XUPS-MIB DEFINITIONS ::= BEGIN
 | 
						||
 | 
						||
-- Revised February 25, 1993
 | 
						||
-- Revised June 21, 1993
 | 
						||
-- Revised (Variable types of ) August 5, 1993
 | 
						||
-- Revised August 16, 1993 - added units of measure
 | 
						||
-- Added Event History to Alarm Group and get/set time/date.
 | 
						||
-- Cleanup for final release.  9/3/93
 | 
						||
 | 
						||
-- Release Version 0.91 9/17/93
 | 
						||
-- Release Version 1.00 11/16/93
 | 
						||
 | 
						||
-- Changes for Release Version 2.00  9/7/94
 | 
						||
-- 1) Renamed UPS-MIB to XUPS-MIB and all names from upsVariable
 | 
						||
--      to xupsVariable to avoid conflicts with RFC 1628 Standard UPS MIB names
 | 
						||
-- 2) Renamed all traps from upsName to xupstName to avoid conflicts with
 | 
						||
--      similar alarm names
 | 
						||
-- 3) Added well known alarms and traps:
 | 
						||
--      BreakerOpen, AlarmEntryAdded, AlarmEntryRemoved
 | 
						||
-- 4) Deprecated xupsControlOutputOnTrapDelay
 | 
						||
-- 5) Added xupsTrapControl group
 | 
						||
-- 6) enumerated the value startTest for xupsTestBattery
 | 
						||
-- 7) Defined oid values to use for sysObjectId
 | 
						||
 | 
						||
-- Changes for Release Version 2.10  11/1/94
 | 
						||
-- 1) Corrected type of xupsAlarms, xupsAlarmNumEvents (Gauge)
 | 
						||
-- 2) Defined three trap sources, which differ in their descriptions
 | 
						||
--      of trap variables (none, Defined, defined plus Port N Interface vars)
 | 
						||
-- 3) Clarified AlarmEvent order and numbering
 | 
						||
 | 
						||
-- Changes for Release Version 2.11  3/30/95
 | 
						||
-- 1) Removed references to version 2.00 MIB files
 | 
						||
-- 2) Added range declarations for appropriate objects
 | 
						||
-- 3) Added Object IDs for new products
 | 
						||
 | 
						||
-- Changes for Release Version 2.20  8/29/96
 | 
						||
-- 1) Corrected upper Integer range from 2147483648 to 2147483647
 | 
						||
-- 2) Added xupsEnvironment group and its objects and alarm xupsAmbientTempBad
 | 
						||
-- 3) Added xupsBatteryAbmStatus to monitor Advanced Battery Management status
 | 
						||
-- 4) Added well-known alarms from RFC 1628 which weren't previously supported:
 | 
						||
--    xupsAlarmBatteryBad, xupsOutputOffAsRequested, xupsDiagnosticTestFailed,
 | 
						||
--    xupsCommunicationsLost, xupsUpsShutdownPending, xupsAlarmTestInProgress
 | 
						||
-- 5) Added Defined and PortN (but not Basic) type traps for above alarms
 | 
						||
-- 6) Added xupsControlToBypassDelay to allow Go To Bypass command.
 | 
						||
 | 
						||
-- Changes for Release Version 2.21  5/19/99
 | 
						||
-- Renaming from Exide Electronics to Powerware Corporation
 | 
						||
 | 
						||
-- Changes for Release Version 3.00 3-Apr-02 Connectivity Systems Group,
 | 
						||
-- Power Systems Division, Invensys
 | 
						||
-- 1) Rolled in Receptacle Control extensions from separate file
 | 
						||
-- 2) Added Topology group objects
 | 
						||
-- 3) Added new var xupsOutputSource, which extends upsOutputSource
 | 
						||
-- 4) Added new var xupsAlarmEventMsg to replace the other deprecated xAEEntry vars
 | 
						||
 | 
						||
-- Changes for Release Version 3.01 15-Aug-02 Connectivity Systems Group,
 | 
						||
-- Powerware, Power Systems Division, Invensys
 | 
						||
-- 1) Added new vars xupsConfigLow- and -HighOutputVoltageLimit.
 | 
						||
 | 
						||
-- Changes for Release Version 3.02 06-Oct-02 Connectivity Systems Group,
 | 
						||
-- Powerware, Power Systems Division, Invensys
 | 
						||
-- To support the ConnectUPS Web/SNMP card's ability to monitor an external contact,
 | 
						||
-- the following traps were added:
 | 
						||
-- 1) Added new trap xupstdContactAlarmActive in xupsTrapDefined
 | 
						||
-- 2) Added new trap xupstdContactAlarmInactive in xupsTrapDefined
 | 
						||
--
 | 
						||
-- These are added to support the ConnectUPS Web/SNMP card's ability to monitor
 | 
						||
-- a single contact closure (firmware and custom cable required)
 | 
						||
 | 
						||
-- Changes for Release Version 3.03 05-Feb-03 Connectivity Systems Group,
 | 
						||
-- Powerware, Invensys Energy Systems
 | 
						||
-- 1) To support the ability to monitor additional external contacts,
 | 
						||
-- the var lists of the xupstdContactActiveNotice and
 | 
						||
--      xupstdContactInactiveNotice traps were modified.
 | 
						||
-- 2) Added new var xupsInputSource
 | 
						||
-- 3) Added new vars xupsLoadShedSecsWithRestart and xupsRecepShedSecsWithRestart to
 | 
						||
--      provide guaranteed correct load shedding behavior to the management software.
 | 
						||
-- 4) Added vars to the Environmental group: xupsEnvAmbientHumidity,
 | 
						||
--      xupsEnvRemoteTemp, and xupsEnvRemoteHumidity.
 | 
						||
-- 5) Added xupsEnvNumContacts and the Environmental Contact Sensing Table,
 | 
						||
--      xupsContactSenseTable.
 | 
						||
-- 6) Updated Tech Support telephone numbers listed below.
 | 
						||
 | 
						||
-- Changes for Release Version 3.04 30-Apr-03 Connectivity Systems Group,
 | 
						||
-- Powerware, Invensys Energy Systems
 | 
						||
-- 1) Added new Well-Known Alarm and traps for xupsLossOfRedundancy,
 | 
						||
--    xupsAlarmTempBad, xupsAlarmChargerFailed, xupsAlarmFanFailure,
 | 
						||
--    xupsAlarmFuseFailure, xupsPowerSwitchBad, xupsModuleFailure,
 | 
						||
--    xupsOnAlternatePowerSource, xupsAltPowerNotAvailable, xupsNoticeCondition
 | 
						||
-- 2) Added new vars for Min/Max limits for Remote Temp & Humidity
 | 
						||
-- 3) Added new W-K Alarms and traps for Min/Max limits for Remote Temp & Humidity
 | 
						||
 | 
						||
--
 | 
						||
-- Customer Support: contact Tech Support at
 | 
						||
--
 | 
						||
-- Single-Phase Products: 800-356-5737 (US) or 608-565-2100
 | 
						||
--
 | 
						||
-- 3-Phase Products: 800-843-9433 (US) or 919-871-1800
 | 
						||
--
 | 
						||
 | 
						||
IMPORTS
 | 
						||
   enterprises, IpAddress, TimeTicks, Gauge, Counter
 | 
						||
FROM RFC1155-SMI
 | 
						||
   DisplayString, ifIndex, ifDescr
 | 
						||
FROM RFC1213-MIB
 | 
						||
   OBJECT-TYPE
 | 
						||
FROM RFC-1212
 | 
						||
   TRAP-TYPE
 | 
						||
FROM RFC-1215;
 | 
						||
 | 
						||
 | 
						||
-- Note that .534. was originally assigned to Exide Electronics
 | 
						||
--      before it was renamed to Invensys Powerware.
 | 
						||
 | 
						||
powerware       OBJECT IDENTIFIER       ::= {enterprises 534}
 | 
						||
xups            OBJECT IDENTIFIER       ::= {powerware 1}
 | 
						||
 | 
						||
xupsIdent        OBJECT IDENTIFIER       ::= { xups 1 }
 | 
						||
xupsBattery      OBJECT IDENTIFIER       ::= { xups 2 }
 | 
						||
xupsInput        OBJECT IDENTIFIER       ::= { xups 3 }
 | 
						||
xupsOutput       OBJECT IDENTIFIER       ::= { xups 4 }
 | 
						||
xupsBypass       OBJECT IDENTIFIER       ::= { xups 5 }
 | 
						||
xupsEnvironment  OBJECT IDENTIFIER       ::= { xups 6 }
 | 
						||
xupsAlarm        OBJECT IDENTIFIER       ::= { xups 7 }
 | 
						||
xupsTest         OBJECT IDENTIFIER       ::= { xups 8 }
 | 
						||
xupsControl      OBJECT IDENTIFIER       ::= { xups 9 }
 | 
						||
xupsConfig       OBJECT IDENTIFIER       ::= { xups 10 }
 | 
						||
xupsTrapControl  OBJECT IDENTIFIER       ::= { xups 11 }
 | 
						||
xupsRecep        OBJECT IDENTIFIER       ::= { xups 12 }
 | 
						||
xupsTopology     OBJECT IDENTIFIER       ::= { xups 13 }
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- The following Object Identifiers are used to distinguish Powerware's
 | 
						||
-- SNMP agents:
 | 
						||
xupsObjectId     OBJECT IDENTIFIER       ::= {powerware 2}
 | 
						||
 | 
						||
powerwareEthernetSnmpAdapter     OBJECT IDENTIFIER   ::= {xupsObjectId 1}
 | 
						||
powerwareNetworkSnmpAdapterEther OBJECT IDENTIFIER   ::= {xupsObjectId 2}
 | 
						||
powerwareNetworkSnmpAdapterToken OBJECT IDENTIFIER   ::= {xupsObjectId 3}
 | 
						||
onlinetDaemon                    OBJECT IDENTIFIER   ::= {xupsObjectId 4}
 | 
						||
connectUPSAdapterEthernet        OBJECT IDENTIFIER   ::= {xupsObjectId 5}
 | 
						||
powerwareNetworkDigitalIOEther   OBJECT IDENTIFIER   ::= {xupsObjectId 6}
 | 
						||
connectUPSAdapterTokenRing       OBJECT IDENTIFIER   ::= {xupsObjectId 7}
 | 
						||
simpleSnmpAdapter                OBJECT IDENTIFIER   ::= {xupsObjectId 8}
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsIdent group:
 | 
						||
--
 | 
						||
xupsIdentManufacturer OBJECT-TYPE
 | 
						||
   SYNTAX DisplayString (SIZE (0..31))
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS Manufacturer Name (e.g. Powerware Corporation)."
 | 
						||
   ::= { xupsIdent 1}
 | 
						||
 | 
						||
xupsIdentModel OBJECT-TYPE
 | 
						||
   SYNTAX DisplayString (SIZE (0..63))
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS Model (e.g. Powerware Plus Model 18)."
 | 
						||
   ::= {xupsIdent 2}
 | 
						||
 | 
						||
xupsIdentSoftwareVersion OBJECT-TYPE
 | 
						||
   SYNTAX DisplayString (SIZE (0..63))
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The firmware revision level(s) of the UPS microcontroller(s)."
 | 
						||
   ::= {xupsIdent 3}
 | 
						||
 | 
						||
xupsIdentOemCode OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..255)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"A binary code indicating who the UPS was manufactured or labeled for.
 | 
						||
0 or 255 indicates Powerware itself."
 | 
						||
   ::= {xupsIdent 4}
 | 
						||
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsBattery group:
 | 
						||
--
 | 
						||
xupsBatTimeRemaining OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS seconds
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Battery run time in seconds before UPS turns off due
 | 
						||
to low battery."
 | 
						||
   ::= { xupsBattery 1}
 | 
						||
 | 
						||
xupsBatVoltage OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS Volts DC
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Battery voltage as reported by the UPS meters."
 | 
						||
   ::= {xupsBattery 2}
 | 
						||
 | 
						||
xupsBatCurrent OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (-2147483648..2147483647)   -- UNITS Amp DC
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Battery Current as reported by the UPS metering.
 | 
						||
Current is positive when discharging, negative
 | 
						||
when recharging the battery."
 | 
						||
   ::= {xupsBattery 3}
 | 
						||
 | 
						||
xupsBatCapacity OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..100)    -- UNITS percent
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Battery percent charge."
 | 
						||
   ::= { xupsBattery 4}
 | 
						||
 | 
						||
xupsBatteryAbmStatus OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER {
 | 
						||
   batteryCharging(1),
 | 
						||
   batteryDischarging(2),
 | 
						||
   batteryFloating(3),
 | 
						||
   batteryResting(4),
 | 
						||
   unknown(5)
 | 
						||
}
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Gives the status of the Advanced Battery Management;
 | 
						||
batteryFloating(3) status means that the charger is temporarily
 | 
						||
charging the battery to its float voltage; batteryResting(4) is the
 | 
						||
state when the battery is fully charged and none of the other actions
 | 
						||
(charging/discharging/floating) is being done."
 | 
						||
   ::= { xupsBattery 5}
 | 
						||
 | 
						||
--
 | 
						||
-- xupsInput group:
 | 
						||
--
 | 
						||
xupsInputFrequency OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The utility line frequency in tenths of Hz."
 | 
						||
   ::= {xupsInput 1}
 | 
						||
 | 
						||
xupsInputLineBads OBJECT-TYPE
 | 
						||
   SYNTAX Counter
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The number of times the Input was out of tolerance
 | 
						||
in voltage or frequency."
 | 
						||
   ::= {xupsInput 2}
 | 
						||
 | 
						||
xupsInputNumPhases OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..6)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   ::= {xupsInput 3}
 | 
						||
 | 
						||
xupsInputTable OBJECT-TYPE
 | 
						||
   SYNTAX SEQUENCE OF XupsInputEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION "The Aggregate Object with number of entries equal to
 | 
						||
   NumPhases and including the xupsInput group."
 | 
						||
   ::= {xupsInput 4}
 | 
						||
 | 
						||
xupsInputEntry OBJECT-TYPE
 | 
						||
   SYNTAX XupsInputEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION "The input table entry containing the current,
 | 
						||
   voltage, etc."
 | 
						||
   INDEX { xupsInputPhase }
 | 
						||
   ::= { xupsInputTable 1 }
 | 
						||
 | 
						||
XupsInputEntry ::= SEQUENCE {
 | 
						||
   xupsInputPhase
 | 
						||
INTEGER,
 | 
						||
   xupsInputVoltage
 | 
						||
INTEGER,
 | 
						||
   xupsInputCurrent
 | 
						||
INTEGER,
 | 
						||
   xupsInputWatts
 | 
						||
INTEGER
 | 
						||
   }
 | 
						||
 | 
						||
xupsInputPhase OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER  (0..6)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The number of the phase.  Serves as index for input table."
 | 
						||
   ::= {xupsInputEntry 1}
 | 
						||
 | 
						||
xupsInputVoltage OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER  (0..2147483647)  -- UNITS RMS Volts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured input voltage from the UPS meters in volts."
 | 
						||
   ::= {xupsInputEntry 2}
 | 
						||
 | 
						||
xupsInputCurrent OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Amp
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured input current from the UPS meters in amps."
 | 
						||
   ::= {xupsInputEntry 3}
 | 
						||
 | 
						||
xupsInputWatts OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS Watts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured input real power in watts."
 | 
						||
   ::= {xupsInputEntry 4}
 | 
						||
 | 
						||
xupsInputSource OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER {
 | 
						||
   other(1),
 | 
						||
   none(2),                 -- For example, Utility failure
 | 
						||
   primaryUtility(3), -- Normal utility feed to the UPS
 | 
						||
   bypassFeed(4),           -- Bypass utility, separate from primaryUtility
 | 
						||
   secondaryUtility(5),     -- Secondary utility feed (on a dual AC input UPS)
 | 
						||
   generator(6), -- Power provided by a generator
 | 
						||
   flywheel(7), -- Power provided by a flywheel (not necessarily AC)
 | 
						||
   fuelcell(8) -- Power provided by fuel cell(s) (not necessarily AC)
 | 
						||
   }
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "The present external source of input power.  The enumeration
 | 
						||
      none(2) indicates that there is no external source of
 | 
						||
      power, for example, the UPS is On Battery (an internal source).
 | 
						||
      The bypassFeed(4) can only be used when the Bypass source is known
 | 
						||
      to be a separate utility feed than the primaryUtility(3)."
 | 
						||
   ::= { xupsInput 5 }
 | 
						||
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsOutput group:
 | 
						||
--
 | 
						||
xupsOutputLoad OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..200)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS output load in percent of rated capacity."
 | 
						||
   ::= {xupsOutput 1}
 | 
						||
 | 
						||
xupsOutputFrequency OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured UPS output frequency in tenths of Hz."
 | 
						||
   ::= {xupsOutput 2}
 | 
						||
 | 
						||
xupsOutputNumPhases OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER  (0..6)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The number of metered output phases, serves as the table
 | 
						||
index."
 | 
						||
   ::= {xupsOutput 3}
 | 
						||
 | 
						||
xupsOutputTable OBJECT-TYPE
 | 
						||
   SYNTAX SEQUENCE OF XupsOutputEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The Aggregate Object with number of entries equal to NumPhases
 | 
						||
and including the xupsOutput group."
 | 
						||
   ::= {xupsOutput 4}
 | 
						||
 | 
						||
xupsOutputEntry OBJECT-TYPE
 | 
						||
   SYNTAX XupsOutputEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Output Table Entry containing voltage, current, etc."
 | 
						||
   INDEX { xupsOutputPhase }
 | 
						||
 | 
						||
   ::= {xupsOutputTable 1}
 | 
						||
 | 
						||
XupsOutputEntry ::= SEQUENCE {
 | 
						||
   xupsOutputPhase
 | 
						||
   INTEGER,
 | 
						||
   xupsOutputVoltage
 | 
						||
   INTEGER,
 | 
						||
   xupsOutputCurrent
 | 
						||
   INTEGER,
 | 
						||
   xupsOutputWatts
 | 
						||
   INTEGER
 | 
						||
   }
 | 
						||
 | 
						||
xupsOutputPhase OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..6)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The number {1..3} of the output phase."
 | 
						||
   ::= {xupsOutputEntry 1}
 | 
						||
 | 
						||
xupsOutputVoltage OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Volts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured output voltage from the UPS metering in volts."
 | 
						||
   ::= {xupsOutputEntry 2}
 | 
						||
 | 
						||
xupsOutputCurrent OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Amp
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured UPS output current in amps."
 | 
						||
   ::= {xupsOutputEntry 3}
 | 
						||
 | 
						||
xupsOutputWatts OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS Watts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured real output power in watts."
 | 
						||
   ::= {xupsOutputEntry 4}
 | 
						||
 | 
						||
xupsOutputSource OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER {
 | 
						||
   other(1),
 | 
						||
   none(2),
 | 
						||
   normal(3), -- normal, single UPS module output
 | 
						||
   bypass(4),
 | 
						||
   battery(5),
 | 
						||
   booster(6), -- Single or Double Boost, line-interactive UPSs only
 | 
						||
   reducer(7), -- Buck, line-interactive UPSs only
 | 
						||
   parallelCapacity(8), -- normal enhanced by Parallel for Capacity operation
 | 
						||
   parallelRedundant(9), -- normal enhanced by Redundant Parallel operation
 | 
						||
   highEfficiencyMode(10) -- normal enhanced by High Efficiency mode
 | 
						||
   }
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "The present source of output power.  The enumeration
 | 
						||
      none(2) indicates that there is no source of output
 | 
						||
      power (and therefore no output power), for example,
 | 
						||
      the system has opened the output breaker."
 | 
						||
   ::= { xupsOutput  5 }
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsBypass group:
 | 
						||
--
 | 
						||
xupsBypassFrequency OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The bypass frequency in tenths of Hz."
 | 
						||
   ::= {xupsBypass 1}
 | 
						||
 | 
						||
xupsBypassNumPhases OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..6)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The number of lines in the UPS bypass table."
 | 
						||
   ::= {xupsBypass 2}
 | 
						||
 | 
						||
xupsBypassTable OBJECT-TYPE
 | 
						||
   SYNTAX SEQUENCE OF XupsBypassEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   ::= {xupsBypass 3}
 | 
						||
 | 
						||
xupsBypassEntry OBJECT-TYPE
 | 
						||
   SYNTAX XupsBypassEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Entry in the XUPS bypass table."
 | 
						||
   INDEX { xupsBypassPhase }
 | 
						||
   ::= {xupsBypassTable 1}
 | 
						||
 | 
						||
XupsBypassEntry ::= SEQUENCE {
 | 
						||
   xupsBypassPhase
 | 
						||
   INTEGER,
 | 
						||
   xupsBypassVoltage
 | 
						||
   INTEGER
 | 
						||
   }
 | 
						||
 | 
						||
xupsBypassPhase OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..6)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The Bypass Phase, index for the table."
 | 
						||
   ::= {xupsBypassEntry 1}
 | 
						||
 | 
						||
xupsBypassVoltage OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Volts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The measured UPS bypass voltage in volts."
 | 
						||
   ::= {xupsBypassEntry 2}
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsEnvironment group:
 | 
						||
--
 | 
						||
 | 
						||
xupsEnvAmbientTemp OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (-100..200)   -- UNITS Degrees Centigrade
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The reading of the ambient temperature in the vicinity of the
 | 
						||
       UPS or SNMP agent."
 | 
						||
   ::= { xupsEnvironment  1 }
 | 
						||
 | 
						||
xupsEnvAmbientLowerLimit OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (-100..200)   -- UNITS Degrees Centigrade
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp
 | 
						||
falls below this value, the xupsAmbientTempBad alarm will occur."
 | 
						||
   ::= { xupsEnvironment  2 }
 | 
						||
 | 
						||
xupsEnvAmbientUpperLimit OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (-100..200)   -- UNITS Degrees Centigrade
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp
 | 
						||
rises above this value, the xupsAmbientTempBad alarm will occur.
 | 
						||
This value should be greater than xupsEnvAmbientLowerLimit."
 | 
						||
   ::= { xupsEnvironment  3 }
 | 
						||
 | 
						||
xupsEnvAmbientHumidity OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (0..100)   -- UNITS %
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The reading of the ambient humidity in the vicinity of the
 | 
						||
       UPS or SNMP agent."
 | 
						||
   ::= { xupsEnvironment  4 }
 | 
						||
 | 
						||
xupsEnvRemoteTemp OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (-100..200)   -- UNITS Degrees Centigrade
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The reading of a remote temperature sensor connected to the
 | 
						||
       UPS or SNMP agent."
 | 
						||
   ::= { xupsEnvironment  5 }
 | 
						||
 | 
						||
xupsEnvRemoteHumidity OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (0..100)   -- UNITS %
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The reading of a remote humidity sensor connected to the
 | 
						||
       UPS or SNMP agent."
 | 
						||
   ::= { xupsEnvironment  6 }
 | 
						||
 | 
						||
--
 | 
						||
-- The Environmental Contact Sensing Table
 | 
						||
--      Contains the table for monitoring all contacts (digital
 | 
						||
--      inputs).
 | 
						||
--
 | 
						||
 | 
						||
xupsEnvNumContacts OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (1..1024)
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "The number of Contacts in the xupsContactSenseTable.
 | 
						||
This object indicates the number of rows in the
 | 
						||
xupsContactSenseTable."
 | 
						||
   ::= { xupsEnvironment  7 }
 | 
						||
 | 
						||
xupsContactSenseTable OBJECT-TYPE
 | 
						||
   SYNTAX  SEQUENCE OF XupsContactsTableEntry
 | 
						||
   ACCESS  not-accessible
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "A list of Contact Sensing table entries.
 | 
						||
The number of entries is given by the value of
 | 
						||
xupsEnvNumContacts."
 | 
						||
   ::= { xupsEnvironment  8 }
 | 
						||
 | 
						||
xupsContactsTableEntry OBJECT-TYPE
 | 
						||
   SYNTAX  XupsContactsTableEntry
 | 
						||
   ACCESS  not-accessible
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "An entry containing information applicable
 | 
						||
to a particular Contact input."
 | 
						||
   INDEX   { xupsContactIndex }
 | 
						||
   ::= { xupsContactSenseTable  1 }
 | 
						||
 | 
						||
XupsContactsTableEntry ::=
 | 
						||
   SEQUENCE {
 | 
						||
xupsContactIndex
 | 
						||
   INTEGER,
 | 
						||
 | 
						||
xupsContactType
 | 
						||
   INTEGER,
 | 
						||
 | 
						||
xupsContactState
 | 
						||
   INTEGER,
 | 
						||
 | 
						||
xupsContactDescr
 | 
						||
   DisplayString
 | 
						||
   }
 | 
						||
 | 
						||
xupsContactIndex OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (1..1024)
 | 
						||
   ACCESS  not-accessible
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "The Contact identifier; identical to the Contact Number."
 | 
						||
   ::= { xupsContactsTableEntry  1 }
 | 
						||
 | 
						||
xupsContactType OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER {
 | 
						||
   normallyOpen(1),            -- or Input Normally High
 | 
						||
   normallyClosed(2),          -- or Input Normally Low
 | 
						||
   anyChange(3),               -- No normal Open/Closed state
 | 
						||
   notUsed(4)                  -- Contact not in service
 | 
						||
   }
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "The normal state for this contact.  The 'other'
 | 
						||
   state is the Active state for generating the xupstdContactActiveNotice
 | 
						||
   trap.  If anyChange(3) is selected, then this trap is sent
 | 
						||
       any time the contact changes to either Open or Closed.
 | 
						||
       No traps are sent if the Contact is set to notUsed(4).
 | 
						||
       In many cases, the configuration for Contacts may be done by other
 | 
						||
       means, so this object may be read-only."
 | 
						||
   ::= { xupsContactsTableEntry  2 }
 | 
						||
 | 
						||
xupsContactState OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER {
 | 
						||
   open(1),
 | 
						||
   closed(2),
 | 
						||
   openWithNotice(3),
 | 
						||
   closedWithNotice(4)
 | 
						||
   }
 | 
						||
   ACCESS  read-only
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "The current state of the Contact input;
 | 
						||
the value is based on the open/closed input state
 | 
						||
and the setting for xupsContactType.
 | 
						||
When entering the openWithNotice(3) and closedWithNotice(4)
 | 
						||
       states, no entries added to the xupsAlarmTable, but
 | 
						||
       the xupstdContactActiveNotice trap is sent."
 | 
						||
   ::= { xupsContactsTableEntry  3 }
 | 
						||
 | 
						||
xupsContactDescr OBJECT-TYPE
 | 
						||
   SYNTAX  DisplayString (SIZE (0..63))
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
  "A label identifying the Contact.  This object should be
 | 
						||
   set by the administrator."
 | 
						||
   ::= { xupsContactsTableEntry  4 }
 | 
						||
 | 
						||
xupsEnvRemoteTempLowerLimit OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (-100..200)   -- UNITS Degrees Centigrade
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The Lower Limit of the remote temperature; if xupsEnvRemoteTemp
 | 
						||
falls below this value, the xupsRemoteTempBad alarm will occur."
 | 
						||
   ::= { xupsEnvironment  9 }
 | 
						||
 | 
						||
xupsEnvRemoteTempUpperLimit OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (-100..200)   -- UNITS Degrees Centigrade
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The Upper Limit of the remote temperature; if xupsEnvRemoteTemp
 | 
						||
rises above this value, the xupsRemoteTempBad alarm will occur.
 | 
						||
This value should be greater than xupsEnvRemoteTempLowerLimit."
 | 
						||
   ::= { xupsEnvironment  10 }
 | 
						||
 | 
						||
xupsEnvRemoteHumidityLowerLimit OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (0..100)   -- UNITS %
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The Lower Limit of the remote humidity reading; if xupsEnvRemoteHumidity
 | 
						||
falls below this value, the xupsRemoteHumidityBad alarm will occur."
 | 
						||
   ::= { xupsEnvironment  11 }
 | 
						||
 | 
						||
xupsEnvRemoteHumidityUpperLimit OBJECT-TYPE
 | 
						||
   SYNTAX  INTEGER (0..100)   -- UNITS %
 | 
						||
   ACCESS  read-write
 | 
						||
   STATUS  mandatory
 | 
						||
   DESCRIPTION
 | 
						||
      "The Upper Limit of the remote humidity reading; if xupsEnvRemoteHumidity
 | 
						||
rises above this value, the xupsRemoteHumidityBad alarm will occur.
 | 
						||
This value should be greater than xupsEnvRemoteHumidityLowerLimit."
 | 
						||
   ::= { xupsEnvironment  12 }
 | 
						||
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsAlarm group:
 | 
						||
--
 | 
						||
xupsAlarms OBJECT-TYPE
 | 
						||
   SYNTAX Gauge
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The current number of alarm conditions."
 | 
						||
   ::= {xupsAlarm 1}
 | 
						||
 | 
						||
xupsAlarmTable OBJECT-TYPE
 | 
						||
   SYNTAX SEQUENCE OF XupsAlarmEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   ::= {xupsAlarm 2}
 | 
						||
 | 
						||
xupsAlarmEntry OBJECT-TYPE
 | 
						||
   SYNTAX XupsAlarmEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   INDEX { xupsAlarmID }
 | 
						||
   ::= {xupsAlarmTable 1}
 | 
						||
 | 
						||
XupsAlarmEntry ::= SEQUENCE {
 | 
						||
   xupsAlarmID
 | 
						||
INTEGER,
 | 
						||
   xupsAlarmDescr
 | 
						||
OBJECT IDENTIFIER,
 | 
						||
   xupsAlarmTime
 | 
						||
TimeTicks
 | 
						||
   }
 | 
						||
 | 
						||
xupsAlarmID OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER  (1..2147483647)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"A unique identifier for an alarm condition."
 | 
						||
   ::= {xupsAlarmEntry 1}
 | 
						||
 | 
						||
xupsAlarmDescr OBJECT-TYPE
 | 
						||
   SYNTAX OBJECT IDENTIFIER
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"A reference to an alarm description object.  The object
 | 
						||
referenced should not be accessible, but rather be used to
 | 
						||
provide a unique description of the alarm condition."
 | 
						||
   ::= {xupsAlarmEntry 2}
 | 
						||
 | 
						||
xupsAlarmTime OBJECT-TYPE
 | 
						||
   SYNTAX TimeTicks
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The value of the MIB-II variable sysUpTime when the alarm
 | 
						||
condition occurred."
 | 
						||
   ::= {xupsAlarmEntry 3}
 | 
						||
 | 
						||
--
 | 
						||
-- Well known alarm conditions.
 | 
						||
--
 | 
						||
xupsOnBattery                    OBJECT IDENTIFIER ::= {xupsAlarm 3}
 | 
						||
xupsLowBattery                   OBJECT IDENTIFIER ::= {xupsAlarm 4}
 | 
						||
xupsUtilityPowerRestored         OBJECT IDENTIFIER ::= {xupsAlarm 5}
 | 
						||
xupsReturnFromLowBattery         OBJECT IDENTIFIER ::= {xupsAlarm 6}
 | 
						||
xupsOutputOverload               OBJECT IDENTIFIER ::= {xupsAlarm 7}
 | 
						||
xupsInternalFailure              OBJECT IDENTIFIER ::= {xupsAlarm 8}
 | 
						||
xupsBatteryDischarged            OBJECT IDENTIFIER ::= {xupsAlarm 9}
 | 
						||
xupsInverterFailure              OBJECT IDENTIFIER ::= {xupsAlarm 10}
 | 
						||
xupsOnBypass                     OBJECT IDENTIFIER ::= {xupsAlarm 11}
 | 
						||
xupsBypassNotAvailable           OBJECT IDENTIFIER ::= {xupsAlarm 12}
 | 
						||
xupsOutputOff                    OBJECT IDENTIFIER ::= {xupsAlarm 13}
 | 
						||
xupsInputFailure                 OBJECT IDENTIFIER ::= {xupsAlarm 14}
 | 
						||
xupsBuildingAlarm                OBJECT IDENTIFIER ::= {xupsAlarm 15}
 | 
						||
xupsShutdownImminent             OBJECT IDENTIFIER ::= {xupsAlarm 16}
 | 
						||
xupsOnInverter                   OBJECT IDENTIFIER ::= {xupsAlarm 17}
 | 
						||
 | 
						||
 | 
						||
xupsAlarmNumEvents OBJECT-TYPE
 | 
						||
   SYNTAX Gauge
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The number of entries in the UPS event history queue."
 | 
						||
   ::= { xupsAlarm 18 }
 | 
						||
 | 
						||
xupsAlarmEventTable OBJECT-TYPE
 | 
						||
   SYNTAX SEQUENCE OF XupsAlarmEventEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"A table of the UPS internal event history queue."
 | 
						||
   ::= { xupsAlarm 19 }
 | 
						||
 | 
						||
xupsAlarmEventEntry OBJECT-TYPE
 | 
						||
   SYNTAX XupsAlarmEventEntry
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"One of the entries in the UPS event history queue."
 | 
						||
   INDEX { xupsAlarmEventID }
 | 
						||
   ::= { xupsAlarmEventTable 1 }
 | 
						||
 | 
						||
-- The first 4 vars in the xAEEntry have been deprecated, since they resulted in
 | 
						||
-- a flood of difficult to interpret data.  They have been replaced by the single
 | 
						||
-- entry, xupsAlarmEventMsg, which gives a human-readable description of the event.
 | 
						||
XupsAlarmEventEntry ::= SEQUENCE {
 | 
						||
   xupsAlarmEventID
 | 
						||
INTEGER,
 | 
						||
   xupsAlarmEventDateAndTime
 | 
						||
DisplayString,
 | 
						||
   xupsAlarmEventKind
 | 
						||
INTEGER,
 | 
						||
   xupsAlarmEventDescr
 | 
						||
INTEGER,
 | 
						||
xupsAlarmEventMsg
 | 
						||
DisplayString
 | 
						||
   }
 | 
						||
 | 
						||
xupsAlarmEventID OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (1..400)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS deprecated
 | 
						||
   DESCRIPTION
 | 
						||
"A unique number that reflects the order in which the event
 | 
						||
occurred. The oldest event in the queue will be number 1.
 | 
						||
Subsequent events will be numbered 2, 3, 4, etc."
 | 
						||
   ::= { xupsAlarmEventEntry 1 }
 | 
						||
 | 
						||
xupsAlarmEventDateAndTime OBJECT-TYPE
 | 
						||
   SYNTAX DisplayString (SIZE (0..22))
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS deprecated
 | 
						||
   DESCRIPTION
 | 
						||
"The time and date that an event occurred as recorded in the UPS
 | 
						||
internal event queue.  This string will reflect the time and
 | 
						||
date as set in the UPS itself and will not be referenced to
 | 
						||
sysUpTime.  The format is MM/DD/YYYY:HH:MM:SS.  Time is 24 hour standard."
 | 
						||
   ::= { xupsAlarmEventEntry 2 }
 | 
						||
 | 
						||
xupsAlarmEventKind OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER {
 | 
						||
   occurred (1),
 | 
						||
   cleared (2),
 | 
						||
   unknown (3)
 | 
						||
   }
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS deprecated
 | 
						||
   DESCRIPTION
 | 
						||
"Enumerated value that tells whether the event is an
 | 
						||
occurrence of an alarm condition or a clearing of an
 | 
						||
alarm condition."
 | 
						||
   ::= { xupsAlarmEventEntry 3 }
 | 
						||
 | 
						||
xupsAlarmEventDescr OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER  (0..2147483647)
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS deprecated
 | 
						||
   DESCRIPTION
 | 
						||
"A description of the event stored in the UPS event queue.
 | 
						||
This description will be a sixteen bit integer value
 | 
						||
representing one of the defined alarms in the Powerware Binary
 | 
						||
Computer Mode communication specification; for example,
 | 
						||
a value of 0 represents the 'Inverter AC Over Voltage'
 | 
						||
alarm (byte 1, bit 0 in the BCM Alarm Map)."
 | 
						||
   ::= { xupsAlarmEventEntry 4 }
 | 
						||
 | 
						||
xupsAlarmEventMsg OBJECT-TYPE
 | 
						||
   SYNTAX DisplayString (SIZE (0..80))
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"A text string describing each entry in the Event Log.  The format of this
 | 
						||
text message is free (not fixed) for the operator to read; good contents
 | 
						||
would be a time & date stamp, the event type, and a description of the event."
 | 
						||
   ::= { xupsAlarmEventEntry 5 }
 | 
						||
 | 
						||
--
 | 
						||
-- More Well known alarm conditions.
 | 
						||
--
 | 
						||
xupsBreakerOpen                  OBJECT IDENTIFIER ::= {xupsAlarm 20}
 | 
						||
xupsAlarmEntryAdded              OBJECT IDENTIFIER ::= {xupsAlarm 21}
 | 
						||
xupsAlarmEntryRemoved            OBJECT IDENTIFIER ::= {xupsAlarm 22}
 | 
						||
 | 
						||
-- Same as RFC 1628 Well Known Alarms:
 | 
						||
xupsAlarmBatteryBad              OBJECT IDENTIFIER ::= {xupsAlarm 23}
 | 
						||
xupsOutputOffAsRequested         OBJECT IDENTIFIER ::= {xupsAlarm 24}
 | 
						||
xupsDiagnosticTestFailed         OBJECT IDENTIFIER ::= {xupsAlarm 25}
 | 
						||
xupsCommunicationsLost           OBJECT IDENTIFIER ::= {xupsAlarm 26}
 | 
						||
xupsUpsShutdownPending           OBJECT IDENTIFIER ::= {xupsAlarm 27}
 | 
						||
xupsAlarmTestInProgress          OBJECT IDENTIFIER ::= {xupsAlarm 28}
 | 
						||
 | 
						||
-- Alarm for the Ambient Temperature, when outside of lo/hi limits
 | 
						||
xupsAmbientTempBad               OBJECT IDENTIFIER ::= {xupsAlarm 29}
 | 
						||
 | 
						||
-- For Loss of Redundancy in parallel systems
 | 
						||
xupsLossOfRedundancy             OBJECT IDENTIFIER ::= {xupsAlarm 30}
 | 
						||
 | 
						||
-- More Same as RFC 1628 Well Known Alarms:
 | 
						||
xupsAlarmTempBad                 OBJECT IDENTIFIER ::= {xupsAlarm 31}
 | 
						||
xupsAlarmChargerFailed           OBJECT IDENTIFIER ::= {xupsAlarm 32}
 | 
						||
xupsAlarmFanFailure              OBJECT IDENTIFIER ::= {xupsAlarm 33}
 | 
						||
xupsAlarmFuseFailure             OBJECT IDENTIFIER ::= {xupsAlarm 34}
 | 
						||
 | 
						||
-- A Relay, Contactor, or Breaker has failed
 | 
						||
xupsPowerSwitchBad               OBJECT IDENTIFIER ::= {xupsAlarm 35}
 | 
						||
 | 
						||
-- One module in a parallel or composite system has failed
 | 
						||
xupsModuleFailure                OBJECT IDENTIFIER ::= {xupsAlarm 36}
 | 
						||
 | 
						||
-- Two Alarms for systems with an Alternate Power Source, such as
 | 
						||
-- Secondary utility feed (on a dual AC input UPS), generator,
 | 
						||
-- flywheel, or fuelcell.
 | 
						||
xupsOnAlternatePowerSource       OBJECT IDENTIFIER ::= {xupsAlarm 37}
 | 
						||
xupsAltPowerNotAvailable         OBJECT IDENTIFIER ::= {xupsAlarm 38}
 | 
						||
 | 
						||
-- Some Notice condition exists which is not covered by the other WKA
 | 
						||
-- (like an xupsInternalFailure, but at a lower level of urgency)
 | 
						||
xupsNoticeCondition              OBJECT IDENTIFIER ::= {xupsAlarm 39}
 | 
						||
 | 
						||
-- Alarms for the Remote Temperature & Humidity, when outside of lo/hi limits
 | 
						||
xupsRemoteTempBad                OBJECT IDENTIFIER ::= {xupsAlarm 40}
 | 
						||
xupsRemoteHumidityBad            OBJECT IDENTIFIER ::= {xupsAlarm 41}
 | 
						||
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsTest group:
 | 
						||
--
 | 
						||
xupsTestBattery OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER { startTest (1) }
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Setting this variable to startTest initiates the
 | 
						||
battery test.  All other set values are invalid."
 | 
						||
   ::= {xupsTest 1}
 | 
						||
 | 
						||
xupsTestBatteryStatus OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER {
 | 
						||
   unknown (1),
 | 
						||
   passed (2),
 | 
						||
   failed (3),
 | 
						||
   inProgress (4),
 | 
						||
   notSupported (5),
 | 
						||
   inhibited (6),
 | 
						||
scheduled (7)
 | 
						||
   }
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Reading this enumerated value gives an indication of the
 | 
						||
UPS Battery test status."
 | 
						||
   ::= {xupsTest 2}
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsControl group:
 | 
						||
--
 | 
						||
xupsControlOutputOffDelay OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Setting this value to other than zero will cause the UPS
 | 
						||
output to turn off after the number of seconds.
 | 
						||
Setting it to 0 will cause an attempt to abort a pending
 | 
						||
shutdown."
 | 
						||
   ::= {xupsControl 1}
 | 
						||
 | 
						||
xupsControlOutputOnDelay OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Setting this value to other than zero will cause the UPS
 | 
						||
output to turn on after the number of seconds.
 | 
						||
Setting it to 0 will cause an attempt to abort a pending
 | 
						||
startup."
 | 
						||
   ::= {xupsControl 2}
 | 
						||
 | 
						||
xupsControlOutputOffTrapDelay OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"When xupsControlOutputOffDelay reaches this value, a trap will
 | 
						||
be sent."
 | 
						||
   ::= {xupsControl 3}
 | 
						||
 | 
						||
xupsControlOutputOnTrapDelay OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS deprecated
 | 
						||
   DESCRIPTION
 | 
						||
"When xupsControlOutputOnDelay reaches this value, a
 | 
						||
xupsOutputOff trap will be sent."
 | 
						||
   ::= {xupsControl 4}
 | 
						||
 | 
						||
xupsControlToBypassDelay OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Setting this value to other than zero will cause the UPS
 | 
						||
output to go to Bypass after the number of seconds.
 | 
						||
If the Bypass is unavailable, this may cause the UPS
 | 
						||
to not supply power to the load.
 | 
						||
Setting it to 0 will cause an attempt to abort a pending
 | 
						||
shutdown."
 | 
						||
   ::= {xupsControl 5}
 | 
						||
 | 
						||
xupsLoadShedSecsWithRestart OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Setting this value will cause the UPS output to turn off
 | 
						||
after the set number of seconds, then restart (after a UPS-defined
 | 
						||
'down time') when the utility is again available.
 | 
						||
Unlike xupsControlOutputOffDelay, which might or might not,
 | 
						||
      this object always maps to the XCP 0x8A Load Dump & Restart command,
 | 
						||
      so the desired shutdown and restart behavior is guaranteed to happen.
 | 
						||
Once set, this command cannot be aborted.
 | 
						||
      This is the preferred Control object to use when performing an On
 | 
						||
      Battery OS Shutdown."
 | 
						||
   ::= {xupsControl 6}
 | 
						||
 | 
						||
--
 | 
						||
-- xupsConfig group:
 | 
						||
--
 | 
						||
xupsConfigOutputVoltage OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Volts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The nominal UPS Output voltage per phase in volts."
 | 
						||
   ::= {xupsConfig 1}
 | 
						||
 | 
						||
xupsConfigInputVoltage OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Volts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The nominal UPS Input voltage per phase in volts."
 | 
						||
   ::= {xupsConfig 2}
 | 
						||
 | 
						||
xupsConfigOutputWatts OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS Watts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The nominal UPS available real power output in watts."
 | 
						||
   ::= {xupsConfig 3}
 | 
						||
 | 
						||
xupsConfigOutputFreq OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The nominal output frequency in tenths of Hz."
 | 
						||
   ::= {xupsConfig 4}
 | 
						||
 | 
						||
xupsConfigDateAndTime OBJECT-TYPE
 | 
						||
   SYNTAX DisplayString (SIZE (0..22))
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Date and time information for the UPS.  Setting this variable
 | 
						||
will initiate a set UPS date and time to this value.  Reading
 | 
						||
this variable will return the UPS time and date.  This value
 | 
						||
is not referenced to sysUpTime.  It is simply the clock value
 | 
						||
from the UPS real time clock.
 | 
						||
Format is as follows: MM/DD/YYYY:HH:MM:SS."
 | 
						||
   ::= { xupsConfig 5 }
 | 
						||
 | 
						||
xupsConfigLowOutputVoltageLimit OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Volts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The Lower limit for acceptable Output Voltage, per the UPS
 | 
						||
specifications."
 | 
						||
   ::= {xupsConfig 6}
 | 
						||
 | 
						||
xupsConfigHighOutputVoltageLimit OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)  -- UNITS RMS Volts
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The Upper limit for acceptable Output Voltage, per the UPS
 | 
						||
specifications."
 | 
						||
   ::= {xupsConfig 7}
 | 
						||
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsTrapControl group:
 | 
						||
--
 | 
						||
xupsMaxTrapLevel OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER {
 | 
						||
   none     (1),
 | 
						||
   critical (2),
 | 
						||
   major    (3),
 | 
						||
   allTraps (4)
 | 
						||
   }
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The level of severity of traps which will be sent to the
 | 
						||
requesting host; individual trap receivers will have
 | 
						||
individual values for this variable.  Values are:
 | 
						||
(1) none: no traps will be sent to this host;
 | 
						||
(2) critical: only traps for Critical alarm conditions will
 | 
						||
   be sent to this host;
 | 
						||
(3) major: Critical and Major traps will be sent;
 | 
						||
(4) allTraps: all Traps will be sent to this host
 | 
						||
   (Critical, Major, Minor, Informational)."
 | 
						||
   ::= {xupsTrapControl 1}
 | 
						||
 | 
						||
xupsSendTrapType OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER {
 | 
						||
   stnd     (1),
 | 
						||
   xups     (2),
 | 
						||
   stndPlus (3),
 | 
						||
   xupsPlus (4)
 | 
						||
   }
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The type of traps which will be sent to the
 | 
						||
requesting host; individual trap receivers will have
 | 
						||
individual values for this variable.  The additional
 | 
						||
variables in types (3) and (4) are useful for determining
 | 
						||
which UPS is the source on multi-port network adapters,
 | 
						||
and for getting additional descriptive information.
 | 
						||
Types (1) through (4) are all SNMP version 1 trap PDUs.
 | 
						||
Values are:
 | 
						||
(1) stnd: Traps as defined in the Standard UPS MIB (RFC1628)
 | 
						||
   and Generic (MIB II) traps as defined in RFC 1215.
 | 
						||
(2) xups: xupsTrapDefined Traps as defined in the PowerMIB
 | 
						||
   and Generic (MIB II) traps as defined in RFC 1215.
 | 
						||
(3) stndPlus: same as stnd plus variables from the interface
 | 
						||
   group and, where appropriate, xupsTrapMessage.
 | 
						||
(4) xupsPlus: xupsTrapPortN Traps (same as xups plus
 | 
						||
   variables from the interface group) and,
 | 
						||
   for authFail, xupsTrapMessage."
 | 
						||
   ::= {xupsTrapControl 2}
 | 
						||
 | 
						||
xupsTrapMessage OBJECT-TYPE
 | 
						||
   SYNTAX DisplayString (SIZE (0..79))
 | 
						||
   ACCESS not-accessible
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"A descriptive message which may be sent with traps to
 | 
						||
further explain the reason for the trap."
 | 
						||
   ::= {xupsTrapControl 3}
 | 
						||
 | 
						||
 | 
						||
 | 
						||
--
 | 
						||
-- xupsRecep group:
 | 
						||
--
 | 
						||
-- (Note that the terms Receptacle, Outlet, and Load Group are used interchangeably
 | 
						||
--  here and all mean "one of a set of controllable, power-switched outputs")
 | 
						||
--
 | 
						||
xupsNumReceptacles OBJECT-TYPE
 | 
						||
SYNTAX INTEGER (0..64)
 | 
						||
ACCESS read-only
 | 
						||
STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The number of independently controllable Receptacles, as described in the
 | 
						||
xupsRecepTable."
 | 
						||
::= {xupsRecep 1}
 | 
						||
 | 
						||
xupsRecepTable OBJECT-TYPE
 | 
						||
SYNTAX SEQUENCE OF XupsRecepEntry
 | 
						||
ACCESS not-accessible
 | 
						||
STATUS mandatory
 | 
						||
DESCRIPTION "The Aggregate Object with number of entries equal to
 | 
						||
   NumReceptacles and including the xupsRecep group."
 | 
						||
::={xupsRecep 2}
 | 
						||
 | 
						||
xupsRecepEntry OBJECT-TYPE
 | 
						||
SYNTAX XupsRecepEntry
 | 
						||
ACCESS not-accessible
 | 
						||
STATUS mandatory
 | 
						||
DESCRIPTION "The Recep table entry, etc."
 | 
						||
INDEX { xupsRecepIndex }
 | 
						||
::= { xupsRecepTable 1 }
 | 
						||
 | 
						||
XupsRecepEntry ::= SEQUENCE {
 | 
						||
xupsRecepIndex
 | 
						||
INTEGER,
 | 
						||
xupsRecepStatus
 | 
						||
INTEGER,
 | 
						||
xupsRecepOffDelaySecs
 | 
						||
INTEGER,
 | 
						||
xupsRecepOnDelaySecs
 | 
						||
INTEGER,
 | 
						||
xupsRecepAutoOffDelay
 | 
						||
       INTEGER,
 | 
						||
xupsRecepAutoOnDelay
 | 
						||
       INTEGER,
 | 
						||
   xupsRecepShedSecsWithRestart
 | 
						||
       INTEGER
 | 
						||
}
 | 
						||
 | 
						||
xupsRecepIndex OBJECT-TYPE
 | 
						||
SYNTAX INTEGER (1..64)
 | 
						||
ACCESS read-only
 | 
						||
STATUS mandatory
 | 
						||
DESCRIPTION
 | 
						||
"The number of the Receptacle. Serves as index for Receptacle table."
 | 
						||
::= {xupsRecepEntry 1}
 | 
						||
 | 
						||
 | 
						||
xupsRecepStatus OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER {
 | 
						||
on(1), off(2), pendingOff(3), pendingOn(4), unknown(5) }
 | 
						||
   ACCESS read-only
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
   "The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
 | 
						||
   4=Off w/Pending ON, 5=Unknown."
 | 
						||
::={xupsRecepEntry 2}
 | 
						||
 | 
						||
 | 
						||
xupsRecepOffDelaySecs OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (-1..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The Delay until the Receptacle is turned Off.  Setting
 | 
						||
this value to other than -1 will cause the UPS output to
 | 
						||
turn off after the number of seconds (0 is immediately).
 | 
						||
Setting it to -1 will cause an attempt to abort a pending shutdown.
 | 
						||
When this object is set while the UPS is On Battery, it is not necessary
 | 
						||
to set xupsRecepOnDelaySecs, since the outlet will turn back on
 | 
						||
automatically when power is available again."
 | 
						||
::= {xupsRecepEntry 3}
 | 
						||
 | 
						||
xupsRecepOnDelaySecs OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (-1..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
" The Delay until the Receptacle is turned On.  Setting
 | 
						||
this value to other than -1 will cause the UPS output to
 | 
						||
turn on after the number of seconds (0 is immediately).
 | 
						||
Setting it to -1 will cause an attempt to abort a pending restart."
 | 
						||
::={xupsRecepEntry 4}
 | 
						||
 | 
						||
 | 
						||
xupsRecepAutoOffDelay OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (-1..32767)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"The delay after going On Battery until the Receptacle is
 | 
						||
automatically turned Off.  A value of -1 means that this Output should
 | 
						||
never be turned Off automatically, but must be turned Off only by command.
 | 
						||
Values from 0 to 30 are valid, but probably innappropriate.
 | 
						||
The AutoOffDelay can be used to prioritize loads in the event of a prolonged
 | 
						||
power outage; less critical loads will turn off earlier to extend battery
 | 
						||
time for the more critical loads. If the utility power is restored before the
 | 
						||
AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off."
 | 
						||
::= {xupsRecepEntry 5}
 | 
						||
 | 
						||
xupsRecepAutoOnDelay OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (-1..32767)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Seconds delay after the Outlet is signaled to turn On before the Output is
 | 
						||
Automatically turned ON. A value of -1 means that this Output should never
 | 
						||
be turned On automatically, but only when specifically commanded to do so.
 | 
						||
A value of 0 means that the Receptacle should come On immediately
 | 
						||
at power-up or for an On command."
 | 
						||
::= {xupsRecepEntry 6}
 | 
						||
 | 
						||
-- xupsRecepAutoOnDelay has three purposes:
 | 
						||
-- 1. To coordinate the automatic startup of various outlets, when the normal
 | 
						||
-- auto-sequencing of 1 second per outlet is not adequate. For example, they may
 | 
						||
-- be used to power up hard disk arrays before CPU units are started.
 | 
						||
-- 2. To force additional 'Down Time' during xupsRecepOffDelaySecs commands, for
 | 
						||
-- equipment to be reset, when the standard 'Down Time' is not long enough.
 | 
						||
-- 3. For the -1 value, to ensure that loads wont be powered until commanded,
 | 
						||
-- following power-up or a xupsRecepOffDelaySecs command.
 | 
						||
 | 
						||
xupsRecepShedSecsWithRestart OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER (0..2147483647)    -- UNITS seconds
 | 
						||
   ACCESS read-write
 | 
						||
   STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Setting this value will cause the UPS output to turn off
 | 
						||
after the set number of seconds, then restart (after a UPS-defined
 | 
						||
'down time') when the utility is again available.
 | 
						||
Unlike xupsRecepOffDelaySecs, which might or might not,
 | 
						||
      this object always maps to the XCP 0x8A Load Dump & Restart command,
 | 
						||
      so the desired shutdown and restart behavior is guaranteed to happen.
 | 
						||
Once set, this command cannot be aborted."
 | 
						||
   ::= {xupsRecepEntry 7}
 | 
						||
 | 
						||
--
 | 
						||
-- xupsTopology group:
 | 
						||
--
 | 
						||
xupsTopologyType OBJECT-TYPE
 | 
						||
SYNTAX INTEGER (0..32767)
 | 
						||
ACCESS read-only
 | 
						||
STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Value which denotes the type of UPS by its power topology.  Values are the
 | 
						||
same as those described in the XCP Topology block's Overall Topology field."
 | 
						||
::= {xupsTopology 1}
 | 
						||
 | 
						||
xupsTopoMachineCode OBJECT-TYPE
 | 
						||
SYNTAX INTEGER (0..32767)
 | 
						||
ACCESS read-only
 | 
						||
STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"ID Value which denotes the Powerware model of the UPS for software.  Values
 | 
						||
are the same as those described in the XCP Configuration block's Machine Code
 | 
						||
field."
 | 
						||
::= {xupsTopology 2}
 | 
						||
 | 
						||
xupsTopoUnitNumber OBJECT-TYPE
 | 
						||
SYNTAX INTEGER (0..64)
 | 
						||
ACCESS read-only
 | 
						||
STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Identifies which unit and what type of data is being reported.
 | 
						||
A value of 0 means that this MIB information comes from the top-level system
 | 
						||
view (eg, manifold module or system bypass cabinet reporting total system
 | 
						||
output).  Standalone units also use a value of 0, since they are the 'full
 | 
						||
system' view.
 | 
						||
A value of 1 or higher indicates the number of the module in the system
 | 
						||
which is reporting only its own data in the PowerMIB objects."
 | 
						||
::= {xupsTopology 3}
 | 
						||
 | 
						||
xupsTopoPowerStrategy OBJECT-TYPE
 | 
						||
   SYNTAX INTEGER {
 | 
						||
highAlert(1), standard(2), enableHighEfficiency(3),
 | 
						||
immediateHighEfficiency(4) }
 | 
						||
ACCESS read-write
 | 
						||
STATUS mandatory
 | 
						||
   DESCRIPTION
 | 
						||
"Value which denotes which Power Strategy is currently set for the UPS.
 | 
						||
The values are:
 | 
						||
highAlert(1) - The UPS shall optimize its operating state to maximize its
 | 
						||
power-protection levels.  This mode will be held for at most 24 hours.
 | 
						||
standard(2) - Balanced, normal power protection strategy. UPS will not enter
 | 
						||
HE operating mode from this setting.
 | 
						||
enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to
 | 
						||
optimize its operating state to maximize its efficiency, when
 | 
						||
conditions change to permit it (as determined by the UPS).
 | 
						||
forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
 | 
						||
and if conditions permit, requires the UPS to enter High Efficiency
 | 
						||
mode now, without delay (for as long as utility conditions permit).
 | 
						||
After successfully set to forceHighEfficiency(4),
 | 
						||
xupsTopoPowerStrategy changes to value enableHighEfficiency(3).
 | 
						||
xupsOutputSource will indicate if the UPS status is actually operating in
 | 
						||
High Efficiency mode."
 | 
						||
::= {xupsTopology 4}
 | 
						||
 | 
						||
-- *************************************************************************
 | 
						||
-- *************************************************************************
 | 
						||
 | 
						||
--
 | 
						||
-- Traps (xupst)
 | 
						||
--
 | 
						||
-- 1) Powerware's traps are defined in this MIB for three different sources:
 | 
						||
--      a) Basic Agents for which the trap variables have not been defined,
 | 
						||
--              though trap variables are included with the trap PDU
 | 
						||
--      b) Agents with exactly Defined trap variables, which may be
 | 
						||
--              used as input to trap response macros on management stations
 | 
						||
--      c) Agents with Defined traps including ifIndex and ifDescr,
 | 
						||
--              which can be used to determine which UPS of a multi-port
 | 
						||
--              agent (eg, Powerware Network SNMP Adapter) sent the trap
 | 
						||
--    The trap definitions for the three sources are very similar,
 | 
						||
--      and use the same alarms as their triggers; their names are prefaced
 | 
						||
--      by xupstb, xupstd, and xupstp to distinguish the three types
 | 
						||
--
 | 
						||
-- 2) Trap Severity Level is given as a comment to indicate which
 | 
						||
--      xupsMaxTrapLevel will result in this trap being sent; levels
 | 
						||
--      are (in order): Critical, Major, Minor, Informational
 | 
						||
--
 | 
						||
-- 3) The following Object Identifiers are used to distinguish Powerware's
 | 
						||
--      Trap sources:
 | 
						||
--      a) The first is for traps without defined trap variables
 | 
						||
xupsNull         OBJECT IDENTIFIER       ::= { xups 0 }
 | 
						||
xupsTrapBasic    OBJECT IDENTIFIER       ::= { xupsNull 0 }
 | 
						||
--      b) The second is for traps with defined variables,
 | 
						||
--              without ifIndex & ifDescr
 | 
						||
xupsTrapSource   OBJECT IDENTIFIER       ::= {xupsTrapControl 4}
 | 
						||
xupsTrapDefined  OBJECT IDENTIFIER       ::= {xupsTrapSource 1}
 | 
						||
--      c) The third is for traps with defined variables
 | 
						||
--              plus ifIndex & ifDescr
 | 
						||
xupsTrapPortN    OBJECT IDENTIFIER       ::= {xupsTrapSource 2}
 | 
						||
 | 
						||
 | 
						||
-- ****************************************************************************
 | 
						||
-- ****************************************************************************
 | 
						||
--
 | 
						||
-- Traps from xupsTrapBasic source (xupstb):
 | 
						||
--
 | 
						||
xupstbControlOff TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS output power will turn off in a number of
 | 
						||
seconds equal to upsControlOutputOffTrapDelay."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 1
 | 
						||
 | 
						||
xupstbControlOn TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS output power will turn on in a number of
 | 
						||
seconds equal to upsControlOutputOnTrapDelay."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 2
 | 
						||
 | 
						||
xupstbOnBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS has no AC input power and is running on
 | 
						||
battery."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 3
 | 
						||
 | 
						||
xupstbLowBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS batteries are low.  Tied to low battery
 | 
						||
alarm condition."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 4
 | 
						||
 | 
						||
xupstbUtilityPowerRestored TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"Input power has been restored after running on battery."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 5
 | 
						||
 | 
						||
xupstbReturnFromLowBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The battery has recovered from a low battery condition."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 6
 | 
						||
 | 
						||
xupstbOutputOverload TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups has sensed an overload of greater than
 | 
						||
106 percent.  Tied to the 106% overload alarm."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 7
 | 
						||
 | 
						||
xupstbInternalFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"Some component of the ups - rectifier, inverter,
 | 
						||
control panel has failed.  Tied to alarms indicating failure."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 8
 | 
						||
 | 
						||
xupstbBatteryDischarged TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The Battery Totally Discharged Alarm has occurred."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 9
 | 
						||
 | 
						||
xupstbInverterFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups inverter is unavailable due to an internal failure."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 10
 | 
						||
 | 
						||
xupstbOnBypass TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups has gone on bypass for some reason."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 11
 | 
						||
 | 
						||
xupstbBypassNotAvailable TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups bypass is unavailable"
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 12
 | 
						||
 | 
						||
xupstbOutputOff TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups output is switched off."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 13
 | 
						||
 | 
						||
xupstbInputFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups input power is incorrect in voltage,
 | 
						||
frequency, or phase rotation."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 14
 | 
						||
 | 
						||
xupstbBuildingAlarm TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"One of the defined building alarms has occurred."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 15
 | 
						||
 | 
						||
xupstbShutdownImminent TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups shutdown imminent alarm has occurred."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 16
 | 
						||
 | 
						||
xupstbOnInverter TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"The ups is returned to utility power running the inverter
 | 
						||
after either a transfer to bypass or a run on battery."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 17
 | 
						||
 | 
						||
xupstbBreakerOpen TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"One of the UPS breakers or contactors has been opened."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 20
 | 
						||
 | 
						||
xupstbAlarmEntryAdded TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"An alarm not defined in the xups Well Known Alarms
 | 
						||
(eg, an alarm defined in RFC1628)
 | 
						||
has been added to the Alarm Table."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 21
 | 
						||
 | 
						||
xupstbAlarmEntryRemoved TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapBasic
 | 
						||
   DESCRIPTION
 | 
						||
"An alarm not defined in the xups Well Known Alarms
 | 
						||
has been removed from the Alarm Table."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 22
 | 
						||
 | 
						||
 | 
						||
-- The following alarms do not have equivalents as Basic Traps
 | 
						||
-- xupstbAlarmBatteryBad        ::= 23
 | 
						||
-- xupstbOutputOffAsRequested   ::= 24
 | 
						||
-- xupstbDiagnosticTestFailed   ::= 25
 | 
						||
-- xupstbCommunicationsLost     ::= 26
 | 
						||
-- xupstbUpsShutdownPending     ::= 27
 | 
						||
-- xupstbAlarmTestInProgress    ::= 28
 | 
						||
-- xupstbAmbientTempBad         ::= 29
 | 
						||
-- xupstbContactActiveNotice    ::= 30
 | 
						||
-- xupstbContactInactiveNotice  ::= 31
 | 
						||
-- xupstbLossOfRedundancy       ::= 32
 | 
						||
-- xupstbAlarmTempBad ::= 33
 | 
						||
-- xupstbAlarmChargerFailed ::= 34
 | 
						||
-- xupstbAlarmFanFailure ::= 35
 | 
						||
-- xupstbAlarmFuseFailure ::= 36
 | 
						||
-- xupstbPowerSwitchBad ::= 37
 | 
						||
-- xupstbModuleFailure ::= 38
 | 
						||
-- xupstbOnAlternatePowerSource ::= 39
 | 
						||
-- xupstbAltPowerNotAvailable ::= 40
 | 
						||
-- xupstbNoticeCondition ::= 41
 | 
						||
-- xupstbRemoteTempBad          ::= 42
 | 
						||
-- xupstbRemoteHumidityBad      ::= 43
 | 
						||
 | 
						||
 | 
						||
-- ****************************************************************************
 | 
						||
-- ****************************************************************************
 | 
						||
--
 | 
						||
-- Traps from xupsTrapDefined source (xupstd):
 | 
						||
--
 | 
						||
 | 
						||
xupstdControlOff TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS output power will turn off in a number of
 | 
						||
seconds equal to upsControlOutputOffTrapDelay."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 1
 | 
						||
 | 
						||
xupstdControlOn TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS output power will turn on in a number of
 | 
						||
seconds equal to upsControlOutputOnTrapDelay."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 2
 | 
						||
 | 
						||
xupstdOnBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS has no AC input power and is running on
 | 
						||
battery."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 3
 | 
						||
 | 
						||
xupstdLowBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS batteries are low.  Tied to low battery
 | 
						||
alarm condition."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 4
 | 
						||
 | 
						||
xupstdUtilityPowerRestored TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"Input power has been restored after running on battery."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 5
 | 
						||
 | 
						||
xupstdReturnFromLowBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The battery has recovered from a low battery condition."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 6
 | 
						||
 | 
						||
xupstdOutputOverload TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups has sensed an overload of greater than
 | 
						||
106 percent.  Tied to the 106% overload alarm."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 7
 | 
						||
 | 
						||
xupstdInternalFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"Some component of the ups - rectifier, inverter,
 | 
						||
control panel has failed.  Tied to alarms indi-
 | 
						||
cating failure."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 8
 | 
						||
 | 
						||
xupstdBatteryDischarged TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The Battery Totally Discharged Alarm has occurred."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 9
 | 
						||
 | 
						||
xupstdInverterFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups inverter is unavailable due to an internal failure."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 10
 | 
						||
 | 
						||
xupstdOnBypass TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups has gone on bypass for some reason."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 11
 | 
						||
 | 
						||
xupstdBypassNotAvailable TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups bypass is unavailable"
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 12
 | 
						||
 | 
						||
xupstdOutputOff TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups output is switched off."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 13
 | 
						||
 | 
						||
xupstdInputFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups input power is incorrect in voltage,
 | 
						||
frequency, or phase rotation."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 14
 | 
						||
 | 
						||
xupstdBuildingAlarm TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"One of the defined building alarms has occurred."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 15
 | 
						||
 | 
						||
xupstdShutdownImminent TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups shutdown imminent alarm has occurred."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 16
 | 
						||
 | 
						||
xupstdOnInverter TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups is returned to utility power running the inverter
 | 
						||
after either a transfer to bypass or a run on battery."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 17
 | 
						||
 | 
						||
xupstdBreakerOpen TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"One of the UPS breakers or contactors has been opened."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 20
 | 
						||
 | 
						||
xupstdAlarmEntryAdded TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"An alarm not defined in the xups Well Known Alarms
 | 
						||
(eg, an alarm defined in RFC1628)
 | 
						||
has been added to the Alarm Table."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 21
 | 
						||
 | 
						||
xupstdAlarmEntryRemoved TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"An alarm not defined in the xups Well Known Alarms
 | 
						||
has been removed from the Alarm Table."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 22
 | 
						||
 | 
						||
xupstdAlarmBatteryBad        TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"One or more batteries have been determined to require replacement."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 23
 | 
						||
 | 
						||
xupstdOutputOffAsRequested   TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS has shutdown as requested, i.e., the output is off."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 24
 | 
						||
 | 
						||
xupstdDiagnosticTestFailed   TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The result of the last diagnostic test indicates a failure."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 25
 | 
						||
 | 
						||
xupstdCommunicationsLost     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"A problem has been encountered in the communications
 | 
						||
between the agent and the UPS."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 26
 | 
						||
 | 
						||
xupstdUpsShutdownPending     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"An xupsControlOutputOffDelay countdown is underway."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 27
 | 
						||
 | 
						||
xupstdAlarmTestInProgress    TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"A test is in progress, as initiated and indicated by the
 | 
						||
Battery Test Group."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 28
 | 
						||
 | 
						||
-- Provide additional information with the AmbientTemp trap
 | 
						||
xupstdAmbientTempBad         TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
 xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
 | 
						||
 xupsEnvAmbientUpperLimit }
 | 
						||
   DESCRIPTION
 | 
						||
      "The ambient temperature, xupsEnvAmbientTemp, has fallen below
 | 
						||
the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
 | 
						||
the set upper limit, xupsEnvAmbientUpperLimit."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 29
 | 
						||
 | 
						||
-- Added to support the ConnectUPS Web/SNMP card's ability to monitor contact(s)
 | 
						||
xupstdContactActiveNotice TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The Contact indicated by xupsContactIndex is in its Active state.
 | 
						||
    The following are the situations that generate this trap:
 | 
						||
   For xupsContactType:    and     xupsContactState:
 | 
						||
       normallyOpen(1)     and     closedWithNotice(4)
 | 
						||
             normallyClosed(2)   and     openWithNotice(3)
 | 
						||
             anyChange(3)        and     openWithNotice(3) or closedWithNotice(4)"
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 30
 | 
						||
 | 
						||
xupstdContactInactiveNotice TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The Contact indicated by xupsContactIndex has changed to its Inactive state."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 31
 | 
						||
 | 
						||
xupstdLossOfRedundancy     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"A parallel UPS system is no longer operating in N+1 redundant mode;
 | 
						||
      this may be due to module failure or removal, or due to overloading."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 32
 | 
						||
 | 
						||
xupstdAlarmTempBad     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"An internal temperature is out of tolerance."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 33
 | 
						||
 | 
						||
xupstdAlarmChargerFailed     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"An uncorrected problem has been detected within the UPS charger subsystem."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 34
 | 
						||
 | 
						||
xupstdAlarmFanFailure     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The failure of one or more fans in the UPS has been detected."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 35
 | 
						||
 | 
						||
xupstdAlarmFuseFailure     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"The failure of one or more fuses has been detected."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 36
 | 
						||
 | 
						||
xupstdPowerSwitchBad     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"A Relay, Contactor, or Breaker has failed."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 37
 | 
						||
 | 
						||
xupstdModuleFailure     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"One module in a parallel or composite system has failed."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 38
 | 
						||
 | 
						||
-- Adds xupsInputSource to its var list
 | 
						||
xupstdOnAlternatePowerSource     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, xupsInputSource }
 | 
						||
   DESCRIPTION
 | 
						||
"The system is being powered by its Alternate Power Source, such as a
 | 
						||
Secondary utility feed (on a dual AC input UPS), generator, flywheel,
 | 
						||
or fuelcell."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 39
 | 
						||
 | 
						||
xupstdAltPowerNotAvailable     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"On systems with a separate alternate power source (eg, dual AC inputs),
 | 
						||
that alternate power source is currently not available.  This could be
 | 
						||
a problem if the primary power source (eg, utility) fails for a period
 | 
						||
of time longer than that for which the internal batteries can supply power."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 40
 | 
						||
 | 
						||
xupstdNoticeCondition     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage }
 | 
						||
   DESCRIPTION
 | 
						||
"Some Notice condition exists which is not covered by the other traps.
 | 
						||
This is like an xupstdInternalFailure, but at a lower severity level."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 41
 | 
						||
 | 
						||
 | 
						||
-- Provide additional information with the RemoteTemp and RemoteHumidity traps
 | 
						||
xupstdRemoteTempBad         TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
 xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit,
 | 
						||
 xupsEnvRemoteTempUpperLimit }
 | 
						||
   DESCRIPTION
 | 
						||
      "The remote temperature, xupsEnvRemoteTemp, has fallen below
 | 
						||
the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
 | 
						||
the set upper limit, xupsEnvRemoteTempUpperLimit."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 42
 | 
						||
 | 
						||
xupstdRemoteHumidityBad     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapDefined
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
 xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
 | 
						||
 xupsEnvRemoteHumidityUpperLimit }
 | 
						||
   DESCRIPTION
 | 
						||
      "The remote temperature, xupsEnvRemoteHumidity, has fallen below
 | 
						||
the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
 | 
						||
the set upper limit, xupsEnvRemoteHumidityUpperLimit."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 43
 | 
						||
 | 
						||
 | 
						||
 | 
						||
-- ****************************************************************************
 | 
						||
-- ****************************************************************************
 | 
						||
--
 | 
						||
-- Traps from xupsTrapPortN source (xupstp):
 | 
						||
--
 | 
						||
 | 
						||
xupstpControlOff TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS output power will turn off in a number of
 | 
						||
seconds equal to upsControlOutputOffTrapDelay."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 1
 | 
						||
 | 
						||
xupstpControlOn TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS output power will turn on in a number of
 | 
						||
seconds equal to upsControlOutputOnTrapDelay."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 2
 | 
						||
 | 
						||
xupstpOnBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS has no AC input power and is running on
 | 
						||
battery."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 3
 | 
						||
 | 
						||
xupstpLowBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS batteries are low.  Tied to low battery
 | 
						||
alarm condition."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 4
 | 
						||
 | 
						||
xupstpUtilityPowerRestored TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"Input power has been restored after running on battery."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 5
 | 
						||
 | 
						||
xupstpReturnFromLowBattery TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The battery has recovered from a low battery condition."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 6
 | 
						||
 | 
						||
xupstpOutputOverload TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups has sensed an overload of greater than
 | 
						||
106 percent.  Tied to the 106% overload alarm."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 7
 | 
						||
 | 
						||
xupstpInternalFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"Some component of the ups - rectifier, inverter,
 | 
						||
control panel has failed.  Tied to alarms indi-
 | 
						||
cating failure."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 8
 | 
						||
 | 
						||
xupstpBatteryDischarged TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The Battery Totally Discharged Alarm has occurred."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 9
 | 
						||
 | 
						||
xupstpInverterFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups inverter is unavailable due to an internal failure."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 10
 | 
						||
 | 
						||
xupstpOnBypass TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups has gone on bypass for some reason."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 11
 | 
						||
 | 
						||
xupstpBypassNotAvailable TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups bypass is unavailable"
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 12
 | 
						||
 | 
						||
xupstpOutputOff TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups output is switched off."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 13
 | 
						||
 | 
						||
xupstpInputFailure TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups input power is incorrect in voltage,
 | 
						||
frequency, or phase rotation."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 14
 | 
						||
 | 
						||
xupstpBuildingAlarm TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"One of the defined building alarms has occurred."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 15
 | 
						||
 | 
						||
xupstpShutdownImminent TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups shutdown imminent alarm has occurred."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 16
 | 
						||
 | 
						||
xupstpOnInverter TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The ups is returned to utility power running the inverter
 | 
						||
after either a transfer to bypass or a run on battery."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 17
 | 
						||
 | 
						||
xupstpBreakerOpen TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"One of the UPS breakers or contactors has been opened."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 20
 | 
						||
 | 
						||
xupstpAlarmEntryAdded TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"An alarm not defined in the xups Well Known Alarms
 | 
						||
(eg, an alarm defined in RFC1628)
 | 
						||
has been added to the Alarm Table."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 21
 | 
						||
 | 
						||
xupstpAlarmEntryRemoved TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"An alarm not defined in the xups Well Known Alarms
 | 
						||
has been removed from the Alarm Table."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 22
 | 
						||
 | 
						||
xupstpAlarmBatteryBad        TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"One or more batteries have been determined to require replacement."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 23
 | 
						||
 | 
						||
xupstpOutputOffAsRequested   TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The UPS has shutdown as requested, i.e., the output is off."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 24
 | 
						||
 | 
						||
xupstpDiagnosticTestFailed   TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The result of the last diagnostic test indicates a failure."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 25
 | 
						||
 | 
						||
xupstpCommunicationsLost     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"A problem has been encountered in the communications
 | 
						||
between the agent and the UPS."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 26
 | 
						||
 | 
						||
xupstpUpsShutdownPending     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"An xupsControlOutputOffDelay countdown is underway."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 27
 | 
						||
 | 
						||
xupstpAlarmTestInProgress    TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
     ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"A test is in progress, as initiated and indicated by the
 | 
						||
Battery Test Group."
 | 
						||
   --#SEVERITY INFORMATIONAL
 | 
						||
   ::= 28
 | 
						||
 | 
						||
-- Provide additional information with the AmbientTemp trap
 | 
						||
xupstpAmbientTempBad         TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
 ifIndex, ifDescr,
 | 
						||
 xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
 | 
						||
 xupsEnvAmbientUpperLimit }
 | 
						||
   DESCRIPTION
 | 
						||
      "The ambient temperature, xupsEnvAmbientTemp, has fallen below
 | 
						||
the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
 | 
						||
the set upper limit, xupsEnvAmbientUpperLimit."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 29
 | 
						||
 | 
						||
-- The following alarms do not have equivalents as PortN Traps
 | 
						||
-- xupstdContactActiveNotice    ::= 30
 | 
						||
-- xupstdContactInactiveNotice  ::= 31
 | 
						||
 | 
						||
xupstpLossOfRedundancy     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"A parallel UPS system is no longer operating in N+1 redundant mode;
 | 
						||
      this may be due to module failure or removal, or due to overloading."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 32
 | 
						||
 | 
						||
 | 
						||
xupstpAlarmTempBad     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"An internal temperature is out of tolerance."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 33
 | 
						||
 | 
						||
xupstpAlarmChargerFailed     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"An uncorrected problem has been detected within the UPS charger subsystem."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 34
 | 
						||
 | 
						||
xupstpAlarmFanFailure     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The failure of one or more fans in the UPS has been detected."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 35
 | 
						||
 | 
						||
xupstpAlarmFuseFailure     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The failure of one or more fuses has been detected."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 36
 | 
						||
 | 
						||
xupstpPowerSwitchBad     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"A Relay, Contactor, or Breaker has failed."
 | 
						||
   --#SEVERITY CRITICAL
 | 
						||
   ::= 37
 | 
						||
 | 
						||
xupstpModuleFailure     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"One module in a parallel or composite system has failed."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 38
 | 
						||
 | 
						||
xupstpOnAlternatePowerSource     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, xupsInputSource,
 | 
						||
                 ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"The system is being powered by its Alternate Power Source, such as a
 | 
						||
Secondary utility feed (on a dual AC input UPS), generator, flywheel,
 | 
						||
or fuelcell."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 39
 | 
						||
 | 
						||
xupstpAltPowerNotAvailable     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"On systems with a separate alternate power source (eg, dual AC inputs),
 | 
						||
that alternate power source is currently not available.  This could be
 | 
						||
a problem if the primary power source (eg, utility) fails for a period
 | 
						||
of time longer than that for which the internal batteries can supply power."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 40
 | 
						||
 | 
						||
xupstpNoticeCondition     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage, ifIndex, ifDescr }
 | 
						||
   DESCRIPTION
 | 
						||
"Some Notice condition exists which is not covered by the other traps.
 | 
						||
This is like an xupstpInternalFailure, but at a lower severity level."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 41
 | 
						||
 | 
						||
 | 
						||
-- Provide additional information with the RemoteTemp and RemoteHumidity traps
 | 
						||
xupstpRemoteTempBad         TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
 ifIndex, ifDescr,
 | 
						||
 xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit,
 | 
						||
 xupsEnvRemoteTempUpperLimit }
 | 
						||
   DESCRIPTION
 | 
						||
      "The remote temperature, xupsEnvRemoteTemp, has fallen below
 | 
						||
the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
 | 
						||
the set upper limit, xupsEnvRemoteTempUpperLimit."
 | 
						||
   --#SEVERITY MAJOR
 | 
						||
   ::= 42
 | 
						||
 | 
						||
xupstpRemoteHumidityBad     TRAP-TYPE
 | 
						||
   ENTERPRISE xupsTrapPortN
 | 
						||
   VARIABLES   { xupsAlarmID,  xupsAlarmDescr, xupsTrapMessage,
 | 
						||
 ifIndex, ifDescr,
 | 
						||
 xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
 | 
						||
 xupsEnvRemoteHumidityUpperLimit }
 | 
						||
   DESCRIPTION
 | 
						||
      "The remote temperature, xupsEnvRemoteHumidity, has fallen below
 | 
						||
the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
 | 
						||
the set upper limit, xupsEnvRemoteHumidityUpperLimit."
 | 
						||
   --#SEVERITY MINOR
 | 
						||
   ::= 43
 | 
						||
 | 
						||
 | 
						||
   END
 |