MG-SNMP-UPS-MIB DEFINITIONS ::= BEGIN
 | 
						|
 | 
						|
-- Title:       UPS MIB
 | 
						|
-- Date:        October 11, 1995
 | 
						|
-- Author:      MGE UPS SYSTEMS
 | 
						|
-- Release:     V1.6
 | 
						|
 | 
						|
-- Date:        October 23, 2003
 | 
						|
-- Author:      MGE UPS SYSTEMS
 | 
						|
-- Release:     V1.7 AB - Add variables for Environment sensor, see comments beginning with AB Release
 | 
						|
 | 
						|
-- Date:        November 22, 2004
 | 
						|
-- Author:      MGE UPS SYSTEMS - PV
 | 
						|
-- Release:     V1.7 AC - Add compatibility with SMI V2  
 | 
						|
 | 
						|
IMPORTS
 | 
						|
        enterprises,IpAddress,TimeTicks
 | 
						|
                FROM RFC1155-SMI
 | 
						|
        DisplayString
 | 
						|
                FROM RFC1213-MIB
 | 
						|
        OBJECT-TYPE
 | 
						|
                FROM RFC-1212
 | 
						|
        TRAP-TYPE
 | 
						|
                FROM RFC-1215;
 | 
						|
 | 
						|
----
 | 
						|
-- Path to the root
 | 
						|
----
 | 
						|
merlinGerin     OBJECT IDENTIFIER ::= { enterprises 705 }
 | 
						|
upsmg          OBJECT IDENTIFIER ::= { merlinGerin 1 }
 | 
						|
 | 
						|
-- Management and Configuration groups of the MIB
 | 
						|
upsmgIdent        OBJECT IDENTIFIER ::= { upsmg 1 }
 | 
						|
upsmgManagement   OBJECT IDENTIFIER ::= { upsmg 2 }
 | 
						|
upsmgReceptacle   OBJECT IDENTIFIER ::= { upsmg 3 }
 | 
						|
upsmgConfig       OBJECT IDENTIFIER ::= { upsmg 4 }
 | 
						|
 | 
						|
-- UPS Monitoring groups of the MIB
 | 
						|
upsmgBattery      OBJECT IDENTIFIER ::= { upsmg 5 }
 | 
						|
upsmgInput        OBJECT IDENTIFIER ::= { upsmg 6 }
 | 
						|
upsmgOutput       OBJECT IDENTIFIER ::= { upsmg 7 }
 | 
						|
upsmgEnviron      OBJECT IDENTIFIER ::= { upsmg 8 }
 | 
						|
 | 
						|
-- UPS Controlling groups of the MIB
 | 
						|
upsmgControl      OBJECT IDENTIFIER ::= { upsmg 9 }
 | 
						|
upsmgTest         OBJECT IDENTIFIER ::= { upsmg 10 }
 | 
						|
upsmgTraps        OBJECT IDENTIFIER ::= { upsmg 11 }
 | 
						|
 | 
						|
upsmgAgent        OBJECT IDENTIFIER ::= { upsmg 12 }
 | 
						|
upsmgRemote       OBJECT IDENTIFIER ::= { upsmg 13 }
 | 
						|
 | 
						|
----
 | 
						|
-- Definition of object types
 | 
						|
----
 | 
						|
 | 
						|
-- Management and Configuration groups of the MIB:
 | 
						|
-- upsmgIdent(1), upsmgManagement(2), upsmgReceptacle(3), upsmgConfig(4)
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgIdent group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
upsmgIdentFamilyName OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS family name (e.g. `PULSAR', `COMET', `GALAXY', ...)."
 | 
						|
        ::= { upsmgIdent 1 }
 | 
						|
 | 
						|
upsmgIdentModelName OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS model name (e.g. `PSX20', `SV9', ... )."
 | 
						|
        ::= { upsmgIdent 2 }
 | 
						|
 | 
						|
upsmgIdentRevisionLevel OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS revision level."
 | 
						|
        ::= { upsmgIdent 3 }
 | 
						|
 | 
						|
upsmgIdentFirmwareVersion OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS microprocessor firmware version number."
 | 
						|
        ::= { upsmgIdent 4 }
 | 
						|
 | 
						|
upsmgIdentUserID OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS user identification (set by administrator)."
 | 
						|
        ::= { upsmgIdent 5 }
 | 
						|
 | 
						|
upsmgIdentInstallationDate OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS installation date in dd/mm/yy format."
 | 
						|
        ::= { upsmgIdent 6 }
 | 
						|
 | 
						|
upsmgIdentSerialNumber OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS manufacturing serial number."
 | 
						|
        ::= { upsmgIdent 7 }
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgManagement group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
-- This group gives objects for description of a list of Managers.
 | 
						|
-- A management platform is identified, can be powered by the UPS,
 | 
						|
-- and is allowed to a certain level of management.
 | 
						|
 | 
						|
upsmgManagersNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The number of managers that could manage the UPS."
 | 
						|
        ::= { upsmgManagement 1 }
 | 
						|
 | 
						|
upsmgManagersTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgManagersEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of managers."
 | 
						|
        ::= { upsmgManagement 2 }
 | 
						|
 | 
						|
upsmgManagersEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgManagersEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of a manager entry in the managers table."
 | 
						|
        INDEX   { mgmanagerIndex }
 | 
						|
        ::= { upsmgManagersTable 1 }
 | 
						|
 | 
						|
UpsmgManagersEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgmanagerIndex INTEGER,
 | 
						|
        mgmanagerDeviceNumber INTEGER,
 | 
						|
        mgmanagerNMSType INTEGER,
 | 
						|
        mgmanagerCommType INTEGER,
 | 
						|
        mgmanagerDescr DisplayString,
 | 
						|
        mgmanagerAddress IpAddress,
 | 
						|
        mgmanagerCommunity DisplayString,
 | 
						|
        mgmanagerSeverityLevel INTEGER,
 | 
						|
        mgmanagerTrapAck INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgmanagerIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A unique value for each manager. Its value ranges between 1
 | 
						|
                and the value of upsmgManagersNum."
 | 
						|
        ::= { upsmgManagersEntry 1 }
 | 
						|
 | 
						|
mgmanagerDeviceNumber OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "This object is the number of the manager device in the
 | 
						|
                DevicesTable of the Config group. This means that the
 | 
						|
                manager is powered by the UPS. If not the default value is 0."
 | 
						|
        ::= { upsmgManagersEntry 2 }
 | 
						|
 | 
						|
mgmanagerNMSType OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                umclient(1),
 | 
						|
                decnetview(2),
 | 
						|
                umview(3),
 | 
						|
                dview(4),
 | 
						|
                hpopenview(5),
 | 
						|
                sunnetmanager(6),
 | 
						|
                novellnms(7),
 | 
						|
                ibmnetview(8),
 | 
						|
                other(9),
 | 
						|
                autolearning(10)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The type of manager according to the NMS platform. We
 | 
						|
                include in the manager class all systems which will be
 | 
						|
                notified by the agent via receiving traps (e.g. basic
 | 
						|
                to complex NMS software)."
 | 
						|
        ::= { upsmgManagersEntry 3 }
 | 
						|
 | 
						|
mgmanagerCommType OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                other(1),       -- none of the following
 | 
						|
                invalid(2),     -- an invalidated manager
 | 
						|
                cmip(3),        -- OSI CMIP
 | 
						|
                snmpv1(4),      -- SNMPv1
 | 
						|
                snmpv2(5)       -- SNMPv2
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The level of communication protocol for that manager.
 | 
						|
                Setting this object to value invalid(2) has the effect of
 | 
						|
                invalidating the corresponding entry in the upsmgManagersTable.
 | 
						|
                It is an implementation-specific matter as to wether the agent
 | 
						|
                removes an invalidated entry from the table. Accordingly,
 | 
						|
                management stations must be prepared to receive tabular
 | 
						|
                information from agents that corresponds to entry not currently
 | 
						|
                in use. Proper interpretation of such entries requires
 | 
						|
                examination of the relevant mgmanagerCommType object."
 | 
						|
        ::= { upsmgManagersEntry 4 }
 | 
						|
 | 
						|
mgmanagerDescr OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A textual string containing information about the manager.
 | 
						|
                (manufacturer and version description)."
 | 
						|
        ::= { upsmgManagersEntry 5 }
 | 
						|
 | 
						|
mgmanagerAddress OBJECT-TYPE
 | 
						|
        SYNTAX IpAddress
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The IP address of the manager station receiving traps. The
 | 
						|
                value of this object is meaningful if and only if the value
 | 
						|
                of the relevant mgmanagerCommType object is snmp type."
 | 
						|
        ::= { upsmgManagersEntry 6 }
 | 
						|
 | 
						|
mgmanagerCommunity OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The manager community string."
 | 
						|
        ::= { upsmgManagersEntry 7 }
 | 
						|
 | 
						|
mgmanagerSeverityLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The severity level of traps to be received by this manager."
 | 
						|
        ::= { upsmgManagersEntry 8 }
 | 
						|
 | 
						|
mgmanagerTrapAck OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                mgack(1),
 | 
						|
                mgnoack(2),
 | 
						|
                stdnomg(3),
 | 
						|
                mgacks(4),
 | 
						|
                cpqnoack(5)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The manager Trap Acknowledgement status. Setting
 | 
						|
                this object to mgnoack(2) or stdnomg(3) or cpqnoack(5)
 | 
						|
                disables the trap acknowledgement from the related
 | 
						|
                manager. The MG enterprise specific trap should then
 | 
						|
                be sent only once by the agent to this manager in case
 | 
						|
                of mgnoack(2), and should not be sent by the agent to
 | 
						|
                this manager in case of stdnomg(3) or cpqnoack(5).
 | 
						|
                mgack(1) allows a basic mecanism for acknowledged
 | 
						|
                traps using upsmgAgentTrapAck object set by the
 | 
						|
                manager to the enterprise specific number of the trap.
 | 
						|
                mgacks(5) allows the enhanced mecanism using the
 | 
						|
                upsmgAgentTrapSignature object set by the manager
 | 
						|
                to the signature received within the trap var binding."
 | 
						|
        ::= { upsmgManagersEntry 9 }
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgReceptacle group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
-- This group gives objects for description of the receptacles of the
 | 
						|
-- UPS. The receptacle notion has been extended to many configurations:
 | 
						|
-- For a small simple UPS, there is only one receptacle which corresponds
 | 
						|
-- to the output of the UPS.
 | 
						|
-- For a more complex UPS with powershare capabilities, there is a one-level
 | 
						|
-- receptacle table allowing to distribute ON/OFF control on the receptacles.
 | 
						|
-- For others (EHQ, big UPS with Distributed Power Units), there is a
 | 
						|
-- two-level receptacle table allowing to distribute control and management
 | 
						|
-- of the receptacles plugs into one of the first level receptacles.
 | 
						|
 | 
						|
upsmgReceptaclesNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The total number of receptacles controlled by the UPS."
 | 
						|
        ::= { upsmgReceptacle 1 }
 | 
						|
 | 
						|
upsmgReceptaclesTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgReceptaclesEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of receptacles that are controlled by the UPS."
 | 
						|
        ::= { upsmgReceptacle 2 }
 | 
						|
 | 
						|
upsmgReceptaclesEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgReceptaclesEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of a receptacle in the table."
 | 
						|
        INDEX   { mgreceptacleIndex }
 | 
						|
        ::= { upsmgReceptaclesTable 1 }
 | 
						|
 | 
						|
UpsmgReceptaclesEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgreceptacleIndex INTEGER,
 | 
						|
        mgreceptacleLevel INTEGER,
 | 
						|
        mgreceptacleType DisplayString,
 | 
						|
        mgreceptacleIdent DisplayString,
 | 
						|
        mgreceptacleState INTEGER,
 | 
						|
        mgreceptacleReceptacle INTEGER,
 | 
						|
        mgreceptaclePowerCons INTEGER,
 | 
						|
        mgreceptacleOverload INTEGER,
 | 
						|
        mgreceptacleAutonomy INTEGER
 | 
						|
 }
 | 
						|
 | 
						|
mgreceptacleIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A unique value for each receptacle. Its value ranges between
 | 
						|
                1 and the value of upsmgReceptaclesNum."
 | 
						|
        ::= { upsmgReceptaclesEntry 1 }
 | 
						|
 | 
						|
mgreceptacleLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The level of receptacle.
 | 
						|
 | 
						|
                Setting this object to value invalid(2) has the effect of
 | 
						|
                invalidating the corresponding entry in the upsmgReceptaclesTable.
 | 
						|
                It is an implementation-specific matter as to wether the agent
 | 
						|
                removes an invalidated entry from the table. Accordingly,
 | 
						|
                management stations must be prepared to receive tabular
 | 
						|
                information from agents that corresponds to entry not currently
 | 
						|
                in use. Proper interpretation of such entries requires
 | 
						|
                examination of the relevant receptacleLevel object.
 | 
						|
                Values 1 and 4 are reserved, value 3 is used to identify a simple
 | 
						|
                one-level receptacle, and values greater than 4 represent a
 | 
						|
                group of equivalent receptacles."
 | 
						|
        ::= { upsmgReceptaclesEntry 2 }
 | 
						|
 | 
						|
mgreceptacleType OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A textual string for the receptacle type."
 | 
						|
        ::= { upsmgReceptaclesEntry 3 }
 | 
						|
 | 
						|
mgreceptacleIdent OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A textual string identification for the user."
 | 
						|
        ::= { upsmgReceptaclesEntry 4 }
 | 
						|
 | 
						|
mgreceptacleState OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                manualON(1),    -- after manual turn on
 | 
						|
                manualOFF(2),   -- after manual turn off
 | 
						|
                normalON(3),    -- after normal restart sequence
 | 
						|
                normalOFF(4),   -- after normal shutoff sequence
 | 
						|
                controlON(5),   -- after upsControl on command
 | 
						|
                controlOFF(6),  -- after upsControl off command
 | 
						|
                scheduleON(7),  -- after schedule turn on
 | 
						|
                scheduleOFF(8)  -- after schedule turn off
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The ON/OFF status of the receptacle."
 | 
						|
        ::= { upsmgReceptaclesEntry 5 }
 | 
						|
 | 
						|
mgreceptacleReceptacle OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle number of the second level receptacle father.
 | 
						|
 | 
						|
                The value of this object is meaningful if and only if the value
 | 
						|
                of the relevant mgreceptacleType object is related to a two-level
 | 
						|
                receptacle class. Otherwise the default value is 0."
 | 
						|
        ::= { upsmgReceptaclesEntry 6 }
 | 
						|
 | 
						|
mgreceptaclePowerCons OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The volt-ampere rating of the receptacle.
 | 
						|
 | 
						|
                The value of this object is meaningful if and only if the value
 | 
						|
                of the relevant mgreceptacleType object is related to a two-level
 | 
						|
                receptacle class. Otherwise the default value is 0."
 | 
						|
        ::= { upsmgReceptaclesEntry 7 }
 | 
						|
 | 
						|
mgreceptacleOverload OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The overload status of the receptacle.
 | 
						|
 | 
						|
                The value of this object is meaningful if and only if the value
 | 
						|
                of the relevant mgreceptacleType object is related to a two-level
 | 
						|
                receptacle class. Otherwise the default value is 0."
 | 
						|
        ::= { upsmgReceptaclesEntry 8 }
 | 
						|
 | 
						|
mgreceptacleAutonomy OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle autonomy.
 | 
						|
 | 
						|
                The value of this object is meaningful if and only if the value
 | 
						|
                of the relevant mgreceptacleType object is related to a two-level
 | 
						|
                receptacle class. Otherwise the default value is 0."
 | 
						|
        ::= { upsmgReceptaclesEntry 9 }
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgConfig group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
-- This group gives objects for describing:
 | 
						|
--  Battery characteristics and administrative status,
 | 
						|
--  Configuration set points for normal shutoff and restart,
 | 
						|
--  Nominal voltage and Input low/high transfer point,
 | 
						|
--  Output and By Pass characteristics,
 | 
						|
--  Devices table (powered systems),
 | 
						|
--  Receptacles default table.
 | 
						|
--  Environ external alarms UserID table.
 | 
						|
 | 
						|
--  Battery characteristics and administrative status.
 | 
						|
 | 
						|
upsmgConfigBatteryInstalled OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The battery installed status."
 | 
						|
        ::= { upsmgConfig 1 }
 | 
						|
 | 
						|
upsmgConfigNominalBatteryVoltage OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The nominal battery voltage."
 | 
						|
        ::= { upsmgConfig 2 }
 | 
						|
 | 
						|
upsmgConfigNominalBatteryTime OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The full load battery autonomy time."
 | 
						|
        ::= { upsmgConfig 3 }
 | 
						|
 | 
						|
upsmgConfigNominalRechargeTime OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The recharge time to go from low battery cut off
 | 
						|
                to full charge at full load."
 | 
						|
        ::= { upsmgConfig 4 }
 | 
						|
 | 
						|
--  Configuration set points for normal shutoff and restart.
 | 
						|
 | 
						|
upsmgConfigMinRechargeLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The minimum battery level required to supply power on the
 | 
						|
                 loads after low battery condition turn off and restart on
 | 
						|
                 main return."
 | 
						|
        ::= { upsmgConfig 5 }
 | 
						|
 | 
						|
upsmgConfigMaxRechargeTime OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The maximum time delay of battery recharge before supply
 | 
						|
                power to the loads."
 | 
						|
        ::= { upsmgConfig 6 }
 | 
						|
 | 
						|
upsmgConfigLowBatteryTime OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set remaining time value for low battery condition."
 | 
						|
        ::= { upsmgConfig 7 }
 | 
						|
 | 
						|
upsmgConfigLowBatteryLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set battery level value for low battery condition."
 | 
						|
        ::= { upsmgConfig 8 }
 | 
						|
 | 
						|
upsmgConfigAutoRestart OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                always(1),
 | 
						|
                never(2),
 | 
						|
                onmain(3)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The automatic restart enabling status."
 | 
						|
        ::= { upsmgConfig 9 }
 | 
						|
 | 
						|
upsmgConfigShutdownTimer OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set ups shutdown timer from on battery condition."
 | 
						|
        ::= { upsmgConfig 10 }
 | 
						|
 | 
						|
upsmgConfigSysShutDuration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set ups shutdown delay (Sn delay)."
 | 
						|
        ::= { upsmgConfig 11 }
 | 
						|
 | 
						|
--  Nominal voltage and Input low/high transfer point.
 | 
						|
 | 
						|
upsmgConfigVARating OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS nominal VA rating."
 | 
						|
        ::= { upsmgConfig 12 }
 | 
						|
 | 
						|
upsmgConfigLowTransfer OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The low voltage transfer point."
 | 
						|
        ::= { upsmgConfig 13 }
 | 
						|
 | 
						|
upsmgConfigHighTransfer OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The high voltage transfer point."
 | 
						|
        ::= { upsmgConfig 14 }
 | 
						|
 | 
						|
--  Output and By Pass characteristics.
 | 
						|
 | 
						|
upsmgConfigOutputNominalVoltage OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The nominal output voltage."
 | 
						|
        ::= { upsmgConfig 15 }
 | 
						|
 | 
						|
upsmgConfigOutputNominalCurrent OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The nominal output current."
 | 
						|
        ::= { upsmgConfig 16 }
 | 
						|
 | 
						|
upsmgConfigOutputNomFrequency OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The nominal output frequency."
 | 
						|
        ::= { upsmgConfig 17 }
 | 
						|
 | 
						|
upsmgConfigByPassType OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                none(1),
 | 
						|
                relay(2),
 | 
						|
                static(3)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS by pass switch type."
 | 
						|
        ::= { upsmgConfig 18 }
 | 
						|
 | 
						|
upsmgConfigAlarmAudible OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set audible alarm status."
 | 
						|
        ::= { upsmgConfig 19 }
 | 
						|
 | 
						|
upsmgConfigAlarmTimeDelay OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set audible alarm time delay."
 | 
						|
        ::= { upsmgConfig 20 }
 | 
						|
 | 
						|
--  Devices table (powered systems).
 | 
						|
 | 
						|
upsmgConfigDevicesNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The number of devices that are powered by the UPS."
 | 
						|
        ::= { upsmgConfig 21 }
 | 
						|
 | 
						|
upsmgConfigDevicesTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgConfigDevicesEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of devices that are powered by the UPS."
 | 
						|
        ::= { upsmgConfig 22 }
 | 
						|
 | 
						|
upsmgConfigDevicesEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgConfigDevicesEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of a device entry in the devices table."
 | 
						|
        INDEX   { mgdeviceIndex }
 | 
						|
        ::= { upsmgConfigDevicesTable 1 }
 | 
						|
 | 
						|
UpsmgConfigDevicesEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgdeviceIndex INTEGER,
 | 
						|
        mgdeviceReceptacleNum INTEGER,
 | 
						|
        mgdeviceIdent DisplayString,
 | 
						|
        mgdeviceVaRating INTEGER,
 | 
						|
        mgdeviceSequenceOff INTEGER,
 | 
						|
        mgdeviceSequenceOn INTEGER,
 | 
						|
        mgdeviceShutdownDuration INTEGER,
 | 
						|
        mgdeviceBootUpDuration INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgdeviceIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A unique value for each device. Its value ranges between 1
 | 
						|
                and the value of upsmgDevicesNum."
 | 
						|
        ::= { upsmgConfigDevicesEntry 1 }
 | 
						|
 | 
						|
mgdeviceReceptacleNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle number of the device plugged into the UPS.
 | 
						|
                This value gives index entry in the ReceptaclesTable object
 | 
						|
                of the Receptacle group. A value of 0 invalidates the entry
 | 
						|
                in the DevicesTable."
 | 
						|
        ::= { upsmgConfigDevicesEntry 2 }
 | 
						|
 | 
						|
mgdeviceIdent OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A textual string for device user identification."
 | 
						|
        ::= { upsmgConfigDevicesEntry 3 }
 | 
						|
 | 
						|
mgdeviceVaRating OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The volt-ampere rating of the device plugged into the UPS."
 | 
						|
        ::= { upsmgConfigDevicesEntry 4 }
 | 
						|
 | 
						|
mgdeviceSequenceOff OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set the device position in the remote shutdown sequence."
 | 
						|
        ::= { upsmgConfigDevicesEntry 5 }
 | 
						|
 | 
						|
mgdeviceSequenceOn OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set the device position in the remote reboot sequence."
 | 
						|
        ::= { upsmgConfigDevicesEntry 6 }
 | 
						|
 | 
						|
mgdeviceShutdownDuration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set the duration from start of computer shut-down
 | 
						|
                to complete."
 | 
						|
        ::= { upsmgConfigDevicesEntry 7 }
 | 
						|
 | 
						|
mgdeviceBootUpDuration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set the duration from start of computer boot-up
 | 
						|
                to complete."
 | 
						|
        ::= { upsmgConfigDevicesEntry 8 }
 | 
						|
 | 
						|
--  Receptacles default table.
 | 
						|
 | 
						|
-- This table gives for every receptacle the power return condition for
 | 
						|
-- each failure cause.
 | 
						|
 | 
						|
upsmgConfigReceptaclesTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgConfigReceptaclesEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of receptacles."
 | 
						|
        ::= { upsmgConfig 23 }
 | 
						|
 | 
						|
upsmgConfigReceptaclesEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgConfigReceptaclesEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of a receptacle entry in the table."
 | 
						|
        INDEX   { mgreceptacleIndexb }
 | 
						|
        ::= { upsmgConfigReceptaclesTable 1 }
 | 
						|
 | 
						|
UpsmgConfigReceptaclesEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgreceptacleIndexb INTEGER,
 | 
						|
        mgreceptacleStateTurnOn INTEGER,
 | 
						|
        mgreceptacleStateMainReturn INTEGER,
 | 
						|
        mgreceptacleStateDischarge INTEGER,
 | 
						|
        mgreceptacleShutoffLevel INTEGER,
 | 
						|
        mgreceptacleShutoffTimer INTEGER,
 | 
						|
        mgreceptacleRestartLevel INTEGER,
 | 
						|
        mgreceptacleRestartDelay INTEGER,
 | 
						|
        mgreceptacleShutdownDuration INTEGER,
 | 
						|
        mgreceptacleBootUpDuration INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgreceptacleIndexb OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A unique value for each receptacle. Its value ranges between 1
 | 
						|
                and the value of upsmgReceptaclesNum."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 1 }
 | 
						|
 | 
						|
mgreceptacleStateTurnOn OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                on(1),
 | 
						|
                off(2),
 | 
						|
                last(3),
 | 
						|
                schedule(4)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Default return state at turn on."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 2 }
 | 
						|
 | 
						|
mgreceptacleStateMainReturn OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                on(1),
 | 
						|
                off(2),
 | 
						|
                last(3),
 | 
						|
                schedule(4)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Default return state on main return."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 3 }
 | 
						|
 | 
						|
mgreceptacleStateDischarge OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                on(1),
 | 
						|
                off(2),
 | 
						|
                last(3),
 | 
						|
                schedule(4)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Default return state on main return from battery discharge."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 4 }
 | 
						|
 | 
						|
mgreceptacleShutoffLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Battery level for starting shutoff sequence."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 5 }
 | 
						|
 | 
						|
mgreceptacleShutoffTimer OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Time delay from on battery for starting shutoff sequence."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 6 }
 | 
						|
 | 
						|
mgreceptacleRestartLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Battery level for starting restart sequence."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 7 }
 | 
						|
 | 
						|
mgreceptacleRestartDelay OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Time delay for starting restart sequence."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 8 }
 | 
						|
 | 
						|
mgreceptacleShutdownDuration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Maximum Shutdown Duration for systems powered by this plug."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 9 }
 | 
						|
 | 
						|
mgreceptacleBootUpDuration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Maximum Reboot Duration for systems powered by this plug."
 | 
						|
        ::= { upsmgConfigReceptaclesEntry 10 }
 | 
						|
 | 
						|
--  Environ external alarms UserID table.
 | 
						|
 | 
						|
upsmgConfigExtAlarmNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The number of environ external alarm, value is
 | 
						|
                  between 8 and 32.."
 | 
						|
        ::= { upsmgConfig 24 }
 | 
						|
 | 
						|
upsmgConfigExtAlarmTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgConfigExtAlarmEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of environmental external alarms."
 | 
						|
        ::= { upsmgConfig 25 }
 | 
						|
 | 
						|
upsmgConfigExtAlarmEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgConfigExtAlarmEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of an external alarm in the table."
 | 
						|
        INDEX   { mgextAlarmIndex }
 | 
						|
        ::= { upsmgConfigExtAlarmTable 1 }
 | 
						|
 | 
						|
UpsmgConfigExtAlarmEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgextAlarmIndex INTEGER,
 | 
						|
        mgextAlarmUID DisplayString
 | 
						|
}
 | 
						|
 | 
						|
mgextAlarmIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A unique value for each external alarm. Its value ranges
 | 
						|
                between 1 and the value of upsmgConfigExtAlarmNum."
 | 
						|
        ::= { upsmgConfigExtAlarmEntry 1 }
 | 
						|
 | 
						|
mgextAlarmUID OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A textual string for alarm state user identification."
 | 
						|
        ::= { upsmgConfigExtAlarmEntry 2 }
 | 
						|
 | 
						|
upsmgConfigEmergencyTestFail OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The emergency condition status on Battery test fail."
 | 
						|
        ::= { upsmgConfig 26 }
 | 
						|
 | 
						|
upsmgConfigEmergencyOnByPass OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The emergency condition status on By Pass."
 | 
						|
        ::= { upsmgConfig 27 }
 | 
						|
 | 
						|
upsmgConfigEmergencyOverload OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The emergency condition status on overload."
 | 
						|
        ::= { upsmgConfig 28 }
 | 
						|
 | 
						|
--  Schedule on/off daily time table.
 | 
						|
 | 
						|
upsmgConfigControlDayTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgConfigControlDayEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of daily on/off time."
 | 
						|
        ::= { upsmgConfig 29 }
 | 
						|
 | 
						|
upsmgConfigControlDayEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgConfigControlDayEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of a daily on/off time schedule in the table."
 | 
						|
        INDEX   { mgcontrolDayIndex }
 | 
						|
        ::= { upsmgConfigControlDayTable 1 }
 | 
						|
 | 
						|
UpsmgConfigControlDayEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgcontrolDayIndex INTEGER,
 | 
						|
        mgcontrolDayOn INTEGER,
 | 
						|
        mgcontrolDayOff INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgcontrolDayIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The day index. It is a number between 1 and 7, 1 for
 | 
						|
                Sunday, 2 for Monday, ..."
 | 
						|
        ::= { upsmgConfigControlDayEntry 1 }
 | 
						|
 | 
						|
mgcontrolDayOn OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set daily power on time. Any value greater than 86400
 | 
						|
                is to disable the Day On."
 | 
						|
        ::= { upsmgConfigControlDayEntry 2 }
 | 
						|
 | 
						|
mgcontrolDayOff OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set daily power off time. Any value greater than 86400
 | 
						|
                is to disable the Day Off."
 | 
						|
        ::= { upsmgConfigControlDayEntry 3 }
 | 
						|
 | 
						|
upsmgConfigLowBooster OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set UPS booster low threshold."
 | 
						|
        ::= { upsmgConfig 30 }
 | 
						|
 | 
						|
upsmgConfigHighBooster OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set UPS booster high threshold."
 | 
						|
        ::= { upsmgConfig 31 }
 | 
						|
 | 
						|
upsmgConfigLowFader OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set UPS fader low threshold."
 | 
						|
        ::= { upsmgConfig 32 }
 | 
						|
 | 
						|
upsmgConfigHighFader OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To set UPS fader high threshold."
 | 
						|
        ::= { upsmgConfig 33 }
 | 
						|
 | 
						|
 | 
						|
-- AB Release on 2003/10/23 : Add Configuration of the environment sensor.
 | 
						|
 | 
						|
upsmgConfigEnvironmentTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgConfigEnvironmentEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table containing the configuration of the environment sensor."
 | 
						|
        ::= { upsmgConfig 34 }
 | 
						|
 | 
						|
upsmgConfigEnvironmentEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgConfigEnvironmentEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of an entry in the table."
 | 
						|
        INDEX   { upsmgConfigSensorIndex }
 | 
						|
        ::= { upsmgConfigEnvironmentTable 1 }
 | 
						|
 | 
						|
UpsmgConfigEnvironmentEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
		upsmgConfigSensorIndex INTEGER,
 | 
						|
        upsmgConfigSensorName DisplayString,
 | 
						|
		upsmgConfigTemperatureLow INTEGER,
 | 
						|
        upsmgConfigTemperatureHigh INTEGER,
 | 
						|
        upsmgConfigTemperatureHysteresis INTEGER,
 | 
						|
		upsmgConfigHumidityLow INTEGER,
 | 
						|
        upsmgConfigHumidityHigh INTEGER,
 | 
						|
        upsmgConfigHumidityHysteresis INTEGER,
 | 
						|
        upsmgConfigInput1Name DisplayString,
 | 
						|
        upsmgConfigInput1ClosedLabel DisplayString,
 | 
						|
        upsmgConfigInput1OpenLabel DisplayString,
 | 
						|
        upsmgConfigInput2Name DisplayString,
 | 
						|
        upsmgConfigInput2ClosedLabel DisplayString,
 | 
						|
        upsmgConfigInput2OpenLabel DisplayString 
 | 
						|
}
 | 
						|
 | 
						|
upsmgConfigSensorIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (0..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The sensor index, ranging from 1 to upsmgEnvironmentNum."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 1 }
 | 
						|
 | 
						|
upsmgConfigSensorName OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..42))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The sensor user-friendly name."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 2 }
 | 
						|
 | 
						|
upsmgConfigTemperatureLow OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The low temperature threshold in unit 0.1 Cel."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 3 }
 | 
						|
 | 
						|
upsmgConfigTemperatureHigh OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The high temperature threshold in unit 0.1 Cel."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 4 }
 | 
						|
 | 
						|
upsmgConfigTemperatureHysteresis OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The temperature hysteresys used for threshold test in unit 0.1 Cel."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 5 }
 | 
						|
 | 
						|
upsmgConfigHumidityLow OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The low humidity threshold in unit 1 %."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 6 }
 | 
						|
 | 
						|
upsmgConfigHumidityHigh OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The high humidity threshold in unit 1 %."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 7 }
 | 
						|
 | 
						|
upsmgConfigHumidityHysteresis OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The humidity hysteresys used for threshold test in unit 1 %."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 8 }
 | 
						|
 | 
						|
upsmgConfigInput1Name OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..22))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The Input #1 user-friendly name."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 9 }
 | 
						|
 | 
						|
upsmgConfigInput1ClosedLabel OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..18))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The Input #1 label for closed position."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 10 }
 | 
						|
 | 
						|
upsmgConfigInput1OpenLabel OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..18))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The Input #1 label for open position."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 11 }
 | 
						|
 | 
						|
upsmgConfigInput2Name OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..22))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The Input #2 user-friendly name."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 12 }
 | 
						|
 | 
						|
upsmgConfigInput2ClosedLabel OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..18))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The Input #2 label for closed position."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 13 }
 | 
						|
 | 
						|
upsmgConfigInput2OpenLabel OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..18))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The Input #2 label for open position."
 | 
						|
        ::= { upsmgConfigEnvironmentEntry 14 }
 | 
						|
 | 
						|
 | 
						|
-- UPS Monitoring groups of the MIB:
 | 
						|
-- upsmgBattery(5), upsmgInput(6), upsmgOutput(7), upsmgEnviron(8)
 | 
						|
 | 
						|
----------------------------
 | 
						|
-- the upsmgBattery group --
 | 
						|
----------------------------
 | 
						|
 | 
						|
upsmgBatteryRemainingTime OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The time remaining actual charge vs actual load (dynamic)."
 | 
						|
        ::= { upsmgBattery 1 }
 | 
						|
 | 
						|
upsmgBatteryLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The battery level as a percentage of charge."
 | 
						|
        ::= { upsmgBattery 2 }
 | 
						|
 | 
						|
upsmgBatteryRechargeTime OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The actual operational battery recharge time to set point
 | 
						|
                equal to upsmgConfigRechargeLevel. This value is computed from
 | 
						|
                upsmgConfigRechargeLevel (level to reach), upsmgBatteryLevel (the
 | 
						|
                actual reached level) and the UPS charge rate."
 | 
						|
        ::= { upsmgBattery 3 }
 | 
						|
 | 
						|
upsmgBatteryRechargeLevel OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The actual value of the battery recharge level that will be
 | 
						|
                reached during the time delay necessary to restart after power
 | 
						|
                returns. This value is computed from upsmgConfigRechargeTime
 | 
						|
                (the delay), upsmgBatteryLevel (the actual level) and the UPS
 | 
						|
                charge rate."
 | 
						|
        ::= { upsmgBattery 4 }
 | 
						|
 | 
						|
upsmgBatteryVoltage OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The actual battery voltage."
 | 
						|
        ::= { upsmgBattery 5 }
 | 
						|
 | 
						|
upsmgBatteryCurrent OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The actual battery current."
 | 
						|
        ::= { upsmgBattery 6 }
 | 
						|
 | 
						|
upsmgBatteryTemperature OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The battery temperature."
 | 
						|
        ::= { upsmgBattery 7 }
 | 
						|
 | 
						|
upsmgBatteryFullRechargeTime OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The battery full recharge time (from 0 to 100 percent)
 | 
						|
                at current load."
 | 
						|
        ::= { upsmgBattery 8 }
 | 
						|
 | 
						|
upsmgBatteryFaultBattery OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The battery fault status."
 | 
						|
        ::= { upsmgBattery 9 }
 | 
						|
 | 
						|
upsmgBatteryNoBattery OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS has no Battery status."
 | 
						|
        ::= { upsmgBattery 10 }
 | 
						|
 | 
						|
upsmgBatteryReplacement OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS Battery to be replaced status."
 | 
						|
        ::= { upsmgBattery 11 }
 | 
						|
 | 
						|
upsmgBatteryUnavailableBattery OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS Battery is unavailable status."
 | 
						|
        ::= { upsmgBattery 12 }
 | 
						|
 | 
						|
upsmgBatteryNotHighCharge OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS Battery quit high condition status."
 | 
						|
        ::= { upsmgBattery 13 }
 | 
						|
 | 
						|
upsmgBatteryLowBattery OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The battery low status."
 | 
						|
        ::= { upsmgBattery 14 }
 | 
						|
 | 
						|
upsmgBatteryChargerFault OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS Battery is not charging status."
 | 
						|
        ::= { upsmgBattery 15 }
 | 
						|
 | 
						|
upsmgBatteryLowCondition OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS is at low condition status."
 | 
						|
        ::= { upsmgBattery 16 }
 | 
						|
 | 
						|
upsmgBatteryLowRecharge OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS Battery is not recharged status."
 | 
						|
        ::= { upsmgBattery 17 }
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgInput group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
upsmgInputPhaseNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The number of input phases."
 | 
						|
        ::= { upsmgInput 1 }
 | 
						|
 | 
						|
upsmgInputPhaseTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgInputPhaseEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of input phases."
 | 
						|
        ::= { upsmgInput 2 }
 | 
						|
 | 
						|
upsmgInputPhaseEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgInputPhaseEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of an input phase."
 | 
						|
        INDEX   { mginputIndex }
 | 
						|
        ::= { upsmgInputPhaseTable 1 }
 | 
						|
 | 
						|
UpsmgInputPhaseEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mginputIndex INTEGER,
 | 
						|
        mginputVoltage INTEGER,
 | 
						|
        mginputFrequency INTEGER,
 | 
						|
        mginputMinimumVoltage INTEGER,
 | 
						|
        mginputMaximumVoltage INTEGER,
 | 
						|
        mginputCurrent INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mginputIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The input phase voltage index. It is a number between 1
 | 
						|
                and upsmgInputPhaseNum."
 | 
						|
        ::= { upsmgInputPhaseEntry 1 }
 | 
						|
 | 
						|
mginputVoltage OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The input phase voltage."
 | 
						|
        ::= { upsmgInputPhaseEntry 2 }
 | 
						|
 | 
						|
mginputFrequency OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The input phase frequency."
 | 
						|
        ::= { upsmgInputPhaseEntry 3 }
 | 
						|
 | 
						|
mginputMinimumVoltage OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The input phase minimum voltage over the last minute."
 | 
						|
        ::= { upsmgInputPhaseEntry 4 }
 | 
						|
 | 
						|
mginputMaximumVoltage OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The input phase maximum voltage over the last minute."
 | 
						|
        ::= { upsmgInputPhaseEntry 5 }
 | 
						|
 | 
						|
mginputCurrent OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The input phase current."
 | 
						|
        ::= { upsmgInputPhaseEntry 6 }
 | 
						|
 | 
						|
upsmgInputBadStatus OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The utility power bad voltage or bad frequency status."
 | 
						|
        ::= { upsmgInput 3 }
 | 
						|
 | 
						|
upsmgInputLineFailCause OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                no(1),
 | 
						|
                outoftolvolt(2),
 | 
						|
                outoftolfreq(3),
 | 
						|
                utilityoff(4)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The utility power failure cause:
 | 
						|
                no(1) is for no utility failure,
 | 
						|
                outoftolvolt(2) is for voltage out of tolerance,
 | 
						|
                outoftolfreq(3) is for frequency out of tolerance,
 | 
						|
                utilityoff(4) is for no voltage at all."
 | 
						|
        ::= { upsmgInput 4 }
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgOutput group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
upsmgOutputPhaseNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The number of output phases."
 | 
						|
        ::= { upsmgOutput 1 }
 | 
						|
 | 
						|
upsmgOutputPhaseTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgOutputPhaseEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of output phases."
 | 
						|
        ::= { upsmgOutput 2 }
 | 
						|
 | 
						|
upsmgOutputPhaseEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgOutputPhaseEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of an output phase."
 | 
						|
        INDEX   { mgoutputPhaseIndex }
 | 
						|
        ::= { upsmgOutputPhaseTable 1 }
 | 
						|
 | 
						|
UpsmgOutputPhaseEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgoutputPhaseIndex INTEGER,
 | 
						|
        mgoutputVoltage INTEGER,
 | 
						|
        mgoutputFrequency INTEGER,
 | 
						|
        mgoutputLoadPerPhase INTEGER,
 | 
						|
        mgoutputCurrent INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgoutputPhaseIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The output phase voltage index. It is a number between 1
 | 
						|
                and upsmgOutputPhaseNum."
 | 
						|
        ::= { upsmgOutputPhaseEntry 1 }
 | 
						|
 | 
						|
mgoutputVoltage OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The output phase voltage."
 | 
						|
        ::= { upsmgOutputPhaseEntry 2 }
 | 
						|
 | 
						|
mgoutputFrequency OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The output phase frequency."
 | 
						|
        ::= { upsmgOutputPhaseEntry 3 }
 | 
						|
 | 
						|
mgoutputLoadPerPhase OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The output load per phase."
 | 
						|
        ::= { upsmgOutputPhaseEntry 4 }
 | 
						|
 | 
						|
mgoutputCurrent OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The output phase current."
 | 
						|
        ::= { upsmgOutputPhaseEntry 5 }
 | 
						|
 | 
						|
upsmgOutputOnBattery OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS on battery / on main status."
 | 
						|
        ::= { upsmgOutput 3 }
 | 
						|
 | 
						|
upsmgOutputOnByPass OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS on bypass status."
 | 
						|
        ::= { upsmgOutput 4 }
 | 
						|
 | 
						|
upsmgOutputUnavailableByPass OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The by pass unavailable status."
 | 
						|
        ::= { upsmgOutput 5 }
 | 
						|
 | 
						|
upsmgOutputNoByPass OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS bypass installed status."
 | 
						|
        ::= { upsmgOutput 6 }
 | 
						|
 | 
						|
upsmgOutputUtilityOff OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS utility off status."
 | 
						|
        ::= { upsmgOutput 7 }
 | 
						|
 | 
						|
upsmgOutputOnBoost OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS on booster status."
 | 
						|
        ::= { upsmgOutput 8 }
 | 
						|
 | 
						|
upsmgOutputInverterOff OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS Inverter on / off status."
 | 
						|
        ::= { upsmgOutput 9 }
 | 
						|
 | 
						|
upsmgOutputOverLoad OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The output over load status."
 | 
						|
        ::= { upsmgOutput 10 }
 | 
						|
 | 
						|
upsmgOutputOverTemp OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The ups over temperature status."
 | 
						|
        ::= { upsmgOutput 11 }
 | 
						|
 | 
						|
upsmgOutputOnBuck OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The UPS on fader status."
 | 
						|
        ::= { upsmgOutput 12 }
 | 
						|
 | 
						|
----------------------------
 | 
						|
-- the upsmgEnviron group --
 | 
						|
----------------------------
 | 
						|
 | 
						|
upsmgEnvironAmbientTemp OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The ambient temperature."
 | 
						|
        ::= { upsmgEnviron 1 }
 | 
						|
 | 
						|
upsmgEnvironAmbientHumidity OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The ambient humidity."
 | 
						|
        ::= { upsmgEnviron 2 }
 | 
						|
 | 
						|
upsmgEnvironExtAlarmTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgEnvironExtAlarmEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of external alarms."
 | 
						|
        ::= { upsmgEnviron 3 }
 | 
						|
 | 
						|
upsmgEnvironExtAlarmEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgEnvironExtAlarmEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of an external alarm."
 | 
						|
        INDEX   { mgalarmNum }
 | 
						|
        ::= { upsmgEnvironExtAlarmTable 1 }
 | 
						|
 | 
						|
UpsmgEnvironExtAlarmEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgalarmNum INTEGER,
 | 
						|
        mgalarmState INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgalarmNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The external alarm number. A number between 1 and
 | 
						|
                upsmgConfigExtAlarmNum."
 | 
						|
        ::= { upsmgEnvironExtAlarmEntry 1 }
 | 
						|
 | 
						|
mgalarmState OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                active(1),
 | 
						|
                inactive(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The external alarm state (active or inactive)."
 | 
						|
        ::= { upsmgEnvironExtAlarmEntry 2 }
 | 
						|
 | 
						|
upsmgEnvironSensorNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The sensor unit number (0 to 4)."
 | 
						|
        ::= { upsmgEnviron 4 }
 | 
						|
 | 
						|
upsmgEnvironSensorTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgEnvironSensorEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of sensor units."
 | 
						|
        ::= { upsmgEnviron 5 }
 | 
						|
 | 
						|
upsmgEnvironSensorEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgEnvironSensorEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of a sensor unit."
 | 
						|
        INDEX   { mgsensorNum }
 | 
						|
        ::= { upsmgEnvironSensorTable 1 }
 | 
						|
 | 
						|
UpsmgEnvironSensorEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgsensorNum INTEGER,
 | 
						|
        mgsensorTemp INTEGER,
 | 
						|
        mgsensorHumidity INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgsensorNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The unit number. A number between 1 and 4."
 | 
						|
        ::= { upsmgEnvironSensorEntry 1 }
 | 
						|
 | 
						|
mgsensorTemp OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The measured temperature of the unit."
 | 
						|
        ::= { upsmgEnvironSensorEntry 2 }
 | 
						|
 | 
						|
mgsensorHumidity OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The measured humidity of the unit."
 | 
						|
        ::= { upsmgEnvironSensorEntry 3 }
 | 
						|
 | 
						|
-- AB Release on 2003/10/23 : Add Measurements of the environment sensor.
 | 
						|
 | 
						|
upsmgEnvironmentNum OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Number of Environment sensor connected."
 | 
						|
        ::= { upsmgEnviron 6 }
 | 
						|
 | 
						|
upsmgEnvironmentSensorTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgEnvironmentSensorEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table containing the measurements and alarms made by Environment sensor units."
 | 
						|
        ::= { upsmgEnviron 7 }
 | 
						|
 | 
						|
upsmgEnvironmentSensorEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgEnvironmentSensorEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of an entry in the measurement table."
 | 
						|
        INDEX   { upsmgEnvironmentIndex }
 | 
						|
        ::= { upsmgEnvironmentSensorTable 1 }
 | 
						|
 | 
						|
UpsmgEnvironmentSensorEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
		upsmgEnvironmentIndex INTEGER,
 | 
						|
        upsmgEnvironmentComFailure INTEGER,
 | 
						|
		upsmgEnvironmentTemperature INTEGER,
 | 
						|
		upsmgEnvironmentTemperatureLow INTEGER,
 | 
						|
		upsmgEnvironmentTemperatureHigh INTEGER,
 | 
						|
		upsmgEnvironmentHumidity INTEGER,
 | 
						|
		upsmgEnvironmentHumidityLow INTEGER,
 | 
						|
		upsmgEnvironmentHumidityHigh INTEGER,
 | 
						|
		upsmgEnvironmentInput1State INTEGER,
 | 
						|
		upsmgEnvironmentInput2State INTEGER
 | 
						|
}
 | 
						|
 | 
						|
upsmgEnvironmentIndex OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The sensor index, ranging from 1 to upsmgEnvironmentNum."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 1 }
 | 
						|
 | 
						|
upsmgEnvironmentComFailure OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The sensor communication failure : yes(1), no(2)."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 2 }
 | 
						|
 | 
						|
upsmgEnvironmentTemperature OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The temperature measurement in unit 0.1 Cel."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 3 }
 | 
						|
 | 
						|
upsmgEnvironmentTemperatureLow OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Temperature is below low theshold : yes(1), no(2)."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 4 }
 | 
						|
 | 
						|
upsmgEnvironmentTemperatureHigh OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Temperature is above high threshold : yes(1), no(2)."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 5 }
 | 
						|
 | 
						|
upsmgEnvironmentHumidity OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The humidity measurement in unit 0.1 %."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 6 }
 | 
						|
 | 
						|
upsmgEnvironmentHumidityLow OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Humidity is below low threshold : yes(1), no(2)."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 7 }
 | 
						|
 | 
						|
upsmgEnvironmentHumidityHigh OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Humidity is above high threshold : yes(1), no(2)."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 8 }
 | 
						|
 | 
						|
upsmgEnvironmentInput1State OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                closed(1),
 | 
						|
                open(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "State of Input#1 : closed(1), open(2)."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 9 }
 | 
						|
 | 
						|
upsmgEnvironmentInput2State OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                closed(1),
 | 
						|
                open(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "State of Input#2 : closed(1), open(2)."
 | 
						|
        ::= { upsmgEnvironmentSensorEntry 10 }
 | 
						|
 | 
						|
 | 
						|
-- UPS Controlling groups of the MIB:
 | 
						|
-- upsmgControl(9), upsmgTest(10), upsmgTraps(11)
 | 
						|
 | 
						|
----------------------------
 | 
						|
-- the upsmgControl group --
 | 
						|
----------------------------
 | 
						|
 | 
						|
--  Receptacles control table.
 | 
						|
 | 
						|
-- This table gives for every receptacle the ON/OFF control objects.
 | 
						|
 | 
						|
upsmgControlReceptaclesTable OBJECT-TYPE
 | 
						|
        SYNTAX SEQUENCE OF UpsmgControlReceptaclesEntry
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The table of receptacles."
 | 
						|
        ::= { upsmgControl 1 }
 | 
						|
 | 
						|
upsmgControlReceptaclesEntry OBJECT-TYPE
 | 
						|
        SYNTAX UpsmgControlReceptaclesEntry 
 | 
						|
        ACCESS not-accessible
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The description of a receptacle entry in the table."
 | 
						|
        INDEX   { mgreceptacleIndexc }
 | 
						|
        ::= { upsmgControlReceptaclesTable 1 }
 | 
						|
 | 
						|
UpsmgControlReceptaclesEntry ::= SEQUENCE { -- ASN.1 type definition
 | 
						|
        mgreceptacleIndexc INTEGER,
 | 
						|
        mgreceptacleOnDelay INTEGER,
 | 
						|
        mgreceptacleOnCtrl INTEGER,
 | 
						|
        mgreceptacleOnStatus INTEGER,
 | 
						|
        mgreceptacleOffDelay INTEGER,
 | 
						|
        mgreceptacleOffCtrl INTEGER,
 | 
						|
        mgreceptacleOffStatus INTEGER,
 | 
						|
        mgreceptacleToggleDelay INTEGER,
 | 
						|
        mgreceptacleToggleCtrl INTEGER,
 | 
						|
        mgreceptacleToggleStatus INTEGER,
 | 
						|
        mgreceptacleToggleDuration INTEGER
 | 
						|
}
 | 
						|
 | 
						|
mgreceptacleIndexc OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER (1..50)
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "A unique value for each receptacle. Its value ranges between 1
 | 
						|
                and the value of upsmgReceptaclesNum."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 1 }
 | 
						|
 | 
						|
mgreceptacleOnDelay OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Turn on UPS receptacle w/delay=?."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 2 }
 | 
						|
 | 
						|
mgreceptacleOnCtrl OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                nothing(1),
 | 
						|
                start(2),
 | 
						|
                stop(3)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle control on action."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 3 }
 | 
						|
 | 
						|
mgreceptacleOnStatus OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                none(1),
 | 
						|
                started(2),
 | 
						|
                inprogressinups(3),
 | 
						|
                completed(4)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle control on status."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 4 }
 | 
						|
 | 
						|
mgreceptacleOffDelay OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Turn off UPS receptacle w/delay=?."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 5 }
 | 
						|
 | 
						|
mgreceptacleOffCtrl OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                nothing(1),
 | 
						|
                start(2),
 | 
						|
                stop(3)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle control off action."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 6 }
 | 
						|
 | 
						|
mgreceptacleOffStatus OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                none(1),
 | 
						|
                started(2),
 | 
						|
                inprogressinups(3),
 | 
						|
                completed(4)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle control off status."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 7 }
 | 
						|
 | 
						|
mgreceptacleToggleDelay OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Turn off then on UPS receptacle w/delay=?."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 8 }
 | 
						|
 | 
						|
mgreceptacleToggleCtrl OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                nothing(1),
 | 
						|
                start(2),
 | 
						|
                stop(3)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle control toggle action."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 9 }
 | 
						|
 | 
						|
mgreceptacleToggleStatus OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                none(1),
 | 
						|
                started(2),
 | 
						|
                inprogressinups(3),
 | 
						|
                completed(4)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The receptacle control toggle status."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 10 }
 | 
						|
 | 
						|
mgreceptacleToggleDuration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "Turn off then on UPS receptacle w/duration=?."
 | 
						|
        ::= { upsmgControlReceptaclesEntry 11 }
 | 
						|
 | 
						|
upsmgControlDayOff OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                sunday(1), monday(2), tuesday(3), wednesday(4),
 | 
						|
                thursday(5), friday(6), saterday(7), none(8)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The schedule off control object. Default value is none(8).
 | 
						|
                Value 1 means to start scheduled off on Sunday,
 | 
						|
                value 2 to start scheduled off on Monday, and so on."
 | 
						|
        ::= { upsmgControl 2 }
 | 
						|
 | 
						|
upsmgControlDayOn OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                sunday(1), monday(2), tuesday(3), wednesday(4),
 | 
						|
                thursday(5), friday(6), saterday(7), none(8)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The schedule on control object. Default value is none(8).
 | 
						|
                Value 1 means to start scheduled on on Sunday,
 | 
						|
                value 2 to start scheduled on on Monday, and so on.
 | 
						|
                This object is meaningfull only for those agent that do not
 | 
						|
                include internal clock. In such a case the object is set by
 | 
						|
                a manager to start the schedule on sequence."
 | 
						|
        ::= { upsmgControl 3 }
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgTest group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
upsmgTestBatterySchedule OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                unknown(1),
 | 
						|
                weekly(2),
 | 
						|
                monthly(3),
 | 
						|
                atturnon(4),
 | 
						|
                none(5),
 | 
						|
                dayly(6)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The automatic battery test schedule."
 | 
						|
        ::= { upsmgTest 1 }
 | 
						|
 | 
						|
upsmgTestDiagnostics OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                default(1),
 | 
						|
                start(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To run self test diagnostics."
 | 
						|
        ::= { upsmgTest 2 }
 | 
						|
 | 
						|
upsmgTestDiagResult OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                success(1),
 | 
						|
                failed(2),
 | 
						|
                none(3)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The automatic test diagnostic result."
 | 
						|
        ::= { upsmgTest 3 }
 | 
						|
 | 
						|
upsmgTestBatteryCalibration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                default(1),
 | 
						|
                start(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To run battery test calibration."
 | 
						|
        ::= { upsmgTest 4 }
 | 
						|
 | 
						|
upsmgTestLastCalibration OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The last battery calibration test date."
 | 
						|
        ::= { upsmgTest 5 }
 | 
						|
 | 
						|
upsmgTestIndicators OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To run UPS indicators test."
 | 
						|
        ::= { upsmgTest 6 }
 | 
						|
 | 
						|
upsmgTestCommandLine OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To send ASCII command line to UPS."
 | 
						|
        ::= { upsmgTest 7 }
 | 
						|
 | 
						|
upsmgTestCommandReady OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To advise UPS that command line has been prepared."
 | 
						|
        ::= { upsmgTest 8 }
 | 
						|
 | 
						|
upsmgTestResponseLine OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To get ASCII protocol response from UPS."
 | 
						|
        ::= { upsmgTest 9 }
 | 
						|
 | 
						|
upsmgTestResponseReady OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "To advise agent that response line has been received."
 | 
						|
        ::= { upsmgTest 10 }
 | 
						|
 | 
						|
upsmgTestBatteryResult OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                msuccess(1),
 | 
						|
                mfailed(2),
 | 
						|
                ssuccess(3),
 | 
						|
                sfailed(4),
 | 
						|
                none(5)
 | 
						|
        }
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "The test battery result:
 | 
						|
                msuccess(1) is for manual battery test success,
 | 
						|
                ssuccess(3) is for scheduled battery test success,
 | 
						|
                mfailed(2) is for manual battery test failed,
 | 
						|
                sfailed(4) is for scheduled battery test failed."
 | 
						|
        ::= { upsmgTest 11 }
 | 
						|
 | 
						|
--------------------------
 | 
						|
-- the upsmgTraps group --
 | 
						|
--------------------------
 | 
						|
 | 
						|
-- This group defines objects and traps, so that for each trap, simple
 | 
						|
-- get request on related objects (one or many) allow to confirm actual
 | 
						|
-- status of the trap.
 | 
						|
 | 
						|
-- TRAPS NOTIFICATIONS
 | 
						|
 | 
						|
upsmgBatteryFault TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS Battery entering Fault status." 
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 1
 | 
						|
 | 
						|
upsmgBatteryOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS Battery returned to OK status."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 2
 | 
						|
 | 
						|
upsmgBatteryReplacementIndicated TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery need to be replaced."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 3
 | 
						|
 | 
						|
upsmgBatteryReplaceNotIndicated TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery does not need to be replaced."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 4
 | 
						|
 | 
						|
upsmgAtLowBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery reached low condition."
 | 
						|
       --#SEVERITY CRITICAL
 | 
						|
::= 5
 | 
						|
 | 
						|
upsmgFromLowBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery returned from low condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 6
 | 
						|
 | 
						|
upsmgChargerFault TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery charger is not active."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 7
 | 
						|
 | 
						|
upsmgChargerOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery charger is active."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 8
 | 
						|
 | 
						|
upsmgAtLowCondition TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS entering low condition."
 | 
						|
       --#SEVERITY CRITICAL
 | 
						|
::= 9
 | 
						|
 | 
						|
upsmgFromLowCondition TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS exiting low condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 10
 | 
						|
 | 
						|
upsmgOnBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS is on Battery." 
 | 
						|
       --#SEVERITY CRITICAL
 | 
						|
::= 11
 | 
						|
 | 
						|
upsmgReturnFromBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS returned from battery."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 12
 | 
						|
 | 
						|
upsmgOnByPass TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS is on by pass."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 13
 | 
						|
 | 
						|
upsmgReturnFromByPass TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS return from by pass."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 14
 | 
						|
 | 
						|
upsmgByPassUnavailable TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS by pass unavailable."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 15
 | 
						|
 | 
						|
upsmgByPassAvailable TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS by pass available."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 16
 | 
						|
 | 
						|
upsmgUtilityFailure TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS utility power failed."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 17
 | 
						|
 | 
						|
upsmgUtilityRestored TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS utility power restored."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 18
 | 
						|
 | 
						|
upsmgOnBoost TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS is on boost."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 19
 | 
						|
 | 
						|
upsmgReturnFromBoost TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS has returned from boost."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 20
 | 
						|
 | 
						|
upsmgOverLoad TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS has overload condition."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 21
 | 
						|
 | 
						|
upsmgLoadOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS quit overload condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 22
 | 
						|
 | 
						|
upsmgOverTemperature TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS has overtemperature condition."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 23
 | 
						|
 | 
						|
upsmgTemperatureOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS quit overtemperature condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 24
 | 
						|
 | 
						|
upsmgOnToStart TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleState, mgreceptacleOnDelay,
 | 
						|
                        mgreceptacleRestartDelay }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS on sequence started."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 25
 | 
						|
 | 
						|
upsmgOnAbort TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleOnDelay }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS on sequence cancelled."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 26
 | 
						|
 | 
						|
upsmgOnInProgress TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleState,
 | 
						|
                        mgreceptacleBootUpDuration }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS on sequence in progress in ups."
 | 
						|
       --#SEVERITY CRITICAL
 | 
						|
::= 27
 | 
						|
 | 
						|
upsmgOnComplete TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleOnDelay }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS on sequence completed."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 28
 | 
						|
 | 
						|
upsmgOffToStart TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleState, mgreceptacleOffDelay,
 | 
						|
                        mgreceptacleShutoffTimer, upsmgConfigSysShutDuration }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS off sequence started."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 29
 | 
						|
 | 
						|
upsmgOffAbort TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleOffDelay }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS off sequence cancelled."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 30
 | 
						|
 | 
						|
upsmgOffInProgress TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleState,
 | 
						|
                        mgreceptacleShutdownDuration }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS off sequence in progress in ups."
 | 
						|
       --#SEVERITY CRITICAL
 | 
						|
::= 31
 | 
						|
 | 
						|
upsmgOffComplete TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleOffDelay }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS off sequence completed."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 32
 | 
						|
 | 
						|
upsmgToggleToStart TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleToggleDelay }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS toggle (off/on) sequence started."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 33
 | 
						|
 | 
						|
upsmgToggleAbort TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleToggleDelay }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS toggle (off/on) sequence cancelled."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 34
 | 
						|
 | 
						|
upsmgToggleInProgress TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleToggleDuration }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS toggle (off/on) sequence in progress in ups."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 35
 | 
						|
 | 
						|
upsmgToggleComplete TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgreceptacleIndex, mgreceptacleToggleDuration }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS toggle (off/on) sequence completed."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 36
 | 
						|
 | 
						|
upsmgCommunicationFailure TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS serial communication failed."
 | 
						|
       --#SEVERITY CRITICAL
 | 
						|
::= 37
 | 
						|
 | 
						|
upsmgCommunicationRestored TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS serial communication restored."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 38
 | 
						|
 | 
						|
upsmgInputBad TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS input has bad condition."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 39
 | 
						|
 | 
						|
upsmgInputOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS input quit bad condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 40
 | 
						|
 | 
						|
upsmgBatteryUnavailable TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery is unavailable."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 41
 | 
						|
 | 
						|
upsmgBatteryAvailable TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS battery return from unavailable condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 42
 | 
						|
 | 
						|
upsmgAtLowRecharge TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS waiting for battery charging condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 43
 | 
						|
 | 
						|
upsmgFromLowRecharge TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { upsmgBatteryRemainingTime, upsmgBatteryLevel }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS reached battery charging condition."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 44
 | 
						|
 | 
						|
upsmgDiagnosticTestFail TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS self test failed."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 45
 | 
						|
 | 
						|
upsmgDiagnosticTestOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS self test succeeded."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 46
 | 
						|
 | 
						|
upsmgBatteryTestOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS passed battery test."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 47
 | 
						|
 | 
						|
upsmgBatteryTestFail TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS failed battery test."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 48
 | 
						|
 | 
						|
upsmgExternalAlarmActive TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgextAlarmIndex, mgextAlarmUID }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS enter environment external alarm."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 49
 | 
						|
 | 
						|
upsmgExternalAlarmInactive TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        VARIABLES { mgextAlarmIndex, mgextAlarmUID }
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS exit environment external alarm."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 50
 | 
						|
 | 
						|
upsmgOnBuck TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS is on buck."
 | 
						|
       --#SEVERITY MINOR
 | 
						|
::= 51
 | 
						|
 | 
						|
upsmgReturnFromBuck TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Trap UPS has returned from buck."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 52
 | 
						|
 | 
						|
-- AB Release on 2003/10/23 : Traps 53 to 64 added for the environment sensor.
 | 
						|
 | 
						|
upsmgEnvironComFailure TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Environment Probe communication failure."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 53
 | 
						|
 | 
						|
upsmgEnvironComOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Environment Probe communication restored."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 54
 | 
						|
 | 
						|
upsmgEnvironTemperatureLow TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Temperature is below low threshold."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 55
 | 
						|
 | 
						|
upsmgEnvironTemperatureHigh TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Temperature is above high threshold."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 56
 | 
						|
 | 
						|
upsmgEnvironTemperatureOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Temperature is in normal range."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 57
 | 
						|
 | 
						|
upsmgEnvironHumidityLow TRAP-TYPE
 | 
						|
       ENTERPRISE upsmgTraps
 | 
						|
       DESCRIPTION
 | 
						|
                "Humidity is below low threshold."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 58
 | 
						|
 | 
						|
upsmgEnvironHumidityHigh TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Humidity is above high threshold."
 | 
						|
       --#SEVERITY MAJOR
 | 
						|
::= 59
 | 
						|
 | 
						|
upsmgEnvironHumidityOK TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Humidity is in normal range."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 60
 | 
						|
 | 
						|
upsmgEnvironInput1Closed TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Input #1 is Closed."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 61
 | 
						|
 | 
						|
upsmgEnvironInput1Open TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Input #1 is Open."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 62
 | 
						|
 | 
						|
upsmgEnvironInput2Closed TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Input #2 is Closed."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 63
 | 
						|
 | 
						|
upsmgEnvironInput2Open TRAP-TYPE
 | 
						|
        ENTERPRISE upsmgTraps
 | 
						|
        DESCRIPTION
 | 
						|
                "Input #2 is Open."
 | 
						|
       --#SEVERITY INFORMATIONAL
 | 
						|
::= 64
 | 
						|
 | 
						|
 | 
						|
 | 
						|
----------------------
 | 
						|
-- upsmgAgent group --
 | 
						|
----------------------
 | 
						|
 | 
						|
--  following objects are configuration variables defined for
 | 
						|
--  UPS proxy agent that perform UPS management protocol
 | 
						|
--  and support SNMP management function
 | 
						|
 | 
						|
upsmgAgentIpaddress OBJECT-TYPE
 | 
						|
        SYNTAX IpAddress
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The ip address that NMS can identify the managed
 | 
						|
                device"
 | 
						|
        ::= { upsmgAgent 1}
 | 
						|
 | 
						|
upsmgAgentSubnetMask OBJECT-TYPE
 | 
						|
        SYNTAX IpAddress
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " Internet address subnet mask"
 | 
						|
        ::= { upsmgAgent 2}
 | 
						|
 | 
						|
upsmgAgentDefGateway OBJECT-TYPE
 | 
						|
        SYNTAX IpAddress
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The default gateway that allow device managed
 | 
						|
                through routers "
 | 
						|
        ::= { upsmgAgent 3}
 | 
						|
 | 
						|
upsmgAgentBaudRate OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " the serial port communication speed. only 2400,
 | 
						|
                4800, and 9600 allowed"
 | 
						|
        ::= { upsmgAgent 4}
 | 
						|
 | 
						|
upsmgAgentPollRate OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The frequency that proxy agent polls the connected
 | 
						|
                UPS in ASCII protocol. (unit : second)"
 | 
						|
        ::= { upsmgAgent 5}
 | 
						|
 | 
						|
upsmgAgentType OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                deviceEth(1),
 | 
						|
                deviceTR(2),
 | 
						|
                proxyEth(3),
 | 
						|
                proxyTR(4),
 | 
						|
                other(5)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                 " The type of agent."
 | 
						|
        ::= { upsmgAgent 6}
 | 
						|
 | 
						|
upsmgAgentTrapAlarmDelay OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The interval for the Trap packet retransmission,
 | 
						|
                while the TRAP Acknowledge is implemented and
 | 
						|
                the ack is received within the interval."
 | 
						|
        ::= { upsmgAgent 7}
 | 
						|
 | 
						|
upsmgAgentTrapAlarmRetry OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                 " The retry count for retransmitting Trap
 | 
						|
                 packet while the TRAP acknowledge is
 | 
						|
                 implemented."
 | 
						|
        ::= { upsmgAgent 8}
 | 
						|
 | 
						|
upsmgAgentReset OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                reset (1),
 | 
						|
                nothing(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                 " The variable initiates reset operation  in
 | 
						|
                 agent software, ie. warm start. write reset(1)
 | 
						|
                 to any one of UPS MIB array, will result in
 | 
						|
                 the same reset operation."
 | 
						|
        ::= { upsmgAgent 9}
 | 
						|
 | 
						|
upsmgAgentFactReset OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                reset (1),
 | 
						|
                nothing(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                 " The variable initiates reset operation in
 | 
						|
                 agent software, ie. warm start, and load
 | 
						|
                 default data (Factory setting) to EEPROM
 | 
						|
                 and to runtime parameters associated with
 | 
						|
                 the UPS."
 | 
						|
        ::= { upsmgAgent 10}
 | 
						|
 | 
						|
upsmgAgentMibVersion OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The version of the MIB implemented in agent."
 | 
						|
        ::= { upsmgAgent 11}
 | 
						|
 | 
						|
upsmgAgentFirmwareVersion OBJECT-TYPE
 | 
						|
        SYNTAX DisplayString(SIZE(0..32))
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The agent firmware version."
 | 
						|
        ::= { upsmgAgent 12}
 | 
						|
 | 
						|
upsmgAgentCommUPS OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The status of communication between agent and ups.
 | 
						|
                Even value means no communication, and odd value
 | 
						|
                means a certain level of communication with devices
 | 
						|
                daisy-chained on the serial port. The value is the
 | 
						|
                following: 1000*NSE + 100*NSW + 10*UPSW + UPST with
 | 
						|
                UPST is UPS type:       5 if no UPS;
 | 
						|
                                        3 if PI (Protocol Interface)
 | 
						|
                                        1 if U-Talk UPS;
 | 
						|
                UPSW is the number of switchable plugs of the UPS;
 | 
						|
                NSW is the number of UM-Switch devices;
 | 
						|
                NSE is the number of UM-Sensor devices."
 | 
						|
        ::= { upsmgAgent 13}
 | 
						|
 | 
						|
upsmgAgentTrapAck OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The last Trap number that has been received by UM-View."
 | 
						|
        ::= { upsmgAgent 14}
 | 
						|
 | 
						|
upsmgAgentAutoLearning OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The enabled/disabled configuration of the Auto Learning
 | 
						|
                process of the agent, default value is yes(1) e.g. enabled."
 | 
						|
        ::= { upsmgAgent 15}
 | 
						|
 | 
						|
upsmgAgentBootP OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The enabled/disabled configuration of the BootP process,
 | 
						|
                default value is yes(1) e.g. enabled."
 | 
						|
        ::= { upsmgAgent 16}
 | 
						|
 | 
						|
upsmgAgentTFTP OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER {
 | 
						|
                yes(1),
 | 
						|
                no(2)
 | 
						|
        }
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The enabled/disabled configuration of the TFTP process,
 | 
						|
                default value is no(2) e.g. disabled."
 | 
						|
        ::= { upsmgAgent 17}
 | 
						|
 | 
						|
upsmgAgentTrapSignature OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-only
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                " The signature of the trap acknowledged by a manager."
 | 
						|
        ::= { upsmgAgent 18}
 | 
						|
 | 
						|
------------------------
 | 
						|
-- upsmgRemote group --
 | 
						|
------------------------
 | 
						|
 | 
						|
upsmgRemoteOnBattery OBJECT-TYPE
 | 
						|
        SYNTAX INTEGER
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "An object to inform an ups-less agent that the remote
 | 
						|
                 UPS is on autonomy. This object could be set by
 | 
						|
                 a management application."
 | 
						|
        ::= { upsmgRemote 1}
 | 
						|
 | 
						|
upsmgRemoteIpAddress OBJECT-TYPE
 | 
						|
        SYNTAX IpAddress
 | 
						|
        ACCESS read-write
 | 
						|
        STATUS mandatory
 | 
						|
        DESCRIPTION
 | 
						|
                "An object to give the IP address of the agent managing
 | 
						|
                 the remote UPS. This object could be read by managers
 | 
						|
                 to perform management of receptacle dependencies
 | 
						|
                 between two different agents."
 | 
						|
        ::= { upsmgRemote 2}
 | 
						|
 | 
						|