mib: CPQPOWER-MIB modules: sensors: current: data: - oid: pduOutputBreakerTable value: breakerCurrent num_oid: '.1.3.6.1.4.1.232.165.2.3.2.1.3.{{ $index }}' index: 'breakerCurrent.{{ $index }}' descr: 'PDU {{ $subindex0 }} Phase {{ $subindex1 }}' skip_values: -1 load: data: - oid: pduOutputBreakerTable value: breakerPercentLoad num_oid: '.1.3.6.1.4.1.232.165.2.3.2.1.4.{{ $index }}' index: 'breakerPercentLoad.{{ $index }}' descr: 'PDU {{ $subindex0 }} Phase {{ $subindex1 }}' skip_values: -1 - oid: pduOutputTable value: pduOutputLoad num_oid: '.1.3.6.1.4.1.232.165.2.3.1.1.2.{{ $index }}' index: 'pduOutputLoad.{{ $index }}' descr: 'PDU {{ $index }}' skip_values: -1 voltage: data: - oid: pduOutputBreakerTable value: breakerVoltage num_oid: '.1.3.6.1.4.1.232.165.2.3.2.1.2.{{ $index }}' index: 'breakerVoltage.{{ $index }}' descr: 'PDU {{ $subindex0 }} Phase {{ $subindex1 }}' skip_values: -1 power: data: - oid: pduOutputTable value: pduOutputPower num_oid: '.1.3.6.1.4.1.232.165.2.3.1.1.4.{{ $index }}' index: 'pduOutputPower.{{ $index }}' descr: 'PDU {{ $index }}' skip_values: -1 state: data: - oid: pduIdentTable value: pduStatus num_oid: '.1.3.6.1.4.1.232.165.2.1.2.1.8.{{ $index }}' descr: 'PDU {{ $index }}' states: - { value: 1, generic: 3, descr: other, graph: 0 } - { value: 2, generic: 0, descr: ok, graph: 0 } - { value: 3, generic: 1, descr: degraded, graph: 0 } - { value: 4, generic: 2, descr: failed, graph: 0 }