisplayString,
|
||||||
|
tmonADesc DisplayString,
|
||||||
|
tmonAState DisplayString,
|
||||||
|
tmonASeverity DisplayString,
|
||||||
|
tmonAChgDate DisplayString,
|
||||||
|
tmonAChgTime DisplayString,
|
||||||
|
tmonAAuxDesc DisplayString,
|
||||||
|
tmonADispDesc DisplayString,
|
||||||
|
tmonAPntType INTEGER,
|
||||||
|
tmonAPort INTEGER,
|
||||||
|
tmonAAddress INTEGER,
|
||||||
|
tmonADisplay INTEGER,
|
||||||
|
tmonAPoint INTEGER,
|
||||||
|
tmonAIPAddr DisplayString,
|
||||||
|
tmonADevDesc DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
tmonAIndex OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..2147483647)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Tmon alarm table index (1..NumberOfAlarms)."
|
||||||
|
::={tmonAlarmEntry 1}
|
||||||
|
|
||||||
|
tmonASite OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The site of the alarm (i.e. Atlanta Hub, Sub-Station H32)."
|
||||||
|
::= {tmonAlarmEntry 2}
|
||||||
|
|
||||||
|
tmonADesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "A user-defined text string associated with the alarm
|
||||||
|
(i.e. South Door, Generator, Power Grid 1)."
|
||||||
|
::= {tmonAlarmEntry 3}
|
||||||
|
|
||||||
|
tmonAState OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The current alarm state."
|
||||||
|
::= {tmonAlarmEntry 4}
|
||||||
|
|
||||||
|
tmonASeverity OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The severity of the last alarm event."
|
||||||
|
::= {tmonAlarmEntry 5}
|
||||||
|
|
||||||
|
tmonAChgDate OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The date (mm/dd/yy) of the last alarm event."
|
||||||
|
::= {tmonAlarmEntry 6}
|
||||||
|
|
||||||
|
tmonAChgTime OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The time (hh:mm:ss) of the last alarm event."
|
||||||
|
::= {tmonAlarmEntry 7}
|
||||||
|
|
||||||
|
tmonAAuxDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
||||||
|
alarm (i.e. This remote needs servicing)."
|
||||||
|
::= {tmonAlarmEntry 8}
|
||||||
|
|
||||||
|
tmonADispDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "A description of the display on which this point appears."
|
||||||
|
::= {tmonAlarmEntry 9}
|
||||||
|
|
||||||
|
tmonAPntType OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Type of this point."
|
||||||
|
::={tmonAlarmEntry 10}
|
||||||
|
|
||||||
|
tmonAPort OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Port on which this point is reported."
|
||||||
|
::={tmonAlarmEntry 11}
|
||||||
|
|
||||||
|
tmonAAddress OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Address of unit reporting this point."
|
||||||
|
::={tmonAlarmEntry 12}
|
||||||
|
|
||||||
|
tmonADisplay OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Display on which this point appears."
|
||||||
|
::={tmonAlarmEntry 13}
|
||||||
|
|
||||||
|
tmonAPoint OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Index into display of this point."
|
||||||
|
::={tmonAlarmEntry 14}
|
||||||
|
|
||||||
|
tmonAIPAddr OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The IP Address of the device on which this point appears."
|
||||||
|
::= {tmonAlarmEntry 16}
|
||||||
|
|
||||||
|
tmonADevDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "A description of the device on which this point appears."
|
||||||
|
::= {tmonAlarmEntry 17}
|
||||||
|
|
||||||
|
-- structure used to issue a command to tmonXM element
|
||||||
|
|
||||||
|
tmonCommandGrid OBJECT IDENTIFIER ::= {tmonXM 3}
|
||||||
|
|
||||||
|
tmonCPType OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Tmon point type."
|
||||||
|
::= {tmonCommandGrid 1}
|
||||||
|
|
||||||
|
tmonCPort OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Tmon port number."
|
||||||
|
::= {tmonCommandGrid 2}
|
||||||
|
|
||||||
|
tmonCAddress OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Tmon_port address number."
|
||||||
|
::= {tmonCommandGrid 3}
|
||||||
|
|
||||||
|
tmonCDisplay OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Tmon_port_address display number."
|
||||||
|
::= {tmonCommandGrid 4}
|
||||||
|
|
||||||
|
tmonCPoint OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (1..64)
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Tmon_port_display point number (1-64)."
|
||||||
|
::= {tmonCommandGrid 5}
|
||||||
|
|
||||||
|
tmonCEvent OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Tmon event ID."
|
||||||
|
::= {tmonCommandGrid 6}
|
||||||
|
|
||||||
|
tmonCAction OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { latch(1),
|
||||||
|
release(2),
|
||||||
|
momentary(3),
|
||||||
|
ack(17),
|
||||||
|
tag(18),
|
||||||
|
untag(19)
|
||||||
|
}
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Requested command action (tmonXM will ignore if invalid)."
|
||||||
|
::= {tmonCommandGrid 7}
|
||||||
|
|
||||||
|
tmonCAuxText OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
||||||
|
command (i.e. User_initials)."
|
||||||
|
::= {tmonCommandGrid 8}
|
||||||
|
|
||||||
|
tmonCResult OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { success(1),
|
||||||
|
failure(2),
|
||||||
|
pending(3)
|
||||||
|
}
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Command result."
|
||||||
|
::= {tmonCommandGrid 9}
|
||||||
|
|
||||||
|
|
||||||
|
|
||||||
|
dpsRTU OBJECT IDENTIFIER ::= {dpsAlarmControl 2}
|
||||||
|
|
||||||
|
dpsRTUIdent OBJECT IDENTIFIER ::= {dpsRTU 1}
|
||||||
|
|
||||||
|
dpsRTUManufacturer OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The Remote Telemetry Unit manufacturer."
|
||||||
|
::= {dpsRTUIdent 1}
|
||||||
|
|
||||||
|
dpsRTUModel OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The RTU model designation."
|
||||||
|
::= {dpsRTUIdent 2}
|
||||||
|
|
||||||
|
dpsRTUFirmwareVersion OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The RTU firmware version."
|
||||||
|
::= {dpsRTUIdent 3}
|
||||||
|
|
||||||
|
dpsRTUDateTime OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The RTU system date and time."
|
||||||
|
::= {dpsRTUIdent 4}
|
||||||
|
|
||||||
|
dpsRTUSyncReq OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { sync(1)
|
||||||
|
}
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Caution: SETting this object initiates traps for all
|
||||||
|
standing alarms."
|
||||||
|
::= {dpsRTUIdent 5}
|
||||||
|
|
||||||
|
|
||||||
|
-- structure used to access displays managed by this RTU
|
||||||
|
|
||||||
|
dpsRTUDisplayGrid OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF DPSrtuDispEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Holds information on displays managed by the RTU."
|
||||||
|
::= {dpsRTU 2}
|
||||||
|
|
||||||
|
dpsRTUDisplayEntry OBJECT-TYPE
|
||||||
|
SYNTAX DPSrtuDispEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Information about a particular RTU display."
|
||||||
|
INDEX {dpsRTUPort, dpsRTUAddress, dpsRTUDisplay}
|
||||||
|
::= {dpsRTUDisplayGrid 1}
|
||||||
|
|
||||||
|
DPSrtuDispEntry ::= SEQUENCE { dpsRTUPort INTEGER,
|
||||||
|
dpsRTUAddress INTEGER,
|
||||||
|
dpsRTUDisplay INTEGER,
|
||||||
|
dpsRTUDispDesc DisplayString,
|
||||||
|
dpsRTUPntMap DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
dpsRTUPort OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU port number."
|
||||||
|
::= {dpsRTUDisplayEntry 1}
|
||||||
|
|
||||||
|
dpsRTUAddress OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port address number."
|
||||||
|
::= {dpsRTUDisplayEntry 2}
|
||||||
|
|
||||||
|
dpsRTUDisplay OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port_address display number."
|
||||||
|
::= {dpsRTUDisplayEntry 3}
|
||||||
|
|
||||||
|
dpsRTUDispDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "A description of the associated display."
|
||||||
|
::= {dpsRTUDisplayEntry 4}
|
||||||
|
|
||||||
|
dpsRTUPntMap OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "A map of the points appearing in this display."
|
||||||
|
::= {dpsRTUDisplayEntry 5}
|
||||||
|
|
||||||
|
|
||||||
|
-- structure used to issue a control to a managed point
|
||||||
|
|
||||||
|
dpsRTUControlGrid OBJECT IDENTIFIER ::= {dpsRTU 3}
|
||||||
|
|
||||||
|
dpsRTUCPort OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU port number."
|
||||||
|
::= {dpsRTUControlGrid 1}
|
||||||
|
|
||||||
|
dpsRTUCAddress OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port address number."
|
||||||
|
::= {dpsRTUControlGrid 2}
|
||||||
|
|
||||||
|
dpsRTUCDisplay OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port_address display number."
|
||||||
|
::= {dpsRTUControlGrid 3}
|
||||||
|
|
||||||
|
dpsRTUCPoint OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (1..64)
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port_display point number (1-64)."
|
||||||
|
::= {dpsRTUControlGrid 4}
|
||||||
|
|
||||||
|
dpsRTUCAction OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { latch(1),
|
||||||
|
release(2),
|
||||||
|
momentary(3)
|
||||||
|
}
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Requested action on point (RTU will ignore if invalid)."
|
||||||
|
::= {dpsRTUControlGrid 5}
|
||||||
|
|
||||||
|
dpsRTUAlarmGrid OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF DPSrtuAlarmEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Holds individual alarm point information."
|
||||||
|
::= {dpsRTU 5}
|
||||||
|
|
||||||
|
dpsRTUAlarmEntry OBJECT-TYPE
|
||||||
|
SYNTAX DPSrtuAlarmEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Detailed information about a particular RTU display."
|
||||||
|
INDEX {dpsRTUAPort, dpsRTUAAddress, dpsRTUADisplay, dpsRTUAPoint}
|
||||||
|
::= {dpsRTUAlarmGrid 1}
|
||||||
|
|
||||||
|
DPSrtuAlarmEntry ::= SEQUENCE { dpsRTUAPort INTEGER,
|
||||||
|
dpsRTUAAddress INTEGER,
|
||||||
|
dpsRTUADisplay INTEGER,
|
||||||
|
dpsRTUAPoint INTEGER,
|
||||||
|
dpsRTUAPntDesc DisplayString,
|
||||||
|
dpsRTUAState DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
dpsRTUAPort OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU port number."
|
||||||
|
::= {dpsRTUAlarmEntry 1}
|
||||||
|
|
||||||
|
dpsRTUAAddress OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port address number."
|
||||||
|
::= {dpsRTUAlarmEntry 2}
|
||||||
|
|
||||||
|
dpsRTUADisplay OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port_address display number."
|
||||||
|
::= {dpsRTUAlarmEntry 3}
|
||||||
|
|
||||||
|
dpsRTUAPoint OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "RTU_port_address_display point number."
|
||||||
|
::= {dpsRTUAlarmEntry 4}
|
||||||
|
|
||||||
|
dpsRTUAPntDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-write
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "A description of this point."
|
||||||
|
::= {dpsRTUAlarmEntry 5}
|
||||||
|
|
||||||
|
dpsRTUAState OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The current state of this point."
|
||||||
|
::= {dpsRTUAlarmEntry 6}
|
||||||
|
|
||||||
|
--Table for accessing analog channel value
|
||||||
|
|
||||||
|
analogChannels OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF ChannelEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Holds information on analog channels"
|
||||||
|
::= {dpsRTU 6}
|
||||||
|
|
||||||
|
channelEntry OBJECT-TYPE
|
||||||
|
SYNTAX ChannelEntry
|
||||||
|
ACCESS not-accessible
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Information about a particular channel"
|
||||||
|
INDEX {channelNumber}
|
||||||
|
::= {analogChannels 1}
|
||||||
|
|
||||||
|
ChannelEntry ::= SEQUENCE { channelNumber INTEGER,
|
||||||
|
enabled INTEGER,
|
||||||
|
description DisplayString,
|
||||||
|
value DisplayString,
|
||||||
|
thresholds INTEGER
|
||||||
|
}
|
||||||
|
|
||||||
|
channelNumber OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER (0..999)
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Input channel number"
|
||||||
|
::= {channelEntry 1}
|
||||||
|
|
||||||
|
enabled OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { disabled (0),
|
||||||
|
enabled (1)
|
||||||
|
}
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Enable status of channel"
|
||||||
|
::= {channelEntry 2}
|
||||||
|
|
||||||
|
description OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The user defined description of the channel"
|
||||||
|
::= {channelEntry 3}
|
||||||
|
|
||||||
|
value OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "The current value of the channel"
|
||||||
|
::= {channelEntry 4}
|
||||||
|
|
||||||
|
thresholds OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { noAlarms (0),
|
||||||
|
minorUnder (1),
|
||||||
|
minorOver (2),
|
||||||
|
majorUnder (3),
|
||||||
|
majorOver (4),
|
||||||
|
notDetected (5)
|
||||||
|
}
|
||||||
|
ACCESS read-only
|
||||||
|
STATUS mandatory
|
||||||
|
DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed"
|
||||||
|
::= {channelEntry 5}
|
||||||
|
|
||||||
|
-- TRAP definitions
|
||||||
|
|
||||||
|
tmonCRalarmSet TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a critical alarm is set."
|
||||||
|
::= 10
|
||||||
|
|
||||||
|
tmonCRalarmClr TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a critical alarm clears."
|
||||||
|
::= 11
|
||||||
|
|
||||||
|
tmonMJalarmSet TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a major alarm is set."
|
||||||
|
::= 12
|
||||||
|
|
||||||
|
tmonMJalarmClr TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a major alarm clears."
|
||||||
|
::= 13
|
||||||
|
|
||||||
|
tmonMNalarmSet TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a minor alarm is set."
|
||||||
|
::= 14
|
||||||
|
|
||||||
|
tmonMNalarmClr TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a minor alarm clears."
|
||||||
|
::= 15
|
||||||
|
|
||||||
|
tmonSTalarmSet TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a status alarm is set."
|
||||||
|
::= 16
|
||||||
|
|
||||||
|
tmonSTalarmClr TRAP-TYPE
|
||||||
|
ENTERPRISE tmonXM
|
||||||
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
||||||
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
||||||
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
||||||
|
tmonAIPAddr, tmonADevDesc }
|
||||||
|
DESCRIPTION "Generated when a status alarm clears."
|
||||||
|
::= 17
|
||||||
|
|
||||||
|
dpsRTUPointSet TRAP-TYPE
|
||||||
|
ENTERPRISE dpsRTU
|
||||||
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
dpsRTUAPort, dpsRTUAAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
DESCRIPTION "Generated when a point is set."
|
||||||
|
::= 20
|
||||||
|
|
||||||
|
dpsRTUPointClr TRAP-TYPE
|
||||||
|
ENTERPRISE dpsRTU
|
||||||
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
DESCRIPTION "Generated when a point clears."
|
||||||
|
::= 21
|
||||||
|
|
||||||
|
dpsRTUsumPSet TRAP-TYPE
|
||||||
|
ENTERPRISE dpsRTU
|
||||||
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
||||||
|
DESCRIPTION "Generated when any point is set."
|
||||||
|
::= 101
|
||||||
|
|
||||||
|
dpsRTUsumPClr TRAP-TYPE
|
||||||
|
ENTERPRISE dpsRTU
|
||||||
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
||||||
|
DESCRIPTION "Generated when all points clear."
|
||||||
|
::= 102
|
||||||
|
|
||||||
|
dpsRTUcomFailed TRAP-TYPE
|
||||||
|
ENTERPRISE dpsRTU
|
||||||
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
||||||
|
DESCRIPTION "Generated when polled unit fails to respond."
|
||||||
|
::= 103
|
||||||
|
|
||||||
|
dpsRTUcomRestored TRAP-TYPE
|
||||||
|
ENTERPRISE dpsRTU
|
||||||
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
||||||
|
DESCRIPTION "Generated when failed unit resumes responding."
|
||||||
|
::= 104
|
||||||
|
|
||||||
|
-- **************************************************************************
|
||||||
|
-- Granular TRAP definitions
|
||||||
|
--
|
||||||
|
-- The following section supports granular trapping available on selected
|
||||||
|
-- DPS remote telemetry units. This software selectable facility changes the
|
||||||
|
-- trap sent by a remote so equipped. The standard trap identifies a SET or
|
||||||
|
-- CLR event in the trap ID and binds variables identifying the specific
|
||||||
|
-- remote point associated with the event. A granular trap identifies a SET
|
||||||
|
-- or CLR event and the specific point associated with the event all in the
|
||||||
|
-- trap ID. This is accomplished by mapping all SET event/points into the
|
||||||
|
-- trap ID range 10001-19999 and all CLR event/points into the trap ID range
|
||||||
|
-- 20001-29999.
|
||||||
|
-- If the unit manages multiple displays, the displays are mapped
|
||||||
|
-- sequentially with each display occupying a 64 point range. For example, a
|
||||||
|
-- standalone standard or timestamp KDA which manages two displays, reports
|
||||||
|
-- SET event/points in the first display (discrete alarm points) in the range
|
||||||
|
-- 10001-10064. The CLR event/points for the same display would be reported
|
||||||
|
-- in the range 20001-20064. The second display (controls & housekeeping
|
||||||
|
-- alarm points) would have its SET event/points reported in the range 10065-
|
||||||
|
-- 10128 and its CLR event/points reported in the range 20065-20128.
|
||||||
|
-- SET and CLR definitions for the first 64 points have been included and
|
||||||
|
-- can be used as is for driving most SNMP manager mechanisms designed to key
|
||||||
|
-- on the trap ID for distinguishing and managing events. Additional events
|
||||||
|
-- can be added simply by editing the following trap definitions prior to
|
||||||
|
-- compiling this file into your SNMP manager. We recommend managing the SET
|
||||||
|
-- and CLR event definitions for a specific point as a single unit and using
|
||||||
|
-- the following simple rules:
|
||||||
|
-- + Adjust the numeric portion of the label preceeding TRAP-TYPE.
|
||||||
|
-- + Adjust the numeric reference in the DESCRIPTION text.
|
||||||
|
-- + Adjust the number on the last line of the definition.
|
||||||
|
--
|
||||||
|
-- Using these rules a definition for the 65th point would be:
|
||||||
|
--
|
||||||
|
-- dpsRTUp0065Set TRAP-TYPE
|
||||||
|
-- ENTERPRISE dpsRTU
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 65 is set."
|
||||||
|
-- ::= 10065
|
||||||
|
--
|
||||||
|
-- dpsRTUp0065Clr TRAP-TYPE
|
||||||
|
-- ENTERPRISE dpsRTU
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 65 clears."
|
||||||
|
-- ::= 20065
|
||||||
|
--
|
||||||
|
-- This editing can can be accomplished quite easily using a plain ASCII
|
||||||
|
-- file editor. The repetitive structure of the definitions also makes for
|
||||||
|
-- rapid scripted or programmed generation if any such tools are available.
|
||||||
|
-- A compressed file containing event/point definitions for 144 displays is
|
||||||
|
-- available (DPS_G36.zip 150K) which uncompressed (DPS_G36.mib 6.2M) can be
|
||||||
|
-- used for cut-and-paste editing if desired.
|
||||||
|
-- The definitions can be further customized if desired by similar editing
|
||||||
|
-- prior to compiling carefully observing the following conventions:
|
||||||
|
-- + The label preceeding the TRAP-TYPE designator can be edited with some
|
||||||
|
-- freedom but the label must be utterly unique among all trap definitions.
|
||||||
|
-- + The ENTERPRISE and VARIABLES sections must not be changed.
|
||||||
|
-- + The DESCRIPTION can be edited with complete freedom and is typically
|
||||||
|
-- ignored within the context of standard SNMP manager trap handling. The
|
||||||
|
-- quote mark before and after the text of the description are required.
|
||||||
|
-- + The number on the last line of the definition is the actual trap ID
|
||||||
|
-- defined and must also be utterly unique.
|
||||||
|
--
|
||||||
|
-- For example:
|
||||||
|
--
|
||||||
|
-- dpsRTUp0001Set TRAP-TYPE
|
||||||
|
-- ENTERPRISE dpsRTU
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 1 is set."
|
||||||
|
-- ::= 10001
|
||||||
|
--
|
||||||
|
-- dpsRTUp0001Clr TRAP-TYPE
|
||||||
|
-- ENTERPRISE dpsRTU
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 1 clears."
|
||||||
|
-- ::= 20001
|
||||||
|
--
|
||||||
|
-- Could be customized as:
|
||||||
|
--
|
||||||
|
-- dpsRTUFireAlarm TRAP-TYPE
|
||||||
|
-- ENTERPRISE dpsRTU
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
-- DESCRIPTION "Generated when smoke detector activates."
|
||||||
|
-- ::= 10001
|
||||||
|
--
|
||||||
|
-- dpsRTUFireOut TRAP-TYPE
|
||||||
|
-- ENTERPRISE dpsRTU
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
||||||
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
||||||
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
||||||
|
-- DESCRIPTION "Generated when smoke detector deactivates."
|
||||||
|
-- ::= 20001
|
||||||
|
-- **************************************************************************
|
||||||
|
|
||||||
|
|
||||||
|
END
|
801
mibs/dpstelecom/DPS-MIB-V38-V2
Normal file
801
mibs/dpstelecom/DPS-MIB-V38-V2
Normal file
@@ -0,0 +1,801 @@
|
|||||||
|
-- Title: DPS_V41v2.MIB
|
||||||
|
-- Version: v4.1 for SNMPv2c
|
||||||
|
--
|
||||||
|
-- Copyright @ 2011 DPS Inc. All Rights Reserved
|
||||||
|
--
|
||||||
|
-- This MIB defines objects for the DPS products.
|
||||||
|
--
|
||||||
|
-- Note: AnalogChannels table only available in NetGuardianG4 v4.2J or later
|
||||||
|
--
|
||||||
|
|
||||||
|
DPS-MIB-V38-V2 DEFINITIONS ::= BEGIN
|
||||||
|
|
||||||
|
IMPORTS
|
||||||
|
DisplayString
|
||||||
|
FROM SNMPv2-TC
|
||||||
|
MODULE-IDENTITY,
|
||||||
|
NOTIFICATION-TYPE,
|
||||||
|
OBJECT-TYPE,
|
||||||
|
Integer32
|
||||||
|
FROM SNMPv2-SMI
|
||||||
|
dpsAlarmControl, tmonXM
|
||||||
|
FROM DPS-MIB-V38;
|
||||||
|
|
||||||
|
tmonV2XM MODULE-IDENTITY
|
||||||
|
LAST-UPDATED "201208081200Z" --August 8th, 2012 12:00 PDT
|
||||||
|
ORGANIZATION "DPS Telecom"
|
||||||
|
CONTACT-INFO "DPS Support Team
|
||||||
|
Web http://dpstele.com/support
|
||||||
|
E-Mail support@dpstele.com
|
||||||
|
Phone (559)454-1600"
|
||||||
|
DESCRIPTION "Second generation MIB for DPS Telecom products"
|
||||||
|
|
||||||
|
REVISION "201208081200Z" --August 8th, 2012 12:00 PDT
|
||||||
|
DESCRIPTION "Modified for proper smi/asn.1 formatting and structure (CBH)"
|
||||||
|
|
||||||
|
::= { dpsAlarmControl 3 }
|
||||||
|
|
||||||
|
tmonV2Ident OBJECT IDENTIFIER ::= {tmonV2XM 1}
|
||||||
|
|
||||||
|
tmonV2IdentManufacturer OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The TMON/XM Unit manufacturer."
|
||||||
|
::= {tmonV2Ident 1}
|
||||||
|
|
||||||
|
tmonV2IdentModel OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The TMON/XM model designation."
|
||||||
|
::= {tmonV2Ident 2}
|
||||||
|
|
||||||
|
tmonV2IdentSoftwareVersion OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The TMON/XM SNMP Agent software version."
|
||||||
|
::= {tmonV2Ident 3}
|
||||||
|
|
||||||
|
tmonV2AlarmTable OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF TMonV2AlarmEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A table of TMonV2 Alarm-specific information."
|
||||||
|
::= {tmonV2XM 2}
|
||||||
|
|
||||||
|
tmonV2AlarmEntry OBJECT-TYPE
|
||||||
|
SYNTAX TMonV2AlarmEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Information about a particular TMonV2 alarm."
|
||||||
|
INDEX {tmonV2AIndex}
|
||||||
|
::= {tmonV2AlarmTable 1}
|
||||||
|
|
||||||
|
TMonV2AlarmEntry ::= SEQUENCE { tmonV2AIndex Integer32,
|
||||||
|
tmonV2ASite DisplayString,
|
||||||
|
tmonV2ADesc DisplayString,
|
||||||
|
tmonV2AState DisplayString,
|
||||||
|
tmonV2ASeverity DisplayString,
|
||||||
|
tmonV2AChgDate DisplayString,
|
||||||
|
tmonV2AChgTime DisplayString,
|
||||||
|
tmonV2AAuxDesc DisplayString,
|
||||||
|
tmonV2ADispDesc DisplayString,
|
||||||
|
tmonV2APntType Integer32,
|
||||||
|
tmonV2APort Integer32,
|
||||||
|
tmonV2AAddress Integer32,
|
||||||
|
tmonV2ADisplay Integer32,
|
||||||
|
tmonV2APoint Integer32,
|
||||||
|
tmonV2AEvent Integer32,
|
||||||
|
tmonV2AIPAddr DisplayString,
|
||||||
|
tmonV2ADevDesc DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
tmonV2AIndex OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Tmon alarm table index (1..NumberOfAlarms)."
|
||||||
|
::={tmonV2AlarmEntry 1}
|
||||||
|
|
||||||
|
tmonV2ASite OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The site of the alarm (i.e. Atlanta Hub, Sub-Station H32)."
|
||||||
|
::= {tmonV2AlarmEntry 2}
|
||||||
|
|
||||||
|
tmonV2ADesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A user-defined text string associated with the alarm
|
||||||
|
(i.e. South Door, Generator, Power Grid 1)."
|
||||||
|
::= {tmonV2AlarmEntry 3}
|
||||||
|
|
||||||
|
tmonV2AState OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The current alarm state."
|
||||||
|
::= {tmonV2AlarmEntry 4}
|
||||||
|
|
||||||
|
tmonV2ASeverity OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The severity of the last alarm event."
|
||||||
|
::= {tmonV2AlarmEntry 5}
|
||||||
|
|
||||||
|
tmonV2AChgDate OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The date (mm/dd/yy) of the last alarm event."
|
||||||
|
::= {tmonV2AlarmEntry 6}
|
||||||
|
|
||||||
|
tmonV2AChgTime OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The time (hh:mm:ss) of the last alarm event."
|
||||||
|
::= {tmonV2AlarmEntry 7}
|
||||||
|
|
||||||
|
tmonV2AAuxDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
||||||
|
alarm (i.e. This remote needs servicing)."
|
||||||
|
::= {tmonV2AlarmEntry 8}
|
||||||
|
|
||||||
|
tmonV2ADispDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A description of the display on which this point appears."
|
||||||
|
::= {tmonV2AlarmEntry 9}
|
||||||
|
|
||||||
|
tmonV2APntType OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..999)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Type of this point."
|
||||||
|
::={tmonV2AlarmEntry 10}
|
||||||
|
|
||||||
|
tmonV2APort OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Port on which this point is reported."
|
||||||
|
::={tmonV2AlarmEntry 11}
|
||||||
|
|
||||||
|
tmonV2AAddress OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..9999)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Address of unit reporting this point."
|
||||||
|
::={tmonV2AlarmEntry 12}
|
||||||
|
|
||||||
|
tmonV2ADisplay OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Display on which this point appears."
|
||||||
|
::={tmonV2AlarmEntry 13}
|
||||||
|
|
||||||
|
tmonV2APoint OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..64)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Index into display of this point."
|
||||||
|
::={tmonV2AlarmEntry 14}
|
||||||
|
|
||||||
|
tmonV2AEvent OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Event id for this message."
|
||||||
|
::={tmonV2AlarmEntry 15}
|
||||||
|
|
||||||
|
tmonV2AIPAddr OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The IP Address of the device on which this point appears."
|
||||||
|
::= {tmonV2AlarmEntry 16}
|
||||||
|
|
||||||
|
tmonV2ADevDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A description of the devie on which this point appears."
|
||||||
|
::= {tmonV2AlarmEntry 17}
|
||||||
|
|
||||||
|
-- structure used to issue a command to tmonV2XM element
|
||||||
|
|
||||||
|
tmonV2CommandGrid OBJECT IDENTIFIER ::= {tmonV2XM 3}
|
||||||
|
|
||||||
|
tmonV2CPType OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Tmon point type."
|
||||||
|
::= {tmonV2CommandGrid 1}
|
||||||
|
|
||||||
|
tmonV2CPort OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Tmon port number."
|
||||||
|
::= {tmonV2CommandGrid 2}
|
||||||
|
|
||||||
|
tmonV2CAddress OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..9999)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Tmon_port address number."
|
||||||
|
::= {tmonV2CommandGrid 3}
|
||||||
|
|
||||||
|
tmonV2CDisplay OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Tmon_port_address display number."
|
||||||
|
::= {tmonV2CommandGrid 4}
|
||||||
|
|
||||||
|
tmonV2CPoint OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..64)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Tmon_port_display point number (1-64)."
|
||||||
|
::= {tmonV2CommandGrid 5}
|
||||||
|
|
||||||
|
tmonV2CEvent OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Tmon event ID."
|
||||||
|
::= {tmonV2CommandGrid 6}
|
||||||
|
|
||||||
|
tmonV2CAction OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { latch(1),
|
||||||
|
release(2),
|
||||||
|
momentary(3),
|
||||||
|
ack(17),
|
||||||
|
tag(18),
|
||||||
|
untag(19)
|
||||||
|
}
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Requested command action (tmonV2XM will ignore if invalid)."
|
||||||
|
::= {tmonV2CommandGrid 7}
|
||||||
|
|
||||||
|
tmonV2CAuxText OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
||||||
|
command (i.e. User_initials)."
|
||||||
|
::= {tmonV2CommandGrid 8}
|
||||||
|
|
||||||
|
tmonV2CResult OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { success(1),
|
||||||
|
failure(2),
|
||||||
|
pending(3)
|
||||||
|
}
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Command result."
|
||||||
|
::= {tmonV2CommandGrid 9}
|
||||||
|
|
||||||
|
|
||||||
|
|
||||||
|
dpsRTUv2 OBJECT IDENTIFIER ::= {dpsAlarmControl 4}
|
||||||
|
|
||||||
|
dpsRTUv2Ident OBJECT IDENTIFIER ::= {dpsRTUv2 1}
|
||||||
|
|
||||||
|
dpsRTUv2Manufacturer OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The Remote Telemetry Unit manufacturer."
|
||||||
|
::= {dpsRTUv2Ident 1}
|
||||||
|
|
||||||
|
dpsRTUv2Model OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The RTU model designation."
|
||||||
|
::= {dpsRTUv2Ident 2}
|
||||||
|
|
||||||
|
dpsRTUv2FirmwareVersion OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The RTU firmware version."
|
||||||
|
::= {dpsRTUv2Ident 3}
|
||||||
|
|
||||||
|
dpsRTUv2DateTime OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The RTU system date and time."
|
||||||
|
::= {dpsRTUv2Ident 4}
|
||||||
|
|
||||||
|
dpsRTUv2SyncReq OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { sync(1)
|
||||||
|
}
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Caution: SETting this object initiates traps for all
|
||||||
|
standing alarms."
|
||||||
|
::= {dpsRTUv2Ident 5}
|
||||||
|
|
||||||
|
|
||||||
|
-- structure used to access displays managed by this RTU
|
||||||
|
|
||||||
|
dpsRTUv2DisplayGrid OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF DPSrtuV2DispEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Holds information on displays managed by the RTU."
|
||||||
|
::= {dpsRTUv2 2}
|
||||||
|
|
||||||
|
dpsRTUv2DisplayEntry OBJECT-TYPE
|
||||||
|
SYNTAX DPSrtuV2DispEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Information about a particular RTU display."
|
||||||
|
INDEX {dpsRTUv2Port, dpsRTUv2Address, dpsRTUv2Display}
|
||||||
|
::= {dpsRTUv2DisplayGrid 1}
|
||||||
|
|
||||||
|
DPSrtuV2DispEntry ::= SEQUENCE { dpsRTUv2Port Integer32,
|
||||||
|
dpsRTUv2Address Integer32,
|
||||||
|
dpsRTUv2Display Integer32,
|
||||||
|
dpsRTUv2DispDesc DisplayString,
|
||||||
|
dpsRTUv2PntMap DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
dpsRTUv2Port OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU port number."
|
||||||
|
::= {dpsRTUv2DisplayEntry 1}
|
||||||
|
|
||||||
|
dpsRTUv2Address OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..9999)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port address number."
|
||||||
|
::= {dpsRTUv2DisplayEntry 2}
|
||||||
|
|
||||||
|
dpsRTUv2Display OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port_address display number."
|
||||||
|
::= {dpsRTUv2DisplayEntry 3}
|
||||||
|
|
||||||
|
dpsRTUv2DispDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A description of the associated display."
|
||||||
|
::= {dpsRTUv2DisplayEntry 4}
|
||||||
|
|
||||||
|
dpsRTUv2PntMap OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A map of the points appearing in this display."
|
||||||
|
::= {dpsRTUv2DisplayEntry 5}
|
||||||
|
|
||||||
|
|
||||||
|
-- structure used to issue a control to a managed point
|
||||||
|
|
||||||
|
dpsRTUv2ControlGrid OBJECT IDENTIFIER ::= {dpsRTUv2 3}
|
||||||
|
|
||||||
|
dpsRTUv2CPort OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU port number."
|
||||||
|
::= {dpsRTUv2ControlGrid 1}
|
||||||
|
|
||||||
|
dpsRTUv2CAddress OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..9999)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port address number."
|
||||||
|
::= {dpsRTUv2ControlGrid 2}
|
||||||
|
|
||||||
|
dpsRTUv2CDisplay OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port_address display number."
|
||||||
|
::= {dpsRTUv2ControlGrid 3}
|
||||||
|
|
||||||
|
dpsRTUv2CPoint OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..64)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port_display point number (1-64)."
|
||||||
|
::= {dpsRTUv2ControlGrid 4}
|
||||||
|
|
||||||
|
dpsRTUv2CAction OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { latch(1),
|
||||||
|
release(2),
|
||||||
|
momentary(3)
|
||||||
|
}
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Requested action on point (RTU will ignore if invalid)."
|
||||||
|
::= {dpsRTUv2ControlGrid 5}
|
||||||
|
|
||||||
|
|
||||||
|
|
||||||
|
dpsRTUv2AlarmGrid OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF DPSrtuV2AlarmEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Holds individual alarm point information."
|
||||||
|
::= {dpsRTUv2 5}
|
||||||
|
|
||||||
|
dpsRTUv2AlarmEntry OBJECT-TYPE
|
||||||
|
SYNTAX DPSrtuV2AlarmEntry
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Detailed information about a particular RTU display."
|
||||||
|
INDEX {dpsRTUv2APort, dpsRTUv2AAddress, dpsRTUv2ADisplay, dpsRTUv2APoint}
|
||||||
|
::= {dpsRTUv2AlarmGrid 1}
|
||||||
|
|
||||||
|
DPSrtuV2AlarmEntry ::= SEQUENCE { dpsRTUv2APort Integer32,
|
||||||
|
dpsRTUv2AAddress Integer32,
|
||||||
|
dpsRTUv2ADisplay Integer32,
|
||||||
|
dpsRTUv2APoint Integer32,
|
||||||
|
dpsRTUv2APntDesc DisplayString,
|
||||||
|
dpsRTUv2AState DisplayString
|
||||||
|
}
|
||||||
|
|
||||||
|
dpsRTUv2APort OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU port number."
|
||||||
|
::= {dpsRTUv2AlarmEntry 1}
|
||||||
|
|
||||||
|
dpsRTUv2AAddress OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..9999)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port address number."
|
||||||
|
::= {dpsRTUv2AlarmEntry 2}
|
||||||
|
|
||||||
|
dpsRTUv2ADisplay OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port_address display number."
|
||||||
|
::= {dpsRTUv2AlarmEntry 3}
|
||||||
|
|
||||||
|
dpsRTUv2APoint OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..64)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port_address_display point number."
|
||||||
|
::= {dpsRTUv2AlarmEntry 4}
|
||||||
|
|
||||||
|
dpsRTUv2APntDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A description of this point."
|
||||||
|
::= {dpsRTUv2AlarmEntry 5}
|
||||||
|
|
||||||
|
dpsRTUv2AState OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The current state of this point."
|
||||||
|
::= {dpsRTUv2AlarmEntry 6}
|
||||||
|
|
||||||
|
|
||||||
|
--Table for accessing analog channel value
|
||||||
|
|
||||||
|
analogChannelsv2 OBJECT-TYPE
|
||||||
|
SYNTAX SEQUENCE OF ChannelEntryv2
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Holds information on analog channels"
|
||||||
|
::= {dpsRTUv2 6}
|
||||||
|
|
||||||
|
channelEntryv2 OBJECT-TYPE
|
||||||
|
SYNTAX ChannelEntryv2
|
||||||
|
MAX-ACCESS not-accessible
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Information about a particular channel"
|
||||||
|
INDEX {channelNumberv2}
|
||||||
|
::= {analogChannelsv2 1}
|
||||||
|
|
||||||
|
ChannelEntryv2 ::= SEQUENCE { channelNumberv2 Integer32,
|
||||||
|
enabledv2 Integer32,
|
||||||
|
descriptionv2 DisplayString,
|
||||||
|
valuev2 DisplayString,
|
||||||
|
thresholdsv2 Integer32
|
||||||
|
}
|
||||||
|
|
||||||
|
channelNumberv2 OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (0..2147483647)
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Input channel number"
|
||||||
|
::= {channelEntryv2 1}
|
||||||
|
|
||||||
|
enabledv2 OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { disabled (0),
|
||||||
|
enabled (1)
|
||||||
|
}
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Enable status of channel"
|
||||||
|
::= {channelEntryv2 2}
|
||||||
|
|
||||||
|
descriptionv2 OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The user defined description of the channel"
|
||||||
|
::= {channelEntryv2 3}
|
||||||
|
|
||||||
|
valuev2 OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The current value of the channel"
|
||||||
|
::= {channelEntryv2 4}
|
||||||
|
|
||||||
|
thresholdsv2 OBJECT-TYPE
|
||||||
|
SYNTAX INTEGER { noAlarms (0),
|
||||||
|
minorUnder (1),
|
||||||
|
minorOver (2),
|
||||||
|
majorUnder (3),
|
||||||
|
majorOver (4),
|
||||||
|
notDetected (5)
|
||||||
|
}
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed"
|
||||||
|
::= {channelEntryv2 5}
|
||||||
|
|
||||||
|
-- TRAP definitions
|
||||||
|
|
||||||
|
tmonV2CRalarmSet NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a critical alarm is set."
|
||||||
|
-- ::= {tmonV2XM 10}
|
||||||
|
::= {tmonXM 10}
|
||||||
|
|
||||||
|
|
||||||
|
tmonV2CRalarmClr NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a critical alarm clears."
|
||||||
|
-- ::= {tmonV2XM 11}
|
||||||
|
::= {tmonXM 11}
|
||||||
|
|
||||||
|
tmonV2MJalarmSet NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a major alarm is set."
|
||||||
|
-- ::= {tmonV2XM 12}
|
||||||
|
::= {tmonXM 12}
|
||||||
|
|
||||||
|
tmonV2MJalarmClr NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a major alarm clears."
|
||||||
|
-- ::= {tmonV2XM 13}
|
||||||
|
::= {tmonXM 13}
|
||||||
|
|
||||||
|
tmonV2MNalarmSet NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a minor alarm is set."
|
||||||
|
-- ::= {tmonV2XM 14}
|
||||||
|
::= {tmonXM 14}
|
||||||
|
|
||||||
|
tmonV2MNalarmClr NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a minor alarm clears."
|
||||||
|
-- ::= {tmonV2XM 15}
|
||||||
|
::= {tmonXM 15}
|
||||||
|
|
||||||
|
tmonV2STalarmSet NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a status alarm is set."
|
||||||
|
-- ::= {tmonV2XM 16}
|
||||||
|
::= {tmonXM 16}
|
||||||
|
|
||||||
|
tmonV2STalarmClr NOTIFICATION-TYPE
|
||||||
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
||||||
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
||||||
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
||||||
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when a status alarm clears."
|
||||||
|
-- ::= {tmonV2XM 17}
|
||||||
|
::= {tmonXM 17}
|
||||||
|
|
||||||
|
--dpsRTUv2PointSet NOTIFICATION-TYPE
|
||||||
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2AAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- STATUS current
|
||||||
|
-- DESCRIPTION "Generated when a point is set."
|
||||||
|
-- ::= {dpsRTUv2 20}
|
||||||
|
--
|
||||||
|
--dpsRTUv2PointClr NOTIFICATION-TYPE
|
||||||
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- STATUS current
|
||||||
|
-- DESCRIPTION "Generated when a point clears."
|
||||||
|
-- ::= {dpsRTUv2 21}
|
||||||
|
--
|
||||||
|
--dpsRTUv2sumPSet NOTIFICATION-TYPE
|
||||||
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
||||||
|
-- STATUS current
|
||||||
|
-- DESCRIPTION "Generated when any point is set."
|
||||||
|
-- ::= {dpsRTUv2 101}
|
||||||
|
--
|
||||||
|
--dpsRTUv2sumPClr NOTIFICATION-TYPE
|
||||||
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
||||||
|
-- STATUS current
|
||||||
|
-- DESCRIPTION "Generated when all points clear."
|
||||||
|
-- ::= {dpsRTUv2 102}
|
||||||
|
--
|
||||||
|
--dpsRTUv2comFailed NOTIFICATION-TYPE
|
||||||
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
||||||
|
-- STATUS current
|
||||||
|
-- DESCRIPTION "Generated when polled unit fails to respond."
|
||||||
|
-- ::= {dpsRTUv2 103}
|
||||||
|
--
|
||||||
|
--dpsRTUv2comRestored NOTIFICATION-TYPE
|
||||||
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
||||||
|
-- STATUS current
|
||||||
|
-- DESCRIPTION "Generated when failed unit resumes responding."
|
||||||
|
-- ::= {dpsRTUv2 104}
|
||||||
|
--
|
||||||
|
-- **************************************************************************
|
||||||
|
-- Granular TRAP definitions
|
||||||
|
--
|
||||||
|
-- The following section supports granular trapping available on selected
|
||||||
|
-- DPS remote telemetry units. This software selectable facility changes the
|
||||||
|
-- trap sent by a remote so equipped. The standard trap identifies a SET or
|
||||||
|
-- CLR event in the trap ID and binds variables identifying the specific
|
||||||
|
-- remote point associated with the event. A granular trap identifies a SET
|
||||||
|
-- or CLR event and the specific point associated with the event all in the
|
||||||
|
-- trap ID. This is accomplished by mapping all SET event/points into the
|
||||||
|
-- trap ID range 10001-19999 and all CLR event/points into the trap ID range
|
||||||
|
-- 20001-29999.
|
||||||
|
-- If the unit manages multiple displays, the displays are mapped
|
||||||
|
-- sequentially with each display occupying a 64 point range. For example, a
|
||||||
|
-- standalone standard or timestamp KDA which manages two displays, reports
|
||||||
|
-- SET event/points in the first display (discrete alarm points) in the range
|
||||||
|
-- 10001-10064. The CLR event/points for the same display would be reported
|
||||||
|
-- in the range 20001-20064. The second display (controls & housekeeping
|
||||||
|
-- alarm points) would have its SET event/points reported in the range 10065-
|
||||||
|
-- 10128 and its CLR event/points reported in the range 20065-20128.
|
||||||
|
-- SET and CLR definitions for the first 64 points have been included and
|
||||||
|
-- can be used as is for driving most SNMP manager mechanisms designed to key
|
||||||
|
-- on the trap ID for distinguishing and managing events. Additional events
|
||||||
|
-- can be added simply by editing the following trap definitions prior to
|
||||||
|
-- compiling this file into your SNMP manager. We recommend managing the SET
|
||||||
|
-- and CLR event definitions for a specific point as a single unit and using
|
||||||
|
-- the following simple rules:
|
||||||
|
-- + Adjust the numeric portion of the label preceeding NOTIFICATION-TYPE.
|
||||||
|
-- + Adjust the numeric reference in the DESCRIPTION text.
|
||||||
|
-- + Adjust the number on the last line of the definition.
|
||||||
|
--
|
||||||
|
-- Using these rules a definition for the 65th point would be:
|
||||||
|
--
|
||||||
|
-- dpsRTUv2p0065Set NOTIFICATION-TYPE
|
||||||
|
-- ENTERPRISE dpsRTUv2
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 65 is set."
|
||||||
|
-- ::= 10065
|
||||||
|
--
|
||||||
|
-- dpsRTUv2p0065Clr NOTIFICATION-TYPE
|
||||||
|
-- ENTERPRISE dpsRTUv2
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 65 clears."
|
||||||
|
-- ::= 20065
|
||||||
|
--
|
||||||
|
-- This editing can can be accomplished quite easily using a plain ASCII
|
||||||
|
-- file editor. The repetitive structure of the definitions also makes for
|
||||||
|
-- rapid scripted or programmed generation if any such tools are available.
|
||||||
|
-- A compressed file containing event/point definitions for 144 displays is
|
||||||
|
-- available (DPS_G36.zip 150K) which uncompressed (DPS_G36.mib 6.2M) can be
|
||||||
|
-- used for cut-and-paste editing if desired.
|
||||||
|
-- The definitions can be further customized if desired by similar editing
|
||||||
|
-- prior to compiling carefully observing the following conventions:
|
||||||
|
-- + The label preceeding the NOTIFICATION-TYPE designator can be edited with some
|
||||||
|
-- freedom but the label must be utterly unique among all trap definitions.
|
||||||
|
-- + The ENTERPRISE and VARIABLES sections must not be changed.
|
||||||
|
-- + The DESCRIPTION can be edited with complete freedom and is typically
|
||||||
|
-- ignored within the context of standard SNMP manager trap handling. The
|
||||||
|
-- quote mark before and after the text of the description are required.
|
||||||
|
-- + The number on the last line of the definition is the actual trap ID
|
||||||
|
-- defined and must also be utterly unique.
|
||||||
|
--
|
||||||
|
-- For example:
|
||||||
|
--
|
||||||
|
-- dpsRTUv2p0001Set NOTIFICATION-TYPE
|
||||||
|
-- ENTERPRISE dpsRTUv2
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 1 is set."
|
||||||
|
-- ::= 10001
|
||||||
|
--
|
||||||
|
-- dpsRTUv2p0001Clr NOTIFICATION-TYPE
|
||||||
|
-- ENTERPRISE dpsRTUv2
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- DESCRIPTION "Generated when granular point 1 clears."
|
||||||
|
-- ::= 20001
|
||||||
|
--
|
||||||
|
-- Could be customized as:
|
||||||
|
--
|
||||||
|
-- dpsRTUv2FireAlarm NOTIFICATION-TYPE
|
||||||
|
-- ENTERPRISE dpsRTUv2
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- DESCRIPTION "Generated when smoke detector activates."
|
||||||
|
-- ::= 10001
|
||||||
|
--
|
||||||
|
-- dpsRTUv2FireOut NOTIFICATION-TYPE
|
||||||
|
-- ENTERPRISE dpsRTUv2
|
||||||
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
||||||
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
||||||
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
||||||
|
-- DESCRIPTION "Generated when smoke detector deactivates."
|
||||||
|
-- ::= 20001
|
||||||
|
-- **************************************************************************
|
||||||
|
|
||||||
|
|
||||||
|
END
|
1187
mibs/dpstelecom/DPS-MIB-V38-V2EXT
Normal file
1187
mibs/dpstelecom/DPS-MIB-V38-V2EXT
Normal file
File diff suppressed because it is too large
Load Diff
171
mibs/dpstelecom/DPS-TEXT-RTU-MIB
Normal file
171
mibs/dpstelecom/DPS-TEXT-RTU-MIB
Normal file
@@ -0,0 +1,171 @@
|
|||||||
|
-- Title: DPS-TEXT-RTU.MIB
|
||||||
|
-- Version: v1.0 for SNMPv2c
|
||||||
|
--
|
||||||
|
-- Copyright @ 2011 DPS Inc. All Rights Reserved
|
||||||
|
--
|
||||||
|
-- This MIB defines objects for the DPS TEXT RTU products.
|
||||||
|
--
|
||||||
|
-- DPS CBH 8/2011
|
||||||
|
--
|
||||||
|
|
||||||
|
DPS-TEXT-RTU-MIB DEFINITIONS ::= BEGIN
|
||||||
|
|
||||||
|
IMPORTS
|
||||||
|
DisplayString
|
||||||
|
FROM SNMPv2-TC
|
||||||
|
OBJECT-TYPE
|
||||||
|
FROM SNMPv2-SMI
|
||||||
|
NOTIFICATION-TYPE
|
||||||
|
FROM SNMPv2-SMI
|
||||||
|
Integer32
|
||||||
|
FROM SNMPv2-SMI
|
||||||
|
dpsAlarmControl
|
||||||
|
FROM DPS-MIB-V38;
|
||||||
|
|
||||||
|
dpsTEXTRTUv2 OBJECT IDENTIFIER ::= {dpsAlarmControl 5}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2Ident OBJECT IDENTIFIER ::= {dpsTEXTRTUv2 1}
|
||||||
|
|
||||||
|
--Textual Conventions
|
||||||
|
|
||||||
|
AnalogThresholds ::= TEXTUAL-CONVENTION
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed. Will be blank if alarm is not from an analog sources"
|
||||||
|
SYNTAX INTEGER {
|
||||||
|
noAlarms (0),
|
||||||
|
minorUnder (1),
|
||||||
|
minorOver (2),
|
||||||
|
majorUnder (3),
|
||||||
|
majorOver (4),
|
||||||
|
notDetected (5)
|
||||||
|
}
|
||||||
|
|
||||||
|
RTUCAction ::= TEXTUAL-CONVENTION
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Requested action. Latch, release, and momentary will affect relays. Sync(s) will resend traps for currently active alarms(TEXT RTU will ignore if invalid)."
|
||||||
|
SYNTAX INTEGER {
|
||||||
|
latch(1),
|
||||||
|
release(2),
|
||||||
|
momentary(3),
|
||||||
|
syncStanding(4),
|
||||||
|
syncAnalogs(5)
|
||||||
|
}
|
||||||
|
|
||||||
|
--Device identifying objects
|
||||||
|
|
||||||
|
dpsTEXTRTUv2DateTime OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The RTU system date and time."
|
||||||
|
::= {dpsTEXTRTUv2Ident 1}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2DeviceType OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Device type of far end SMS device as received in SMS messages to SMS receiver. ie NG216_G3"
|
||||||
|
::= {dpsTEXTRTUv2Ident 2}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2Phone OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The phone number of the far end or originating SMS RTU, only SMS RTUs will have/respond to this variable"
|
||||||
|
::= {dpsTEXTRTUv2Ident 3}
|
||||||
|
|
||||||
|
|
||||||
|
-- Alarm identifying objects
|
||||||
|
|
||||||
|
dpsTEXTRTUv2AlarmGrid OBJECT IDENTIFIER ::= {dpsTEXTRTUv2 2}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2ADisplay OBJECT-TYPE
|
||||||
|
SYNTAX Integer32
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "TEXT RTU display number. See the usermanual for display mapping information"
|
||||||
|
::= {dpsTEXTRTUv2AlarmGrid 1}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2APoint OBJECT-TYPE
|
||||||
|
SYNTAX Integer32
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "TEXT RTU point number. See the usermanual for point mapping information"
|
||||||
|
::= {dpsTEXTRTUv2AlarmGrid 2}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2APntDesc OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "A description of this point."
|
||||||
|
::= {dpsTEXTRTUv2AlarmGrid 3}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2AState OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The current state of this point."
|
||||||
|
::= {dpsTEXTRTUv2AlarmGrid 4}
|
||||||
|
|
||||||
|
dpsTEXTRTUAnalogvalue OBJECT-TYPE
|
||||||
|
SYNTAX DisplayString
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "The current value of the channel. Will be blank if alarm is not from an analog source"
|
||||||
|
::= {dpsTEXTRTUv2AlarmGrid 5}
|
||||||
|
|
||||||
|
dpsTEXTRTUAnalogthresholds OBJECT-TYPE
|
||||||
|
SYNTAX AnalogThresholds
|
||||||
|
MAX-ACCESS read-only
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed. Will be blank if alarm is not from an analog sources"
|
||||||
|
::= {dpsTEXTRTUv2AlarmGrid 6}
|
||||||
|
|
||||||
|
-- TEXT RTU Control Commands
|
||||||
|
|
||||||
|
dpsTEXTRTUv2ControlGrid OBJECT IDENTIFIER ::= {dpsTEXTRTUv2 3}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2CDisplay OBJECT-TYPE
|
||||||
|
SYNTAX Integer32
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port_address display number."
|
||||||
|
::= {dpsTEXTRTUv2ControlGrid 1}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2CPoint OBJECT-TYPE
|
||||||
|
SYNTAX Integer32 (1..64)
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "RTU_port_display point number (1-64)."
|
||||||
|
::= {dpsTEXTRTUv2ControlGrid 2}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2CMOMTime OBJECT-TYPE
|
||||||
|
SYNTAX Integer32
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Momentary latch time (in milliseconds). If value is blank, the default of 600ms will be used"
|
||||||
|
::= {dpsTEXTRTUv2ControlGrid 3}
|
||||||
|
|
||||||
|
dpsTEXTRTUv2CAction OBJECT-TYPE
|
||||||
|
SYNTAX RTUCAction
|
||||||
|
MAX-ACCESS read-write
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Requested action. Latch, release, and momentary will affect relays. Sync(s) will resend traps for currently active alarms(TEXT RTU will ignore if invalid)."
|
||||||
|
::= {dpsTEXTRTUv2ControlGrid 4}
|
||||||
|
|
||||||
|
|
||||||
|
-- DPS SMS RTU traps. Traps generated from SMS receiver indicating event on far end SMS RTU
|
||||||
|
|
||||||
|
dpsTEXTRTUv2AlarmSet NOTIFICATION-TYPE
|
||||||
|
OBJECTS { sysDescr, sysLocation, dpsTEXTRTUv2DateTime, dpsTEXTRTUv2DeviceType, dpsTEXTRTUv2Phone, dpsTEXTRTUv2ADisplay, dpsTEXTRTUv2APoint, dpsTEXTRTUv2APntDesc, dpsTEXTRTUv2AState, dpsTEXTRTUAnalogvalue }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when alarm is received from far end SMS device to SMS receiver."
|
||||||
|
::= { dpsTEXTRTUv2 100 }
|
||||||
|
|
||||||
|
dpsTEXTRTUv2AlarmClear NOTIFICATION-TYPE
|
||||||
|
OBJECTS { sysDescr, sysLocation, dpsTEXTRTUv2DateTime, dpsTEXTRTUv2DeviceType, dpsTEXTRTUv2Phone, dpsTEXTRTUv2ADisplay, dpsTEXTRTUv2APoint, dpsTEXTRTUv2APntDesc, dpsTEXTRTUv2AState, dpsTEXTRTUAnalogvalue }
|
||||||
|
STATUS current
|
||||||
|
DESCRIPTION "Generated when clear is received from far end SMS device to SMS receiver."
|
||||||
|
::= { dpsTEXTRTUv2 200 }
|
||||||
|
|
||||||
|
END
|
2
tests/snmpsim/netguardian.snmprec
Normal file
2
tests/snmpsim/netguardian.snmprec
Normal file
@@ -0,0 +1,2 @@
|
|||||||
|
1.3.6.1.2.1.1.1.0|4|NetGuardian864-G5 v5.4P.0026
|
||||||
|
1.3.6.1.2.1.1.2.0|6|1.3.6.1.4.1.2682
|
Reference in New Issue
Block a user