79 lines
3.4 KiB
PHP

<?php
// blindly copied from sentry3
if ($device['os'] == 'raritan') {
$divisor = '1000';
$outlet_divisor = $divisor;
$multiplier = '1';
// Check Inlets
$inlet_oids = snmp_walk($device, 'inletLabel', '-Osqn', 'PDU2-MIB');
$inlet_oids = trim($inlet_oids);
if ($inlet_oids) {
echo 'PDU Inlet ';
}
foreach (explode("\n", $inlet_oids) as $inlet_data) {
$inlet_data = trim($inlet_data);
if ($inlet_data) {
list($inlet_oid,$inlet_descr) = explode(' ', $inlet_data, 2);
$inlet_split_oid = explode('.', $inlet_oid);
$inlet_index = $inlet_split_oid[(count($inlet_split_oid) - 2)].'.'.$inlet_split_oid[(count($inlet_split_oid) - 1)];
$inlet_oid = ".1.3.6.1.4.1.13742.6.5.2.3.1.4.$inlet_index.1";
$inlet_divisor = pow(10, snmp_get($device, "inletSensorDecimalDigits.$inlet_index.rmsCurrent", '-Ovq', 'PDU2-MIB'));
$inlet_current = (snmp_get($device, "measurementsInletSensorValue.$inlet_index.1", '-Ovq', 'PDU2-MIB') / $inlet_divisor);
if ($inlet_current >= 0) {
discover_sensor($valid['sensor'], 'current', $device, $inlet_oid, $inlet_index, 'raritan', $inlet_descr, $inlet_divisor, $multiplier, null, null, null, null, $inlet_current);
}
}
}
//
// Check for per-outlet polling
$outlet_oids = snmp_walk($device, 'outletIndex', '-Osqn', 'PDU-MIB');
$outlet_oids = trim($outlet_oids);
if ($outlet_oids) {
echo 'PDU Outlet ';
}
foreach (explode("\n", $outlet_oids) as $outlet_data) {
$outlet_data = trim($outlet_data);
if ($outlet_data) {
list($outlet_oid,$outlet_descr) = explode(' ', $outlet_data, 2);
$outlet_split_oid = explode('.', $outlet_oid);
$outlet_index = $outlet_split_oid[(count($outlet_split_oid) - 1)];
$outletsuffix = "$outlet_index";
$outlet_insert_index = $outlet_index;
// outletLoadValue: "A non-negative value indicates the measured load in milli Amps"
$outlet_oid = ".1.3.6.1.4.1.13742.4.1.2.2.1.4.$outletsuffix";
$outlet_descr = snmp_get($device, "outletLabel.$outletsuffix", '-Ovq', 'PDU-MIB');
$outlet_low_warn_limit = null;
$outlet_low_limit = null;
$outlet_high_warn_limit = (snmp_get($device, "outletCurrentUpperWarning.$outletsuffix", '-Ovq', 'PDU-MIB') / $outlet_divisor);
$outlet_high_limit = (snmp_get($device, "outletCurrentUpperCritical.$outletsuffix", '-Ovq', 'PDU-MIB') / $outlet_divisor);
$outlet_current = (snmp_get($device, "outletCurrent.$outletsuffix", '-Ovq', 'PDU-MIB') / $outlet_divisor);
if ($outlet_current >= 0) {
discover_sensor($valid['sensor'], 'current', $device, $outlet_oid, $outlet_insert_index, 'raritan', $outlet_descr, $outlet_divisor, $multiplier, $outlet_low_limit, $outlet_low_warn_limit, $outlet_high_warn_limit, $outlet_high_limit, $outlet_current);
}
}
// unset($outlet_data);
// unset($outlet_oids);
// unset($outlet_oid);
// unset($outlet_descr);
// unset($outlet_low_warn_limit);
// unset($outlet_low_limit);
// unset($outlet_high_warn_limit);
// unset($outlet_high_limit);
// unset($outlet_current);
}
}