UPS-MIB DEFINITIONS ::= BEGIN
 | 
						|
 | 
						|
IMPORTS
 | 
						|
    MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
 | 
						|
    OBJECT-IDENTITY, Counter32, Gauge32, Integer32, mib-2
 | 
						|
        FROM SNMPv2-SMI
 | 
						|
    DisplayString, TimeStamp, TimeInterval, TestAndIncr,
 | 
						|
      AutonomousType, TEXTUAL-CONVENTION
 | 
						|
        FROM SNMPv2-TC
 | 
						|
    MODULE-COMPLIANCE, OBJECT-GROUP
 | 
						|
        FROM SNMPv2-CONF;
 | 
						|
 | 
						|
 | 
						|
upsMIB MODULE-IDENTITY
 | 
						|
    LAST-UPDATED "9402230000Z"
 | 
						|
    ORGANIZATION "IETF UPS MIB Working Group"
 | 
						|
    CONTACT-INFO
 | 
						|
           "        Jeffrey D. Case
 | 
						|
 | 
						|
             Postal: SNMP Research, Incorporated
 | 
						|
                     3001 Kimberlin Heights Road
 | 
						|
                     Knoxville, TN  37920
 | 
						|
                     US
 | 
						|
 | 
						|
                Tel: +1 615 573 1434
 | 
						|
                Fax: +1 615 573 9197
 | 
						|
 | 
						|
             E-mail: case@snmp.com"
 | 
						|
    DESCRIPTION
 | 
						|
            "The MIB module to describe Uninterruptible Power
 | 
						|
            Supplies."
 | 
						|
    ::= { mib-2 33 }
 | 
						|
 | 
						|
PositiveInteger ::= TEXTUAL-CONVENTION
 | 
						|
    DISPLAY-HINT "d"
 | 
						|
    STATUS       current
 | 
						|
    DESCRIPTION
 | 
						|
            "This data type is a non-zero and non-negative value."
 | 
						|
    SYNTAX       INTEGER (1..2147483647)
 | 
						|
 | 
						|
NonNegativeInteger ::= TEXTUAL-CONVENTION
 | 
						|
    DISPLAY-HINT "d"
 | 
						|
    STATUS       current
 | 
						|
    DESCRIPTION
 | 
						|
            "This data type is a non-negative value."
 | 
						|
    SYNTAX       INTEGER (0..2147483647)
 | 
						|
upsObjects            OBJECT IDENTIFIER ::= { upsMIB 1 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- The Device Identification group.
 | 
						|
--      All objects in this group except for upsIdentName and
 | 
						|
--      upsIdentAttachedDevices are set at device initialization
 | 
						|
--      and remain static.
 | 
						|
--
 | 
						|
 | 
						|
upsIdent              OBJECT IDENTIFIER ::= { upsObjects 1 }
 | 
						|
 | 
						|
upsIdentManufacturer OBJECT-TYPE
 | 
						|
    SYNTAX     DisplayString (SIZE (0..31))
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The name of the UPS manufacturer."
 | 
						|
    ::= { upsIdent 1 }
 | 
						|
 | 
						|
upsIdentModel OBJECT-TYPE
 | 
						|
    SYNTAX     DisplayString (SIZE (0..63))
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS Model designation."
 | 
						|
    ::= { upsIdent 2 }
 | 
						|
 | 
						|
upsIdentUPSSoftwareVersion OBJECT-TYPE
 | 
						|
    SYNTAX     DisplayString (SIZE (0..63))
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS firmware/software version(s).  This variable
 | 
						|
            may or may not have the same value as
 | 
						|
            upsIdentAgentSoftwareVersion in some implementations."
 | 
						|
    ::= { upsIdent 3 }
 | 
						|
 | 
						|
upsIdentAgentSoftwareVersion OBJECT-TYPE
 | 
						|
    SYNTAX     DisplayString (SIZE (0..63))
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS agent software version.  This variable may or
 | 
						|
            may not have the same value as
 | 
						|
            upsIdentUPSSoftwareVersion in some implementations."
 | 
						|
    ::= { upsIdent 4 }
 | 
						|
 | 
						|
upsIdentName OBJECT-TYPE
 | 
						|
    SYNTAX     DisplayString (SIZE(0..63))
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A string identifying the UPS.  This object should be
 | 
						|
            set by the administrator."
 | 
						|
    ::= { upsIdent 5 }
 | 
						|
 | 
						|
upsIdentAttachedDevices OBJECT-TYPE
 | 
						|
    SYNTAX     DisplayString (SIZE(0..63))
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A string identifying the devices attached to the
 | 
						|
            output(s) of the UPS.  This object should be set by
 | 
						|
            the administrator."
 | 
						|
    ::= { upsIdent 6 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- Battery Group
 | 
						|
--
 | 
						|
 | 
						|
upsBattery            OBJECT IDENTIFIER ::= { upsObjects 2 }
 | 
						|
 | 
						|
upsBatteryStatus OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        unknown(1),
 | 
						|
        batteryNormal(2),
 | 
						|
        batteryLow(3),
 | 
						|
        batteryDepleted(4)
 | 
						|
    }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The indication of the capacity remaining in the UPS
 | 
						|
            system's batteries.   A value of batteryNormal
 | 
						|
            indicates that the remaining run-time is greater than
 | 
						|
            upsConfigLowBattTime.  A value of batteryLow indicates
 | 
						|
            that the remaining battery run-time is less than or
 | 
						|
            equal to upsConfigLowBattTime.  A value of
 | 
						|
            batteryDepleted indicates that the UPS will be unable
 | 
						|
            to sustain the present load when and if the utility
 | 
						|
            power is lost (including the possibility that the
 | 
						|
            utility power is currently absent and the UPS is
 | 
						|
            unable to sustain the output)."
 | 
						|
    ::= { upsBattery 1 }
 | 
						|
 | 
						|
upsSecondsOnBattery OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "seconds"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "If the unit is on battery power, the elapsed time
 | 
						|
            since the UPS last switched to battery power, or the
 | 
						|
            time since the network management subsystem was last
 | 
						|
            restarted, whichever is less.  Zero shall be returned
 | 
						|
            if the unit is not on battery power."
 | 
						|
    ::= { upsBattery 2 }
 | 
						|
 | 
						|
upsEstimatedMinutesRemaining OBJECT-TYPE
 | 
						|
    SYNTAX     PositiveInteger
 | 
						|
    UNITS      "minutes"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An estimate of the time to battery charge depletion
 | 
						|
            under the present load conditions if the utility power
 | 
						|
            is off and remains off, or if it were to be lost and
 | 
						|
            remain off."
 | 
						|
    ::= { upsBattery 3 }
 | 
						|
 | 
						|
upsEstimatedChargeRemaining OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER (0..100)
 | 
						|
    UNITS      "percent"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An estimate of the battery charge remaining expressed
 | 
						|
            as a percent of full charge."
 | 
						|
    ::= { upsBattery 4 }
 | 
						|
 | 
						|
upsBatteryVoltage OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 Volt DC"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the present battery voltage."
 | 
						|
    ::= { upsBattery 5 }
 | 
						|
 | 
						|
upsBatteryCurrent OBJECT-TYPE
 | 
						|
    SYNTAX     Integer32
 | 
						|
    UNITS      "0.1 Amp DC"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present battery current."
 | 
						|
    ::= { upsBattery 6 }
 | 
						|
 | 
						|
upsBatteryTemperature OBJECT-TYPE
 | 
						|
    SYNTAX     Integer32
 | 
						|
    UNITS      "degrees Centigrade"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The ambient temperature at or near the UPS Battery
 | 
						|
            casing."
 | 
						|
    ::= { upsBattery 7 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- Input Group
 | 
						|
--
 | 
						|
 | 
						|
upsInput              OBJECT IDENTIFIER ::= { upsObjects 3 }
 | 
						|
 | 
						|
upsInputLineBads OBJECT-TYPE
 | 
						|
    SYNTAX     Counter32
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A count of the number of times the input entered an
 | 
						|
            out-of-tolerance condition as defined by the
 | 
						|
            manufacturer.  This count is incremented by one each
 | 
						|
            time the input transitions from zero out-of-tolerance
 | 
						|
            lines to one or more input lines out-of-tolerance."
 | 
						|
    ::= { upsInput 1 }
 | 
						|
 | 
						|
 | 
						|
upsInputNumLines OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The number of input lines utilized in this device.
 | 
						|
            This variable indicates the number of rows in the
 | 
						|
            input table."
 | 
						|
    ::= { upsInput 2 }
 | 
						|
 | 
						|
upsInputTable OBJECT-TYPE
 | 
						|
    SYNTAX     SEQUENCE OF UpsInputEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A list of input table entries.  The number of entries
 | 
						|
            is given by the value of upsInputNumLines."
 | 
						|
    ::= { upsInput 3 }
 | 
						|
 | 
						|
upsInputEntry OBJECT-TYPE
 | 
						|
    SYNTAX     UpsInputEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An entry containing information applicable to a
 | 
						|
            particular input line."
 | 
						|
    INDEX { upsInputLineIndex }
 | 
						|
    ::= { upsInputTable 1 }
 | 
						|
 | 
						|
UpsInputEntry ::= SEQUENCE {
 | 
						|
    upsInputLineIndex   PositiveInteger,
 | 
						|
    upsInputFrequency   NonNegativeInteger,
 | 
						|
    upsInputVoltage     NonNegativeInteger,
 | 
						|
    upsInputCurrent     NonNegativeInteger,
 | 
						|
    upsInputTruePower   NonNegativeInteger
 | 
						|
}
 | 
						|
 | 
						|
upsInputLineIndex OBJECT-TYPE
 | 
						|
    SYNTAX     PositiveInteger
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The input line identifier."
 | 
						|
    ::= { upsInputEntry 1 }
 | 
						|
 | 
						|
upsInputFrequency OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 Hertz"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present input frequency."
 | 
						|
    ::= { upsInputEntry 2 }
 | 
						|
 | 
						|
upsInputVoltage OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "RMS Volts"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the present input voltage."
 | 
						|
    ::= { upsInputEntry 3 }
 | 
						|
 | 
						|
upsInputCurrent OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 RMS Amp"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the present input current."
 | 
						|
    ::= { upsInputEntry 4 }
 | 
						|
 | 
						|
upsInputTruePower OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "Watts"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the present input true power."
 | 
						|
    ::= { upsInputEntry 5 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- The Output group.
 | 
						|
--
 | 
						|
 | 
						|
upsOutput             OBJECT IDENTIFIER ::= { upsObjects 4 }
 | 
						|
 | 
						|
upsOutputSource OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        other(1),
 | 
						|
        none(2),
 | 
						|
        normal(3),
 | 
						|
        bypass(4),
 | 
						|
        battery(5),
 | 
						|
        booster(6),
 | 
						|
        reducer(7)
 | 
						|
    }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present source of output power.  The enumeration
 | 
						|
            none(2) indicates that there is no source of output
 | 
						|
            power (and therefore no output power), for example,
 | 
						|
            the system has opened the output breaker."
 | 
						|
    ::= { upsOutput 1 }
 | 
						|
 | 
						|
upsOutputFrequency OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 Hertz"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present output frequency."
 | 
						|
    ::= { upsOutput 2 }
 | 
						|
 | 
						|
upsOutputNumLines OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The number of output lines utilized in this device.
 | 
						|
            This variable indicates the number of rows in the
 | 
						|
            output table."
 | 
						|
    ::= { upsOutput 3 }
 | 
						|
 | 
						|
upsOutputTable OBJECT-TYPE
 | 
						|
    SYNTAX     SEQUENCE OF UpsOutputEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A list of output table entries.  The number of
 | 
						|
            entries is given by the value of upsOutputNumLines."
 | 
						|
    ::= { upsOutput 4 }
 | 
						|
 | 
						|
upsOutputEntry OBJECT-TYPE
 | 
						|
    SYNTAX     UpsOutputEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An entry containing information applicable to a
 | 
						|
            particular output line."
 | 
						|
    INDEX { upsOutputLineIndex }
 | 
						|
    ::= { upsOutputTable 1 }
 | 
						|
 | 
						|
UpsOutputEntry ::= SEQUENCE {
 | 
						|
    upsOutputLineIndex   PositiveInteger,
 | 
						|
    upsOutputVoltage     NonNegativeInteger,
 | 
						|
    upsOutputCurrent     NonNegativeInteger,
 | 
						|
    upsOutputPower       NonNegativeInteger,
 | 
						|
    upsOutputPercentLoad INTEGER
 | 
						|
}
 | 
						|
 | 
						|
upsOutputLineIndex OBJECT-TYPE
 | 
						|
    SYNTAX     PositiveInteger
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The output line identifier."
 | 
						|
    ::= { upsOutputEntry 1 }
 | 
						|
 | 
						|
upsOutputVoltage OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "RMS Volts"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present output voltage."
 | 
						|
    ::= { upsOutputEntry 2 }
 | 
						|
 | 
						|
upsOutputCurrent OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 RMS Amp"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present output current."
 | 
						|
    ::= { upsOutputEntry 3 }
 | 
						|
 | 
						|
upsOutputPower OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "Watts"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present output true power."
 | 
						|
    ::= { upsOutputEntry 4 }
 | 
						|
 | 
						|
upsOutputPercentLoad OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER (0..200)
 | 
						|
    UNITS      "percent"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The percentage of the UPS power capacity presently
 | 
						|
            being used on this output line, i.e., the greater of
 | 
						|
            the percent load of true power capacity and the
 | 
						|
            percent load of VA."
 | 
						|
    ::= { upsOutputEntry 5 }
 | 
						|
 | 
						|
--
 | 
						|
-- The Bypass group.
 | 
						|
--
 | 
						|
 | 
						|
upsBypass             OBJECT IDENTIFIER ::= { upsObjects 5 }
 | 
						|
 | 
						|
upsBypassFrequency OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 Hertz"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present bypass frequency."
 | 
						|
    ::= { upsBypass 1 }
 | 
						|
 | 
						|
upsBypassNumLines OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The number of bypass lines utilized in this device.
 | 
						|
            This entry indicates the number of rows in the bypass
 | 
						|
            table."
 | 
						|
    ::= { upsBypass 2 }
 | 
						|
 | 
						|
upsBypassTable OBJECT-TYPE
 | 
						|
    SYNTAX     SEQUENCE OF UpsBypassEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A list of bypass table entries.  The number of
 | 
						|
            entries is given by the value of upsBypassNumLines."
 | 
						|
    ::= { upsBypass 3 }
 | 
						|
 | 
						|
upsBypassEntry OBJECT-TYPE
 | 
						|
    SYNTAX     UpsBypassEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An entry containing information applicable to a
 | 
						|
            particular bypass input."
 | 
						|
    INDEX { upsBypassLineIndex }
 | 
						|
    ::= { upsBypassTable 1 }
 | 
						|
 | 
						|
UpsBypassEntry ::= SEQUENCE {
 | 
						|
    upsBypassLineIndex  PositiveInteger,
 | 
						|
    upsBypassVoltage    NonNegativeInteger,
 | 
						|
    upsBypassCurrent    NonNegativeInteger,
 | 
						|
    upsBypassPower      NonNegativeInteger
 | 
						|
}
 | 
						|
 | 
						|
upsBypassLineIndex OBJECT-TYPE
 | 
						|
    SYNTAX     PositiveInteger
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The bypass line identifier."
 | 
						|
    ::= { upsBypassEntry 1 }
 | 
						|
 | 
						|
upsBypassVoltage OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "RMS Volts"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present bypass voltage."
 | 
						|
    ::= { upsBypassEntry 2 }
 | 
						|
 | 
						|
upsBypassCurrent OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 RMS Amp"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present bypass current."
 | 
						|
    ::= { upsBypassEntry 3 }
 | 
						|
 | 
						|
upsBypassPower OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "Watts"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present true power conveyed by the bypass."
 | 
						|
    ::= { upsBypassEntry 4 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- The Alarm group.
 | 
						|
--
 | 
						|
 | 
						|
upsAlarm              OBJECT IDENTIFIER ::= { upsObjects 6 }
 | 
						|
 | 
						|
upsAlarmsPresent OBJECT-TYPE
 | 
						|
    SYNTAX     Gauge32
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The present number of active alarm conditions."
 | 
						|
    ::= { upsAlarm 1 }
 | 
						|
 | 
						|
upsAlarmTable OBJECT-TYPE
 | 
						|
    SYNTAX     SEQUENCE OF UpsAlarmEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A list of alarm table entries.  The table contains
 | 
						|
            zero, one, or many rows at any moment, depending upon
 | 
						|
            the number of alarm conditions in effect.  The table
 | 
						|
            is initially empty at agent startup.  The agent
 | 
						|
            creates a row in the table each time a condition is
 | 
						|
            detected and deletes that row when that condition no
 | 
						|
            longer pertains.  The agent creates the first row with
 | 
						|
            upsAlarmId equal to 1, and increments the value of
 | 
						|
            upsAlarmId each time a new row is created, wrapping to
 | 
						|
            the first free value greater than or equal to 1 when
 | 
						|
            the maximum value of upsAlarmId would otherwise be
 | 
						|
            exceeded.  Consequently, after multiple operations,
 | 
						|
            the table may become sparse, e.g., containing entries
 | 
						|
            for rows 95, 100, 101, and 203 and the entries should
 | 
						|
            not be assumed to be in chronological order because
 | 
						|
            upsAlarmId might have wrapped.
 | 
						|
 | 
						|
            Alarms are named by an AutonomousType (OBJECT
 | 
						|
            IDENTIFIER), upsAlarmDescr, to allow a single table to
 | 
						|
            reflect well known alarms plus alarms defined by a
 | 
						|
            particular implementation, i.e., as documented in the
 | 
						|
            private enterprise MIB definition for the device.  No
 | 
						|
            two rows will have the same value of upsAlarmDescr,
 | 
						|
            since alarms define conditions.  In order to meet this
 | 
						|
            requirement, care should be taken in the definition of
 | 
						|
            alarm conditions to insure that a system cannot enter
 | 
						|
            the same condition multiple times simultaneously.
 | 
						|
 | 
						|
            The number of rows in the table at any given time is
 | 
						|
            reflected by the value of upsAlarmsPresent."
 | 
						|
    ::= { upsAlarm 2 }
 | 
						|
 | 
						|
upsAlarmEntry OBJECT-TYPE
 | 
						|
    SYNTAX     UpsAlarmEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An entry containing information applicable to a
 | 
						|
            particular alarm."
 | 
						|
    INDEX { upsAlarmId }
 | 
						|
    ::= { upsAlarmTable 1 }
 | 
						|
 | 
						|
UpsAlarmEntry ::= SEQUENCE {
 | 
						|
    upsAlarmId          PositiveInteger,
 | 
						|
    upsAlarmDescr       AutonomousType,
 | 
						|
    upsAlarmTime        TimeStamp
 | 
						|
}
 | 
						|
 | 
						|
upsAlarmId OBJECT-TYPE
 | 
						|
    SYNTAX     PositiveInteger
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A unique identifier for an alarm condition.  This
 | 
						|
            value must remain constant."
 | 
						|
    ::= { upsAlarmEntry 1 }
 | 
						|
 | 
						|
upsAlarmDescr OBJECT-TYPE
 | 
						|
    SYNTAX     AutonomousType
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A reference to an alarm description object.  The
 | 
						|
            object referenced should not be accessible, but rather
 | 
						|
            be used to provide a unique description of the alarm
 | 
						|
            condition."
 | 
						|
    ::= { upsAlarmEntry 2 }
 | 
						|
 | 
						|
upsAlarmTime OBJECT-TYPE
 | 
						|
    SYNTAX     TimeStamp
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The value of sysUpTime when the alarm condition was
 | 
						|
            detected.  If the alarm condition was detected at the
 | 
						|
            time of agent startup and presumably existed before
 | 
						|
            agent startup, the value of upsAlarmTime shall equal
 | 
						|
            0."
 | 
						|
    ::= { upsAlarmEntry 3 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- Well known alarm conditions.
 | 
						|
--
 | 
						|
 | 
						|
upsWellKnownAlarms    OBJECT IDENTIFIER ::= { upsAlarm 3 }
 | 
						|
 | 
						|
upsAlarmBatteryBad OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "One or more batteries have been determined to require
 | 
						|
            replacement."
 | 
						|
    ::= { upsWellKnownAlarms  1 }
 | 
						|
 | 
						|
upsAlarmOnBattery OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS is drawing power from the batteries."
 | 
						|
    ::= { upsWellKnownAlarms  2 }
 | 
						|
 | 
						|
upsAlarmLowBattery OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The remaining battery run-time is less than or equal
 | 
						|
            to upsConfigLowBattTime."
 | 
						|
    ::= { upsWellKnownAlarms  3 }
 | 
						|
 | 
						|
 | 
						|
upsAlarmDepletedBattery OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS will be unable to sustain the present load
 | 
						|
            when and if the utility power is lost."
 | 
						|
    ::= { upsWellKnownAlarms  4 }
 | 
						|
 | 
						|
upsAlarmTempBad OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A temperature is out of tolerance."
 | 
						|
    ::= { upsWellKnownAlarms  5 }
 | 
						|
 | 
						|
upsAlarmInputBad OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An input condition is out of tolerance."
 | 
						|
    ::= { upsWellKnownAlarms  6 }
 | 
						|
 | 
						|
upsAlarmOutputBad OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An output condition (other than OutputOverload) is
 | 
						|
            out of tolerance."
 | 
						|
    ::= { upsWellKnownAlarms  7 }
 | 
						|
 | 
						|
upsAlarmOutputOverload OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The output load exceeds the UPS output capacity."
 | 
						|
    ::= { upsWellKnownAlarms  8 }
 | 
						|
 | 
						|
upsAlarmOnBypass OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The Bypass is presently engaged on the UPS."
 | 
						|
    ::= { upsWellKnownAlarms  9 }
 | 
						|
 | 
						|
upsAlarmBypassBad OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The Bypass is out of tolerance."
 | 
						|
    ::= { upsWellKnownAlarms 10 }
 | 
						|
 | 
						|
upsAlarmOutputOffAsRequested OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS has shutdown as requested, i.e., the output
 | 
						|
            is off."
 | 
						|
    ::= { upsWellKnownAlarms 11 }
 | 
						|
 | 
						|
upsAlarmUpsOffAsRequested OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The entire UPS has shutdown as commanded."
 | 
						|
    ::= { upsWellKnownAlarms 12 }
 | 
						|
 | 
						|
upsAlarmChargerFailed OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "An uncorrected problem has been detected within the
 | 
						|
            UPS charger subsystem."
 | 
						|
    ::= { upsWellKnownAlarms 13 }
 | 
						|
 | 
						|
upsAlarmUpsOutputOff OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The output of the UPS is in the off state."
 | 
						|
    ::= { upsWellKnownAlarms 14 }
 | 
						|
 | 
						|
upsAlarmUpsSystemOff OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS system is in the off state."
 | 
						|
    ::= { upsWellKnownAlarms 15 }
 | 
						|
 | 
						|
upsAlarmFanFailure OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The failure of one or more fans in the UPS has been
 | 
						|
            detected."
 | 
						|
    ::= { upsWellKnownAlarms 16 }
 | 
						|
 | 
						|
upsAlarmFuseFailure OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The failure of one or more fuses has been detected."
 | 
						|
    ::= { upsWellKnownAlarms 17 }
 | 
						|
 | 
						|
upsAlarmGeneralFault OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A general fault in the UPS has been detected."
 | 
						|
    ::= { upsWellKnownAlarms 18 }
 | 
						|
 | 
						|
upsAlarmDiagnosticTestFailed OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The result of the last diagnostic test indicates a
 | 
						|
            failure."
 | 
						|
    ::= { upsWellKnownAlarms 19 }
 | 
						|
 | 
						|
upsAlarmCommunicationsLost OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A problem has been encountered in the communications
 | 
						|
            between the agent and the UPS."
 | 
						|
    ::= { upsWellKnownAlarms 20 }
 | 
						|
 | 
						|
upsAlarmAwaitingPower OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS output is off and the UPS is awaiting the
 | 
						|
            return of input power."
 | 
						|
    ::= { upsWellKnownAlarms 21 }
 | 
						|
 | 
						|
upsAlarmShutdownPending OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A upsShutdownAfterDelay countdown is underway."
 | 
						|
    ::= { upsWellKnownAlarms 22 }
 | 
						|
 | 
						|
upsAlarmShutdownImminent OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS will turn off power to the load in less than
 | 
						|
            5 seconds; this may be either a timed shutdown or a
 | 
						|
            low battery shutdown."
 | 
						|
    ::= { upsWellKnownAlarms 23 }
 | 
						|
 | 
						|
upsAlarmTestInProgress OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A test is in progress, as initiated and indicated by
 | 
						|
            the Test Group.  Tests initiated via other
 | 
						|
            implementation-specific mechanisms can indicate the
 | 
						|
            presence of the testing in the alarm table, if
 | 
						|
            desired, via a OBJECT-IDENTITY macro in the MIB
 | 
						|
            document specific to that implementation and are
 | 
						|
            outside the scope of this OBJECT-IDENTITY."
 | 
						|
    ::= { upsWellKnownAlarms 24 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- The Test Group
 | 
						|
--
 | 
						|
 | 
						|
upsTest               OBJECT IDENTIFIER ::= { upsObjects 7 }
 | 
						|
 | 
						|
upsTestId OBJECT-TYPE
 | 
						|
    SYNTAX     OBJECT IDENTIFIER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The test is named by an OBJECT IDENTIFIER which
 | 
						|
            allows a standard mechanism for the initiation of
 | 
						|
            tests, including the well known tests identified in
 | 
						|
            this document as well as those introduced by a
 | 
						|
            particular implementation, i.e., as documented in the
 | 
						|
            private enterprise MIB definition for the device.
 | 
						|
 | 
						|
            Setting this variable initiates the named test. Sets
 | 
						|
            to this variable require the presence of
 | 
						|
            upsTestSpinLock in the same SNMP message.
 | 
						|
 | 
						|
            The set request will be rejected with an appropriate
 | 
						|
            error message if the requested test cannot be
 | 
						|
            performed, including attempts to start a test when
 | 
						|
            another test is already in progress.  The status of
 | 
						|
            the current or last test is maintained in
 | 
						|
            upsTestResultsSummary. Tests in progress may be
 | 
						|
            aborted by setting the upsTestId variable to
 | 
						|
            upsTestAbortTestInProgress.
 | 
						|
 | 
						|
            Read operations return the value of the name of the
 | 
						|
            test in progress if a test is in progress or the name
 | 
						|
            of the last test performed if no test is in progress,
 | 
						|
            unless no test has been run, in which case the well
 | 
						|
            known value upsTestNoTestsInitiated is returned."
 | 
						|
    ::= { upsTest 1 }
 | 
						|
 | 
						|
-- see [6] for more information on the semantics of objects with
 | 
						|
-- syntax of TestAndIncr
 | 
						|
 | 
						|
upsTestSpinLock OBJECT-TYPE
 | 
						|
    SYNTAX     TestAndIncr
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A spin lock on the test subsystem.  The spinlock is
 | 
						|
            used as follows.
 | 
						|
 | 
						|
            Before starting a test, a manager-station should make
 | 
						|
            sure that a test is not in progress as follows:
 | 
						|
 | 
						|
                try_again:
 | 
						|
                  get (upsTestSpinLock)
 | 
						|
                  while (upsTestResultsSummary == inProgress) {
 | 
						|
                    /* loop while a test is running for another
 | 
						|
            manager */
 | 
						|
                    short delay
 | 
						|
                    get (upsTestSpinLock)
 | 
						|
                  }
 | 
						|
                  lock_value = upsTestSpinLock
 | 
						|
                  /* no test in progress, start the test */
 | 
						|
                  set (upsTestSpinLock = lock_value, upsTestId =
 | 
						|
            requested_test)
 | 
						|
                  if (error_index == 1) { /* (upsTestSpinLock
 | 
						|
            failed) */
 | 
						|
                    /* if problem is not access control, then
 | 
						|
                        some other manager slipped in ahead of us
 | 
						|
            */
 | 
						|
                    goto try_again
 | 
						|
                  }
 | 
						|
                  if (error_index == 2) { /* (upsTestId) */
 | 
						|
                    /* cannot perform the test */
 | 
						|
                    give up
 | 
						|
                  }
 | 
						|
                  /* test started ok */
 | 
						|
                  /* wait for test completion by polling
 | 
						|
            upsTestResultsSummary */
 | 
						|
                  get (upsTestSpinLock, upsTestResultsSummary,
 | 
						|
            upsTestResultsDetail)
 | 
						|
                  while (upsTestResultsSummary == inProgress) {
 | 
						|
                    short delay
 | 
						|
                    get (upsTestSpinLock, upsTestResultsSummary,
 | 
						|
            upsTestResultsDetail)
 | 
						|
                  }
 | 
						|
                  /* when test completes, retrieve any additional
 | 
						|
            test results */
 | 
						|
                  /* if upsTestSpinLock == lock_value + 1, then
 | 
						|
            these are our test */
 | 
						|
                  /* results (as opposed to another manager's */
 | 
						|
                  The initial value of upsTestSpinLock at agent
 | 
						|
            initialization shall
 | 
						|
                  be 1."
 | 
						|
    ::= { upsTest 2 }
 | 
						|
 | 
						|
upsTestResultsSummary OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        donePass(1),
 | 
						|
        doneWarning(2),
 | 
						|
        doneError(3),
 | 
						|
        aborted(4),
 | 
						|
        inProgress(5),
 | 
						|
        noTestsInitiated(6)
 | 
						|
    }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The results of the current or last UPS diagnostics
 | 
						|
            test performed.  The values for donePass(1),
 | 
						|
            doneWarning(2), and doneError(3) indicate that the
 | 
						|
            test completed either successfully, with a warning, or
 | 
						|
            with an error, respectively.  The value aborted(4) is
 | 
						|
            returned for tests which are aborted by setting the
 | 
						|
            value of upsTestId to upsTestAbortTestInProgress.
 | 
						|
            Tests which have not yet concluded are indicated by
 | 
						|
            inProgress(5).  The value noTestsInitiated(6)
 | 
						|
            indicates that no previous test results are available,
 | 
						|
            such as is the case when no tests have been run since
 | 
						|
            the last reinitialization of the network management
 | 
						|
            subsystem and the system has no provision for non-
 | 
						|
            volatile storage of test results."
 | 
						|
    ::= { upsTest 3 }
 | 
						|
 | 
						|
upsTestResultsDetail OBJECT-TYPE
 | 
						|
    SYNTAX     DisplayString (SIZE (0..255))
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "Additional information about upsTestResultsSummary.
 | 
						|
            If no additional information available, a zero length
 | 
						|
            string is returned."
 | 
						|
    ::= { upsTest 4 }
 | 
						|
 | 
						|
upsTestStartTime OBJECT-TYPE
 | 
						|
    SYNTAX     TimeStamp
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The value of sysUpTime at the time the test in
 | 
						|
            progress was initiated, or, if no test is in progress,
 | 
						|
            the time the previous test was initiated.  If the
 | 
						|
            value of upsTestResultsSummary is noTestsInitiated(6),
 | 
						|
            upsTestStartTime has the value 0."
 | 
						|
    ::= { upsTest 5 }
 | 
						|
 | 
						|
upsTestElapsedTime OBJECT-TYPE
 | 
						|
    SYNTAX     TimeInterval
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The amount of time, in TimeTicks, since the test in
 | 
						|
            progress was initiated, or, if no test is in progress,
 | 
						|
            the previous test took to complete.  If the value of
 | 
						|
            upsTestResultsSummary is noTestsInitiated(6),
 | 
						|
            upsTestElapsedTime has the value 0."
 | 
						|
    ::= { upsTest 6 }
 | 
						|
 | 
						|
--
 | 
						|
-- Well known tests.
 | 
						|
--
 | 
						|
 | 
						|
upsWellKnownTests     OBJECT IDENTIFIER ::= { upsTest 7 }
 | 
						|
 | 
						|
 | 
						|
upsTestNoTestsInitiated OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "No tests have been initiated and no test is in
 | 
						|
            progress."
 | 
						|
    ::= { upsWellKnownTests  1 }
 | 
						|
 | 
						|
upsTestAbortTestInProgress OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The test in progress is to be aborted / the test in
 | 
						|
            progress was aborted."
 | 
						|
    ::= { upsWellKnownTests  2 }
 | 
						|
 | 
						|
upsTestGeneralSystemsTest OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The manufacturer's standard test of UPS device
 | 
						|
            systems."
 | 
						|
    ::= { upsWellKnownTests  3 }
 | 
						|
 | 
						|
upsTestQuickBatteryTest OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "A test that is sufficient to determine if the battery
 | 
						|
            needs replacement."
 | 
						|
    ::= { upsWellKnownTests  4 }
 | 
						|
 | 
						|
upsTestDeepBatteryCalibration OBJECT-IDENTITY
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The system is placed on battery to a discharge level,
 | 
						|
            set by the manufacturer, sufficient to determine
 | 
						|
            battery replacement and battery run-time with a high
 | 
						|
            degree of confidence.  WARNING:  this test will leave
 | 
						|
            the battery in a low charge state and will require
 | 
						|
            time for recharging to a level sufficient to provide
 | 
						|
            normal battery duration for the protected load."
 | 
						|
    ::= { upsWellKnownTests  5 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- The Control group.
 | 
						|
--
 | 
						|
 | 
						|
upsControl            OBJECT IDENTIFIER ::= { upsObjects 8 }
 | 
						|
 | 
						|
upsShutdownType OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        output(1),
 | 
						|
        system(2)
 | 
						|
    }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "This object determines the nature of the action to be
 | 
						|
            taken at the time when the countdown of the
 | 
						|
            upsShutdownAfterDelay and upsRebootWithDuration
 | 
						|
            objects reaches zero.
 | 
						|
 | 
						|
            Setting this object to output(1) indicates that
 | 
						|
            shutdown requests should cause only the output of the
 | 
						|
            UPS to turn off.  Setting this object to system(2)
 | 
						|
            indicates that shutdown requests will cause the entire
 | 
						|
            UPS system to turn off."
 | 
						|
    ::= { upsControl 1 }
 | 
						|
 | 
						|
upsShutdownAfterDelay OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER (-1..2147483648)
 | 
						|
    UNITS      "seconds"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "Setting this object will shutdown (i.e., turn off)
 | 
						|
            either the UPS output or the UPS system (as determined
 | 
						|
            by the value of upsShutdownType at the time of
 | 
						|
            shutdown) after the indicated number of seconds, or
 | 
						|
            less if the UPS batteries become depleted. Setting
 | 
						|
            this object to 0 will cause the shutdown to occur
 | 
						|
            immediately.  Setting this object to -1 will abort the
 | 
						|
            countdown.  If the system is already in the desired
 | 
						|
            state at the time the countdown reaches 0, then
 | 
						|
            nothing will happen.  That is, there is no additional
 | 
						|
            action at that time if upsShutdownType = system and
 | 
						|
            the system is already off.  Similarly, there is no
 | 
						|
            additional action at that time if upsShutdownType =
 | 
						|
            output and the output is already off.  When read,
 | 
						|
            upsShutdownAfterDelay will return the number of
 | 
						|
            seconds remaining until shutdown, or -1 if no shutdown
 | 
						|
            countdown is in effect.  On some systems, if the agent
 | 
						|
            is restarted while a shutdown countdown is in effect,
 | 
						|
            the countdown may be aborted.  Sets to this object
 | 
						|
            override any upsShutdownAfterDelay already in effect."
 | 
						|
    ::= { upsControl 2 }
 | 
						|
 | 
						|
upsStartupAfterDelay OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER (-1..2147483648)
 | 
						|
    UNITS      "seconds"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "Setting this object will start the output after the
 | 
						|
            indicated number of seconds, including starting the
 | 
						|
            UPS, if necessary.  Setting this object to 0 will
 | 
						|
            cause the startup to occur immediately.  Setting this
 | 
						|
            object to -1 will abort the countdown.  If the output
 | 
						|
            is already on at the time the countdown reaches 0,
 | 
						|
            then nothing will happen.  Sets to this object
 | 
						|
            override the effect of any upsStartupAfterDelay
 | 
						|
            countdown or upsRebootWithDuration countdown in
 | 
						|
            progress.  When read, upsStartupAfterDelay will return
 | 
						|
            the number of seconds until startup, or -1 if no
 | 
						|
            startup countdown is in effect.  If the countdown
 | 
						|
            expires during a utility failure, the startup shall
 | 
						|
            not occur until the utility power is restored.  On
 | 
						|
            some systems, if the agent is restarted while a
 | 
						|
            startup countdown is in effect, the countdown is
 | 
						|
            aborted."
 | 
						|
    ::= { upsControl 3 }
 | 
						|
 | 
						|
upsRebootWithDuration OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER (-1..300)
 | 
						|
    UNITS      "seconds"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "Setting this object will immediately shutdown (i.e.,
 | 
						|
            turn off) either the UPS output or the UPS system (as
 | 
						|
            determined by the value of upsShutdownType at the time
 | 
						|
            of shutdown) for a period equal to the indicated
 | 
						|
            number of seconds, after which time the output will be
 | 
						|
            started, including starting the UPS, if necessary.  If
 | 
						|
            the number of seconds required to perform the request
 | 
						|
            is greater than the requested duration, then the
 | 
						|
            requested shutdown and startup cycle shall be
 | 
						|
            performed in the minimum time possible, but in no case
 | 
						|
            shall this require more than the requested duration
 | 
						|
            plus 60 seconds.  When read, upsRebootWithDuration
 | 
						|
            shall return the number of seconds remaining in the
 | 
						|
            countdown, or -1 if no countdown is in progress.  If
 | 
						|
            the startup should occur during a utility failure, the
 | 
						|
            startup shall not occur until the utility power is
 | 
						|
            restored."
 | 
						|
    ::= { upsControl 4 }
 | 
						|
 | 
						|
upsAutoRestart OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        on(1),
 | 
						|
        off(2)
 | 
						|
    }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "Setting this object to 'on' will cause the UPS system
 | 
						|
            to restart after a shutdown if the shutdown occurred
 | 
						|
            during a power loss as a result of either a
 | 
						|
            upsShutdownAfterDelay or an internal battery depleted
 | 
						|
            condition.  Setting this object to 'off' will prevent
 | 
						|
            the UPS system from restarting after a shutdown until
 | 
						|
            an operator manually or remotely explicitly restarts
 | 
						|
            it.  If the UPS is in a startup or reboot countdown,
 | 
						|
            then the UPS will not restart until that delay has
 | 
						|
            been satisfied."
 | 
						|
    ::= { upsControl 5 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- The Configuration group.
 | 
						|
--
 | 
						|
 | 
						|
upsConfig             OBJECT IDENTIFIER ::= { upsObjects 9 }
 | 
						|
 | 
						|
upsConfigInputVoltage OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "RMS Volts"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the nominal input voltage.  On those
 | 
						|
            systems which support read-write access to this
 | 
						|
            object, if there is an attempt to set this variable to
 | 
						|
            a value that is not supported, the request must be
 | 
						|
            rejected and the agent shall respond with an
 | 
						|
            appropriate error message, i.e., badValue for SNMPv1,
 | 
						|
            or inconsistentValue for SNMPv2."
 | 
						|
    ::= { upsConfig 1 }
 | 
						|
 | 
						|
upsConfigInputFreq OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 Hertz"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The nominal input frequency.  On those systems which
 | 
						|
            support read-write access to this object, if there is
 | 
						|
            an attempt to set this variable to a value that is not
 | 
						|
            supported, the request must be rejected and the agent
 | 
						|
            shall respond with an appropriate error message, i.e.,
 | 
						|
            badValue for SNMPv1, or inconsistentValue for SNMPv2."
 | 
						|
    ::= { upsConfig 2 }
 | 
						|
 | 
						|
upsConfigOutputVoltage OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "RMS Volts"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the nominal output voltage.  On
 | 
						|
            those systems which support read-write access to this
 | 
						|
            object, if there is an attempt to set this variable to
 | 
						|
            a value that is not supported, the request must be
 | 
						|
            rejected and the agent shall respond with an
 | 
						|
            appropriate error message, i.e., badValue for SNMPv1,
 | 
						|
            or inconsistentValue for SNMPv2."
 | 
						|
    ::= { upsConfig 3 }
 | 
						|
 | 
						|
upsConfigOutputFreq OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "0.1 Hertz"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The nominal output frequency.  On those systems which
 | 
						|
            support read-write access to this object, if there is
 | 
						|
            an attempt to set this variable to a value that is not
 | 
						|
            supported, the request must be rejected and the agent
 | 
						|
            shall respond with an appropriate error message, i.e.,
 | 
						|
            badValue for SNMPv1, or inconsistentValue for SNMPv2."
 | 
						|
    ::= { upsConfig 4 }
 | 
						|
 | 
						|
upsConfigOutputVA OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "Volt-Amps"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the nominal Volt-Amp rating."
 | 
						|
    ::= { upsConfig 5 }
 | 
						|
 | 
						|
upsConfigOutputPower OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "Watts"
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The magnitude of the nominal true power rating."
 | 
						|
    ::= { upsConfig 6 }
 | 
						|
 | 
						|
upsConfigLowBattTime OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "minutes"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The value of upsEstimatedMinutesRemaining at which a
 | 
						|
            lowBattery condition is declared.  For agents which
 | 
						|
            support only discrete (discontinuous) values, then the
 | 
						|
            agent shall round up to the next supported value.  If
 | 
						|
            the requested value is larger than the largest
 | 
						|
            supported value, then the largest supported value
 | 
						|
            shall be selected."
 | 
						|
    ::= { upsConfig 7 }
 | 
						|
 | 
						|
upsConfigAudibleStatus OBJECT-TYPE
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        disabled(1),
 | 
						|
        enabled(2),
 | 
						|
        muted(3)
 | 
						|
    }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The requested state of the audible alarm.  When in
 | 
						|
            the disabled state, the audible alarm should never
 | 
						|
            sound.  The enabled state is self-describing.  Setting
 | 
						|
            this object to muted(3) when the audible alarm is
 | 
						|
            sounding shall temporarily silence the alarm.  It will
 | 
						|
            remain muted until it would normally stop sounding and
 | 
						|
            the value returned for read operations during this
 | 
						|
            period shall equal muted(3).  At the end of this
 | 
						|
            period, the value shall revert to enabled(2).  Writes
 | 
						|
            of the value muted(3) when the audible alarm is not
 | 
						|
            sounding shall be accepted but otherwise shall have no
 | 
						|
            effect."
 | 
						|
    ::= { upsConfig 8 }
 | 
						|
 | 
						|
upsConfigLowVoltageTransferPoint OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "RMS Volts"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The minimum input line voltage allowed before the UPS
 | 
						|
            system transfers to battery backup."
 | 
						|
    ::= { upsConfig 9 }
 | 
						|
 | 
						|
upsConfigHighVoltageTransferPoint OBJECT-TYPE
 | 
						|
    SYNTAX     NonNegativeInteger
 | 
						|
    UNITS      "RMS Volts"
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The maximum line voltage allowed before the UPS
 | 
						|
            system transfers to battery backup."
 | 
						|
    ::= { upsConfig 10 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- notifications, i.e., traps
 | 
						|
--
 | 
						|
upsTraps              OBJECT IDENTIFIER ::= { upsMIB 2 }
 | 
						|
 | 
						|
-- This section defines the well-known notifications sent by
 | 
						|
-- UPS agents.
 | 
						|
-- Care must be taken to insure that no particular notification
 | 
						|
-- is sent to a single receiving entity more often than once
 | 
						|
-- every five seconds.
 | 
						|
 | 
						|
upsTrapOnBattery NOTIFICATION-TYPE
 | 
						|
    OBJECTS { upsEstimatedMinutesRemaining, upsSecondsOnBattery,
 | 
						|
              upsConfigLowBattTime }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The UPS is operating on battery power.  This trap is
 | 
						|
            persistent and is resent at one minute intervals until
 | 
						|
            the UPS either turns off or is no longer running on
 | 
						|
            battery."
 | 
						|
  ::= { upsTraps 1 }
 | 
						|
 | 
						|
upsTrapTestCompleted NOTIFICATION-TYPE
 | 
						|
    OBJECTS { upsTestId, upsTestSpinLock,
 | 
						|
              upsTestResultsSummary, upsTestResultsDetail,
 | 
						|
              upsTestStartTime, upsTestElapsedTime }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "This trap is sent upon completion of a UPS diagnostic
 | 
						|
            test."
 | 
						|
  ::= { upsTraps 2 }
 | 
						|
 | 
						|
upsTrapAlarmEntryAdded NOTIFICATION-TYPE
 | 
						|
    OBJECTS { upsAlarmId, upsAlarmDescr }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "This trap is sent each time an alarm is inserted into
 | 
						|
            to the alarm table.  It is sent on the insertion of
 | 
						|
            all alarms except for upsAlarmOnBattery and
 | 
						|
            upsAlarmTestInProgress."
 | 
						|
  ::= { upsTraps 3 }
 | 
						|
 | 
						|
upsTrapAlarmEntryRemoved NOTIFICATION-TYPE
 | 
						|
    OBJECTS { upsAlarmId, upsAlarmDescr }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "This trap is sent each time an alarm is removed from
 | 
						|
            the alarm table.  It is sent on the removal of all
 | 
						|
            alarms except for upsAlarmTestInProgress."
 | 
						|
  ::= { upsTraps 4 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- conformance information
 | 
						|
--
 | 
						|
upsConformance        OBJECT IDENTIFIER ::= { upsMIB 3 }
 | 
						|
 | 
						|
upsCompliances        OBJECT IDENTIFIER ::= { upsConformance 1 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- compliance statements
 | 
						|
--
 | 
						|
 | 
						|
upsSubsetCompliance MODULE-COMPLIANCE
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
 | 
						|
            "The compliance statement for UPSs that only support
 | 
						|
            the two-contact communication protocol."
 | 
						|
    MODULE -- this module
 | 
						|
        MANDATORY-GROUPS  { upsSubsetIdentGroup,
 | 
						|
                  upsSubsetBatteryGroup, upsSubsetInputGroup,
 | 
						|
                  upsSubsetOutputGroup, upsSubsetAlarmGroup,
 | 
						|
                  upsSubsetControlGroup, upsSubsetConfigGroup }
 | 
						|
 | 
						|
    OBJECT     upsBatteryStatus
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        batteryNormal(2),
 | 
						|
        batteryLow(3)
 | 
						|
    }
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of the values unknown(1) and
 | 
						|
            batteryDepleted(4) is not required."
 | 
						|
 | 
						|
    OBJECT     upsAlarmDescr
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of all `well known' alarm types is not
 | 
						|
            required.  The well known alarm types which must be
 | 
						|
            supported are: upsAlarmOnBattery, upsAlarmLowBattery,
 | 
						|
            upsAlarmInputBad, upsAlarmUpsOutputOff,
 | 
						|
            upsAlarmUpsSystemOff, and upsAlarmTestInProgress."
 | 
						|
 | 
						|
    OBJECT     upsOutputSource
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        normal(2),
 | 
						|
        battery(4)
 | 
						|
    }
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of the values other(1), none(2), bypass(4),
 | 
						|
            booster(6) and reducer(7) is not required."
 | 
						|
 | 
						|
    OBJECT     upsShutdownType
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required, i.e., compliant
 | 
						|
            systems need not support more than one shutdown type."
 | 
						|
 | 
						|
    OBJECT     upsAutoRestart
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required, i.e., compliant
 | 
						|
            systems need not support more than one restart type."
 | 
						|
 | 
						|
    OBJECT     upsConfigInputVoltage
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigInputFreq
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigOutputVoltage
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigOutputFreq
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
    ::= { upsCompliances 1 }
 | 
						|
 | 
						|
upsBasicCompliance MODULE-COMPLIANCE
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
 | 
						|
            "The compliance statement for UPSs that support
 | 
						|
            full-featured functions, such as control."
 | 
						|
    MODULE -- this module
 | 
						|
        MANDATORY-GROUPS { upsBasicIdentGroup,
 | 
						|
                  upsBasicBatteryGroup, upsBasicInputGroup,
 | 
						|
                  upsBasicOutputGroup, upsBasicAlarmGroup,
 | 
						|
                  upsBasicTestGroup, upsBasicControlGroup,
 | 
						|
                  upsBasicConfigGroup }
 | 
						|
 | 
						|
 | 
						|
    OBJECT     upsAlarmDescr
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of all `well known' alarm types is not
 | 
						|
            required.  The well known alarm types which must be
 | 
						|
            supported are: upsAlarmOnBattery, upsAlarmLowBattery,
 | 
						|
            upsAlarmDepletedBattery, upsAlarmTempBad,
 | 
						|
            upsAlarmInputBad, upsAlarmOutputOverload,
 | 
						|
            upsAlarmOnBypass, upsAlarmBypassBad,
 | 
						|
            upsAlarmOutputOffAsRequested,
 | 
						|
            upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
 | 
						|
            upsAlarmUpsSystemOff, upsAlarmGeneralFault,
 | 
						|
            upsAlarmDiagnosticTestFailed,
 | 
						|
            upsAlarmCommunicationsLost, upsAlarmShutdownPending,
 | 
						|
            and upsAlarmTestInProgress."
 | 
						|
 | 
						|
    OBJECT     upsTestId
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of all `well known' test types is not
 | 
						|
            required.  If no tests are supported, then the only
 | 
						|
            well known test type which must be supported is
 | 
						|
            upsTestNoTestsInitiated."
 | 
						|
 | 
						|
    OBJECT     upsOutputSource
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        normal(2),
 | 
						|
        battery(4)
 | 
						|
    }
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of the values other(1), none(2), bypass(4),
 | 
						|
            booster(6) and reducer(7) is not required."
 | 
						|
 | 
						|
        GROUP upsBasicBypassGroup
 | 
						|
        DESCRIPTION
 | 
						|
            "The upsBasicBypassGroup is only required for UPSs
 | 
						|
            that have a Bypass present."
 | 
						|
    OBJECT     upsShutdownType
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required, i.e., compliant
 | 
						|
            systems need not support more than one shutdown type."
 | 
						|
 | 
						|
    OBJECT     upsAutoRestart
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required, i.e., compliant
 | 
						|
            systems need not support more than one restart type."
 | 
						|
 | 
						|
    OBJECT     upsConfigInputVoltage
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigInputFreq
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigOutputVoltage
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigOutputFreq
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigLowBattTime
 | 
						|
    DESCRIPTION
 | 
						|
            "Implementation of all possible values may be onerous
 | 
						|
            for some systems.  Consequently, not all possible
 | 
						|
            values must be supported.  However, at least two
 | 
						|
            different manufacturer-selected values must be
 | 
						|
            supported."
 | 
						|
 | 
						|
    ::= { upsCompliances 2 }
 | 
						|
 | 
						|
upsFullCompliance MODULE-COMPLIANCE
 | 
						|
    STATUS     current
 | 
						|
    DESCRIPTION
 | 
						|
            "The compliance statement for UPSs that support
 | 
						|
            advanced full-featured functions."
 | 
						|
    MODULE -- this module
 | 
						|
        MANDATORY-GROUPS { upsFullIdentGroup, upsFullBatteryGroup,
 | 
						|
                  upsFullInputGroup, upsFullOutputGroup,
 | 
						|
                  upsFullAlarmGroup, upsFullTestGroup,
 | 
						|
                  upsFullControlGroup, upsFullConfigGroup }
 | 
						|
 | 
						|
    OBJECT     upsAlarmDescr
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of all `well known' alarm types is not
 | 
						|
            required.  The well known alarm types which must be
 | 
						|
            supported are: upsAlarmBatteryBad, upsAlarmOnBattery,
 | 
						|
            upsAlarmLowBattery, upsAlarmDepletedBattery,
 | 
						|
            upsAlarmTempBad, upsAlarmInputBad, upsAlarmOnBypass,
 | 
						|
            upsAlarmBypassBad, upsAlarmOutputOffAsRequested,
 | 
						|
            upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
 | 
						|
            upsAlarmUpsSystemOff, upsAlarmGeneralFault,
 | 
						|
            upsAlarmDiagnosticTestFailed,
 | 
						|
            upsAlarmCommunicationsLost, upsAlarmShutdownPending,
 | 
						|
            and upsAlarmTestInProgress."
 | 
						|
 | 
						|
    OBJECT     upsTestId
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of all `well known' test types is not
 | 
						|
            required.  The well known test types which must be
 | 
						|
            supported are: upsTestNoTestsInitiated,
 | 
						|
            upsTestGeneralSystemsTest, and
 | 
						|
            upsTestQuickBatteryTest."
 | 
						|
 | 
						|
    OBJECT     upsOutputSource
 | 
						|
    SYNTAX     INTEGER {
 | 
						|
        normal(2),
 | 
						|
        battery(4)
 | 
						|
    }
 | 
						|
    DESCRIPTION
 | 
						|
            "Support of the values other(1), none(2), bypass(4),
 | 
						|
            booster(6) and reducer(7) is not required."
 | 
						|
 | 
						|
        GROUP upsFullBypassGroup
 | 
						|
        DESCRIPTION
 | 
						|
            "The upsFullBypassGroup is only required for UPSs that
 | 
						|
            have a Bypass present."
 | 
						|
 | 
						|
    OBJECT     upsShutdownType
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required, i.e., compliant
 | 
						|
            systems need not support more than one shutdown type."
 | 
						|
 | 
						|
    OBJECT     upsAutoRestart
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required, i.e., compliant
 | 
						|
            systems need not support more than one restart type."
 | 
						|
 | 
						|
    OBJECT     upsConfigInputVoltage
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigInputFreq
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigOutputVoltage
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigOutputFreq
 | 
						|
    MIN-ACCESS read-only
 | 
						|
    DESCRIPTION
 | 
						|
            "Read-write access is not required."
 | 
						|
 | 
						|
    OBJECT     upsConfigLowBattTime
 | 
						|
    DESCRIPTION
 | 
						|
            "Implementation of all possible values may be onerous
 | 
						|
            for some systems.  Consequently, not all possible
 | 
						|
            values must be supported.  However, at least two
 | 
						|
            different manufacturer-selected values must be
 | 
						|
            supported."
 | 
						|
 | 
						|
    ::= { upsCompliances 3 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
-- units of conformance
 | 
						|
--
 | 
						|
 | 
						|
-- summary at a glance:
 | 
						|
 | 
						|
--                                      subset  basic   adv
 | 
						|
--upsIdentManufacturer                  x       x       x
 | 
						|
--upsIdentModel                         x       x       x
 | 
						|
 | 
						|
--upsIdentUPSSoftwareVersion                    x       x
 | 
						|
--upsIdentAgentSoftwareVersion          x       x       x
 | 
						|
--upsIdentName                          x       x       x
 | 
						|
--upsIdentAttachedDevices               x               x
 | 
						|
--
 | 
						|
--upsBatteryStatus                      x       x       x  notes
 | 
						|
--upsSecondsOnBattery                   x       x       x
 | 
						|
--upsEstimatedMinutesRemaining                          x
 | 
						|
--upsEstimatedChargeRemaining                           x
 | 
						|
--upsBatteryVoltage
 | 
						|
--upsBatteryCurrent
 | 
						|
--upsBatteryTemperature
 | 
						|
--
 | 
						|
--upsInputLineBads                      x       x       x
 | 
						|
--upsInputNumLines                              x       x
 | 
						|
--upsInputFrequency                             x       x
 | 
						|
--upsInputVoltage                               x       x
 | 
						|
--upsInputCurrent
 | 
						|
--upsInputTruePower
 | 
						|
--
 | 
						|
--upsOutputSource                       x       x       x  notes
 | 
						|
--upsOutputFrequency                            x       x
 | 
						|
--upsOutputNumLines                             x       x
 | 
						|
--upsOutputVoltage                              x       x
 | 
						|
--upsOutputCurrent                                      x
 | 
						|
--upsOutputPower                                        x
 | 
						|
--upsOutputPercentLoad                                  x
 | 
						|
--
 | 
						|
--
 | 
						|
--upsBypassFrequency                            x       x  notes
 | 
						|
--upsBypassNumLines                             x       x
 | 
						|
--upsBypassVoltage                              x       x
 | 
						|
--upsBypassCurrent
 | 
						|
--upsBypassPower
 | 
						|
--
 | 
						|
--
 | 
						|
--upsAlarmsPresent                      x       x       x
 | 
						|
--upsAlarmDescr                         x       x       x  notes
 | 
						|
--upsAlarmTime                          x       x       x
 | 
						|
--
 | 
						|
--upsTestId                                     x       x  notes
 | 
						|
--upsTestSpinLock                               x       x
 | 
						|
--upsTestResultsSummary                         x       x
 | 
						|
--upsTestResultsDetail                          x       x
 | 
						|
--upsTestStartTime                              x       x
 | 
						|
--upsTestElapsedTime                            x       x
 | 
						|
--
 | 
						|
--upsShutdownType                       x       x       x  notes
 | 
						|
 | 
						|
--upsShutdownAfterDelay                 x       x       x
 | 
						|
--upsStartupAfterDelay                          x       x
 | 
						|
--upsRebootWithDuration                         x       x
 | 
						|
--upsAutoRestart                        x       x       x  notes
 | 
						|
--
 | 
						|
--upsConfigInputVoltage                 x       x       x  notes
 | 
						|
--upsConfigInputFreq                    x       x       x  notes
 | 
						|
--upsConfigOutputVoltage                x       x       x  notes
 | 
						|
--upsConfigOutputFreq                   x       x       x  notes
 | 
						|
--upsConfigOutputVA                     x       x       x
 | 
						|
--upsConfigOutputPower                  x       x       x
 | 
						|
--upsConfigLowBattTime                          x       x  notes
 | 
						|
--upsConfigAudibleStatus                        x       x
 | 
						|
--upsConfigLowVoltageTransferPoint
 | 
						|
--upsConfigHighVoltageTransferPoint
 | 
						|
 | 
						|
 | 
						|
-- units of conformance
 | 
						|
upsGroups             OBJECT IDENTIFIER ::= { upsConformance 2 }
 | 
						|
 | 
						|
upsSubsetGroups       OBJECT IDENTIFIER ::= { upsGroups 1 }
 | 
						|
 | 
						|
upsSubsetIdentGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsIdentManufacturer, upsIdentModel,
 | 
						|
              upsIdentAgentSoftwareVersion, upsIdentName,
 | 
						|
              upsIdentAttachedDevices }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsSubsetIdentGroup defines objects which are
 | 
						|
            common across all UPSs which meet subset compliance.
 | 
						|
            Most devices which conform to the upsSubsetIdentGroup
 | 
						|
            will provide access to these objects via a proxy
 | 
						|
            agent.  If the proxy agent is compatible with multiple
 | 
						|
            UPS types, configuration of the proxy agent will
 | 
						|
            require specifying some of these values, either
 | 
						|
            individually, or as a group (perhaps through a table
 | 
						|
            lookup mechanism based on the UPS model number)."
 | 
						|
    ::= { upsSubsetGroups 1 }
 | 
						|
 | 
						|
upsSubsetBatteryGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsSubsetBatteryGroup defines the objects that
 | 
						|
            are common to battery groups of two-contact UPSs."
 | 
						|
    ::= { upsSubsetGroups 2 }
 | 
						|
 | 
						|
upsSubsetInputGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsInputLineBads }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsSubsetInputGroup defines the objects that are
 | 
						|
            common to the Input groups of two-contact UPSs."
 | 
						|
    ::= { upsSubsetGroups 3 }
 | 
						|
 | 
						|
upsSubsetOutputGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsOutputSource }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsSubsetOutputGroup defines the objects that are
 | 
						|
            common to the Output groups of two-contact UPSs."
 | 
						|
    ::= { upsSubsetGroups 4 }
 | 
						|
 | 
						|
 | 
						|
-- { upsSubsetGroups 5 } is reserved for
 | 
						|
-- future use (upsSubsetBypassGroup)
 | 
						|
 | 
						|
upsSubsetAlarmGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsSubsetAlarmGroup defines the objects that are
 | 
						|
            common to the Alarm groups of two-contact UPSs."
 | 
						|
    ::= { upsSubsetGroups 6 }
 | 
						|
 | 
						|
-- { upsSubsetGroups 7 } is reserved for
 | 
						|
-- future use (upsSubsetTestGroup)
 | 
						|
 | 
						|
upsSubsetControlGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsShutdownType, upsShutdownAfterDelay,
 | 
						|
                  upsAutoRestart }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsSubsetControlGroup defines the objects that
 | 
						|
            are common to the Control groups of two-contact UPSs."
 | 
						|
    ::= { upsSubsetGroups 8 }
 | 
						|
 | 
						|
upsSubsetConfigGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
 | 
						|
              upsConfigOutputVoltage, upsConfigOutputFreq,
 | 
						|
              upsConfigOutputVA, upsConfigOutputPower }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsSubsetConfigGroup defines the objects that are
 | 
						|
            common to the Config groups of two-contact UPSs."
 | 
						|
    ::= { upsSubsetGroups 9 }
 | 
						|
upsBasicGroups        OBJECT IDENTIFIER ::= { upsGroups 2 }
 | 
						|
 | 
						|
upsBasicIdentGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsIdentManufacturer, upsIdentModel,
 | 
						|
              upsIdentUPSSoftwareVersion,
 | 
						|
              upsIdentAgentSoftwareVersion, upsIdentName }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicIdentGroup defines objects which are
 | 
						|
            common to the Ident group of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 1 }
 | 
						|
 | 
						|
upsBasicBatteryGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicBatteryGroup defines the objects that are
 | 
						|
            common to the battery groups of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 2 }
 | 
						|
 | 
						|
upsBasicInputGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsInputLineBads, upsInputNumLines,
 | 
						|
              upsInputFrequency, upsInputVoltage }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicInputGroup defines the objects that are
 | 
						|
            common to the Input groups of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 3 }
 | 
						|
 | 
						|
upsBasicOutputGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsOutputSource, upsOutputFrequency,
 | 
						|
              upsOutputNumLines, upsOutputVoltage }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicOutputGroup defines the objects that are
 | 
						|
            common to the Output groups of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 4 }
 | 
						|
 | 
						|
upsBasicBypassGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsBypassFrequency, upsBypassNumLines,
 | 
						|
              upsBypassVoltage }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicBypassGroup defines the objects that are
 | 
						|
            common to the Bypass groups of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 5 }
 | 
						|
 | 
						|
upsBasicAlarmGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
 | 
						|
            "The upsBasicAlarmGroup defines the objects that are
 | 
						|
            common to the Alarm  groups of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 6 }
 | 
						|
 | 
						|
upsBasicTestGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsTestId, upsTestSpinLock,
 | 
						|
              upsTestResultsSummary, upsTestResultsDetail,
 | 
						|
              upsTestStartTime, upsTestElapsedTime }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicTestGroup defines the objects that are
 | 
						|
            common to the Test groups of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 7 }
 | 
						|
 | 
						|
upsBasicControlGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsShutdownType, upsShutdownAfterDelay,
 | 
						|
              upsStartupAfterDelay, upsRebootWithDuration,
 | 
						|
              upsAutoRestart }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicControlGroup defines the objects that are
 | 
						|
            common to the Control groups of compliant UPSs which
 | 
						|
            support basic functions."
 | 
						|
    ::= { upsBasicGroups 8 }
 | 
						|
 | 
						|
upsBasicConfigGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
 | 
						|
              upsConfigOutputVoltage, upsConfigOutputFreq,
 | 
						|
              upsConfigOutputVA, upsConfigOutputPower,
 | 
						|
              upsConfigLowBattTime, upsConfigAudibleStatus }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsBasicConfigGroup defines the objects that are
 | 
						|
            common to the Config groups of UPSs which support
 | 
						|
            basic functions."
 | 
						|
    ::= { upsBasicGroups 9 }
 | 
						|
upsFullGroups         OBJECT IDENTIFIER ::= { upsGroups 3 }
 | 
						|
 | 
						|
upsFullIdentGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsIdentManufacturer, upsIdentModel,
 | 
						|
              upsIdentUPSSoftwareVersion,
 | 
						|
              upsIdentAgentSoftwareVersion, upsIdentName,
 | 
						|
              upsIdentAttachedDevices }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsFullIdentGroup defines objects which are
 | 
						|
            common to the Ident group of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 1 }
 | 
						|
 | 
						|
upsFullBatteryGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsBatteryStatus, upsSecondsOnBattery,
 | 
						|
              upsEstimatedMinutesRemaining,
 | 
						|
              upsEstimatedChargeRemaining }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsFullBatteryGroup defines the objects that are
 | 
						|
            common to the battery groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 2 }
 | 
						|
 | 
						|
upsFullInputGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsInputLineBads, upsInputNumLines,
 | 
						|
              upsInputFrequency, upsInputVoltage }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsFullInputGroup defines the objects that are
 | 
						|
            common to the Input groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 3 }
 | 
						|
 | 
						|
upsFullOutputGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsOutputSource, upsOutputFrequency,
 | 
						|
              upsOutputNumLines, upsOutputVoltage,
 | 
						|
              upsOutputCurrent, upsOutputPower,
 | 
						|
              upsOutputPercentLoad }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsFullOutputGroup defines the objects that are
 | 
						|
            common to the Output groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 4 }
 | 
						|
 | 
						|
upsFullBypassGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsBypassFrequency, upsBypassNumLines,
 | 
						|
              upsBypassVoltage }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsFullBypassGroup defines the objects that are
 | 
						|
            common to the Bypass groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 5 }
 | 
						|
 | 
						|
upsFullAlarmGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
 | 
						|
            "The upsFullAlarmGroup defines the objects that are
 | 
						|
            common to the Alarm  groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 6 }
 | 
						|
 | 
						|
upsFullTestGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsTestId, upsTestSpinLock,
 | 
						|
              upsTestResultsSummary, upsTestResultsDetail,
 | 
						|
              upsTestStartTime, upsTestElapsedTime }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsFullTestGroup defines the objects that are
 | 
						|
            common to the Test groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 7 }
 | 
						|
 | 
						|
upsFullControlGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsShutdownType, upsShutdownAfterDelay,
 | 
						|
              upsStartupAfterDelay, upsRebootWithDuration,
 | 
						|
              upsAutoRestart }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
"The upsFullControlGroup defines the objects that are
 | 
						|
common to the Control groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 8 }
 | 
						|
 | 
						|
upsFullConfigGroup OBJECT-GROUP
 | 
						|
    OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
 | 
						|
              upsConfigOutputVoltage, upsConfigOutputFreq,
 | 
						|
              upsConfigOutputVA, upsConfigOutputPower,
 | 
						|
              upsConfigLowBattTime, upsConfigAudibleStatus }
 | 
						|
    STATUS  current
 | 
						|
    DESCRIPTION
 | 
						|
            "The upsFullConfigGroup defines the objects that are
 | 
						|
            common to the Config groups of fully compliant UPSs."
 | 
						|
    ::= { upsFullGroups 9 }
 | 
						|
 | 
						|
END
 |