mirror of
				https://github.com/librenms/librenms.git
				synced 2024-10-07 16:52:45 +00:00 
			
		
		
		
	git-svn-id: http://www.observium.org/svn/observer/trunk@2851 61d68cd4-352d-0410-923a-c4978735b2b8
		
			
				
	
	
		
			3587 lines
		
	
	
		
			131 KiB
		
	
	
	
		
			Plaintext
		
	
	
	
	
	
			
		
		
	
	
			3587 lines
		
	
	
		
			131 KiB
		
	
	
	
		
			Plaintext
		
	
	
	
	
	
-- ****************************************************************************
 | 
						|
--
 | 
						|
--                         Rack Information MIB
 | 
						|
--         Management Information Base for SNMP Network Management
 | 
						|
--
 | 
						|
--
 | 
						|
--      Copyright 2002,2003 Hewlett-Packard Development Company, L.P.
 | 
						|
--
 | 
						|
--      Hewlett-Packard Company shall not be liable for technical or
 | 
						|
--      editorial errors or omissions contained herein. The information in
 | 
						|
--      this document is provided "as is" without warranty of any kind and
 | 
						|
--      is subject to change without notice. The warranties for HP products
 | 
						|
--      are set forth in the express limited warranty statements
 | 
						|
--      accompanying such products. Nothing herein should be construed as
 | 
						|
--      constituting an additional warranty.
 | 
						|
--
 | 
						|
--      Confidential computer software. Valid license from HP required for
 | 
						|
--      possession, use or copying. Consistent with FAR 12.211 and 12.212,
 | 
						|
--      Commercial Computer Software, Computer Software Documentation, and
 | 
						|
--      Technical Data for Commercial Items are licensed to the U.S.
 | 
						|
--      Government under vendor's standard commercial license.
 | 
						|
--
 | 
						|
--      Refer to the READMIB.RDM file for more information about the
 | 
						|
--      organization of the information in the Compaq Enterprise.
 | 
						|
--
 | 
						|
--      The Compaq Enterprise number is 232.
 | 
						|
--      The ASN.1 prefix to, and including the Compaq Enterprise is:
 | 
						|
--           1.3.6.1.4.1.232
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
CPQRACK-MIB DEFINITIONS ::= BEGIN
 | 
						|
 | 
						|
    IMPORTS
 | 
						|
        compaq                         FROM CPQHOST-MIB
 | 
						|
        DisplayString                  FROM RFC1213-MIB
 | 
						|
        OBJECT-TYPE                    FROM RFC-1212
 | 
						|
        sysName                        FROM RFC1213-MIB
 | 
						|
        cpqHoTrapFlags                 FROM CPQHOST-MIB
 | 
						|
        TRAP-TYPE                      FROM RFC-1215;
 | 
						|
 | 
						|
--  compaq                             OBJECT IDENTIFIER ::= { enterprises 232 }
 | 
						|
    cpqRackInfo                        OBJECT IDENTIFIER ::= { compaq 22 }
 | 
						|
    cpqRackMibRev                      OBJECT IDENTIFIER ::= { cpqRackInfo 1 }
 | 
						|
    cpqRackComponent                   OBJECT IDENTIFIER ::= { cpqRackInfo 2 }
 | 
						|
    cpqRackSysObjID                    OBJECT IDENTIFIER ::= { cpqRackInfo 3 }
 | 
						|
 | 
						|
    cpqRackInterface                   OBJECT IDENTIFIER ::= { cpqRackComponent 1 }
 | 
						|
    cpqRackAsset                       OBJECT IDENTIFIER ::= { cpqRackComponent 2 }
 | 
						|
    cpqRackEnclosure                   OBJECT IDENTIFIER ::= { cpqRackComponent 3 }
 | 
						|
    cpqRackServer                      OBJECT IDENTIFIER ::= { cpqRackComponent 4 }
 | 
						|
    cpqRackPower                       OBJECT IDENTIFIER ::= { cpqRackComponent 5 }
 | 
						|
    cpqRackNetwork                     OBJECT IDENTIFIER ::= { cpqRackComponent 6 }
 | 
						|
 | 
						|
    cpqRackOsCommon                    OBJECT IDENTIFIER ::= { cpqRackInterface 4 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosure             OBJECT IDENTIFIER ::= { cpqRackEnclosure 1 }
 | 
						|
    cpqRackServerEnclosure             OBJECT IDENTIFIER ::= { cpqRackEnclosure 2 }
 | 
						|
    cpqRackPowerEnclosure              OBJECT IDENTIFIER ::= { cpqRackEnclosure 3 }
 | 
						|
 | 
						|
    cpqRackServerBlade                 OBJECT IDENTIFIER ::= { cpqRackServer 1 }
 | 
						|
 | 
						|
    cpqRackPowerSupply                 OBJECT IDENTIFIER ::= { cpqRackPower 1 }
 | 
						|
 | 
						|
    cpqRackNetConnector                OBJECT IDENTIFIER ::= { cpqRackNetwork 1 }
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Information MIB Revision
 | 
						|
--   =============================
 | 
						|
--
 | 
						|
-- The compaq enterprise               (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group              (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackMibRev Group           (1.3.6.1.4.1.232.22.1)
 | 
						|
--
 | 
						|
--    Implementation of the MibRev group is mandatory for all Agents
 | 
						|
--    supporting the Rack Information MIB.
 | 
						|
--
 | 
						|
--     An Agent conforming to this document will return a
 | 
						|
--     cpqRackMibRevMajor of one (1) and a cpqRackMibRevMinor of three (3).
 | 
						|
--
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackMibRevMajor OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER (1..65535)
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The major revision level of the MIB.
 | 
						|
 | 
						|
            A change in the major revision level represents a major change
 | 
						|
            in the architecture of the MIB.  A change in the major revision
 | 
						|
            level may indicate a significant change in the information
 | 
						|
            supported and/or the meaning of the supported information,
 | 
						|
            correct interpretation of data may require a MIB document with
 | 
						|
            the same major revision level."
 | 
						|
        ::= { cpqRackMibRev 1 }
 | 
						|
 | 
						|
    cpqRackMibRevMinor OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER (0..65535)
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The minor revision level of the MIB.
 | 
						|
 | 
						|
            A change in the minor revision level may represent some minor
 | 
						|
            additional support, no changes to any pre-existing information
 | 
						|
            has occurred."
 | 
						|
        ::= { cpqRackMibRev 2 }
 | 
						|
 | 
						|
    cpqRackMibCondition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            ok(2),              -- default
 | 
						|
            degraded(3),
 | 
						|
            failed(4)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The overall condition.
 | 
						|
 | 
						|
            This object represents the overall status of the
 | 
						|
            rack information represented by this MIB."
 | 
						|
        ::= { cpqRackMibRev 3 }
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Information Common
 | 
						|
--   =======================
 | 
						|
--
 | 
						|
-- The compaq enterprise               (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group              (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group        (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackInterface Group       (1.3.6.1.4.1.232.22.2.1)
 | 
						|
--         cpqRackOsCommon Group       (1.3.6.1.4.1.232.22.2.1.4)
 | 
						|
--
 | 
						|
--
 | 
						|
--  Implementation of the cpqRackOsCommon group is mandatory for all
 | 
						|
--  Agents that support the Rack Information MIB.
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackOsCommonPollFreq OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER (0..65535)
 | 
						|
        ACCESS  read-write
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The Management Agent's polling frequency.
 | 
						|
 | 
						|
            The frequency, in seconds, at which the Agent requests
 | 
						|
            information from the device driver.  A frequency of zero (0)
 | 
						|
            indicates that the Insight Agent retrieves the information upon
 | 
						|
            request of a management station, it does not poll the device
 | 
						|
            driver at a specific interval.
 | 
						|
 | 
						|
            If the poll frequency is zero (0) all attempts to write to this
 | 
						|
            object will fail.  If the poll frequency is non-zero,
 | 
						|
            setting this value will change the polling frequency of the
 | 
						|
            Insight Agent.  Setting the poll frequency to zero (0) will
 | 
						|
            always fail, an agent may also choose to fail any request to
 | 
						|
            change the poll frequency to a value that would severely impact
 | 
						|
            system performance."
 | 
						|
        ::= { cpqRackOsCommon 1 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Asset Group
 | 
						|
--   ================
 | 
						|
--
 | 
						|
-- The compaq enterprise               (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group              (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group        (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackAsset Group           (1.3.6.1.4.1.232.22.2.2)
 | 
						|
--
 | 
						|
--  The cpqRackAsset group contains the serial numbers, names, etc. of any
 | 
						|
--  Rack hardware that supports asset management.
 | 
						|
--
 | 
						|
--  Implementation of the cpqRackAsset group is mandatory for all
 | 
						|
--  Agents that support the Rack Information MIB.
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Asset Table
 | 
						|
--   ================
 | 
						|
--
 | 
						|
-- The compaq enterprise               (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group              (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group        (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackAsset Group           (1.3.6.1.4.1.232.22.2.2)
 | 
						|
--         cpqRackAssetTable           (1.3.6.1.4.1.232.22.2.2.1)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackAssetTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackAssetEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack asset information."
 | 
						|
        ::= { cpqRackAsset 1 }
 | 
						|
 | 
						|
    cpqRackAssetEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackAssetEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack asset description."
 | 
						|
        INDEX   { cpqRackAssetIndex }
 | 
						|
        ::= { cpqRackAssetTable 1 }
 | 
						|
 | 
						|
    CpqRackAssetEntry ::= SEQUENCE {
 | 
						|
        cpqRackAssetIndex           INTEGER,
 | 
						|
        cpqRackName                 DisplayString,
 | 
						|
        cpqRackUid                  DisplayString,
 | 
						|
        cpqRackSerialNum            DisplayString,
 | 
						|
        cpqRackTrapSequenceNum      INTEGER,
 | 
						|
        cpqRackHeight               INTEGER,
 | 
						|
        cpqRackWidth                INTEGER,
 | 
						|
        cpqRackDepth                INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackAssetIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack table entry."
 | 
						|
        ::= { cpqRackAssetEntry 1 }
 | 
						|
 | 
						|
    cpqRackName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The customer changeable identifier used to identify the entire
 | 
						|
            rack.
 | 
						|
 | 
						|
            The string will be empty if the system does not report this
 | 
						|
            function."
 | 
						|
        ::= { cpqRackAssetEntry 2 }
 | 
						|
 | 
						|
    cpqRackUid OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The rack unique identifier.
 | 
						|
 | 
						|
            The string will be empty if the rack does not report the
 | 
						|
            UID or if it could not be determined."
 | 
						|
        ::= { cpqRackAssetEntry 3 }
 | 
						|
 | 
						|
    cpqRackSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The rack serial number.
 | 
						|
 | 
						|
            The string will be empty if the rack does not report the
 | 
						|
            serial number."
 | 
						|
        ::= { cpqRackAssetEntry 4 }
 | 
						|
 | 
						|
    cpqRackTrapSequenceNum OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The trap sequence number for rack traps.
 | 
						|
 | 
						|
            This is used by the management application trap processing.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackAssetEntry 5 }
 | 
						|
 | 
						|
    cpqRackHeight OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The internal height dimension of the useable rack space expressed
 | 
						|
            in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackAssetEntry 6 }
 | 
						|
 | 
						|
    cpqRackWidth OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The internal width dimension of the useable rack space expressed
 | 
						|
            in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackAssetEntry 7 }
 | 
						|
 | 
						|
    cpqRackDepth OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The internal depth dimension of the useable rack space expressed
 | 
						|
            in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackAssetEntry 8 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Enclosure Chassis Group
 | 
						|
--   ============================
 | 
						|
--
 | 
						|
-- The compaq enterprise               (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group              (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group        (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group       (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--
 | 
						|
--  The cpqRackEnclosure group contains the information about rack
 | 
						|
--  enclosures.
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Common Enclosure Table
 | 
						|
--   ===========================
 | 
						|
--
 | 
						|
-- The compaq enterprise                 (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group          (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group         (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--         cpqRackCommonEnclosure Group  (1.3.6.1.4.1.232.22.2.3.1)
 | 
						|
--          cpqRackCommonEnclosureTable  (1.3.6.1.4.1.232.22.2.3.1.1)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackCommonEnclosureEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack enclosure information."
 | 
						|
        ::= { cpqRackCommonEnclosure 1 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackCommonEnclosureEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack enclosure description."
 | 
						|
        INDEX   { cpqRackCommonEnclosureRack,
 | 
						|
                  cpqRackCommonEnclosureIndex }
 | 
						|
        ::= { cpqRackCommonEnclosureTable 1 }
 | 
						|
 | 
						|
    CpqRackCommonEnclosureEntry ::= SEQUENCE {
 | 
						|
        cpqRackCommonEnclosureRack                 INTEGER,
 | 
						|
        cpqRackCommonEnclosureIndex                INTEGER,
 | 
						|
        cpqRackCommonEnclosureModel                DisplayString,
 | 
						|
        cpqRackCommonEnclosureAssetTag             DisplayString,
 | 
						|
        cpqRackCommonEnclosurePartNumber           DisplayString,
 | 
						|
        cpqRackCommonEnclosureSparePartNumber      DisplayString,
 | 
						|
        cpqRackCommonEnclosureSerialNum            DisplayString,
 | 
						|
        cpqRackCommonEnclosureFWRev                DisplayString,
 | 
						|
        cpqRackCommonEnclosureName                 DisplayString,
 | 
						|
        cpqRackCommonEnclosureNeighborNamePrev     DisplayString,
 | 
						|
        cpqRackCommonEnclosureNeighborNameNext     DisplayString,
 | 
						|
        cpqRackCommonEnclosureHeight               INTEGER,
 | 
						|
        cpqRackCommonEnclosureWidth                INTEGER,
 | 
						|
        cpqRackCommonEnclosureDepth                INTEGER,
 | 
						|
        cpqRackCommonEnclosureTrapSequenceNum      INTEGER,
 | 
						|
        cpqRackCommonEnclosureCondition            INTEGER,
 | 
						|
        cpqRackCommonEnclosureHasServerBlades      INTEGER,
 | 
						|
        cpqRackCommonEnclosureHasPowerSupplies     INTEGER,
 | 
						|
        cpqRackCommonEnclosureHasNetConnectors     INTEGER,
 | 
						|
        cpqRackCommonEnclosureHasTempSensors       INTEGER,
 | 
						|
        cpqRackCommonEnclosureHasFans              INTEGER,
 | 
						|
        cpqRackCommonEnclosureHasFuses             INTEGER,
 | 
						|
        cpqRackCommonEnclosureMgmtUID              INTEGER,
 | 
						|
        cpqRackCommonEnclosureSerialNumPrev        DisplayString,
 | 
						|
        cpqRackCommonEnclosureSerialNumNext        DisplayString,
 | 
						|
        cpqRackCommonEnclosureAddress              INTEGER,
 | 
						|
        cpqRackCommonEnclosureProductId            DisplayString,
 | 
						|
        cpqRackCommonEnclosureProductIdPrev        DisplayString,
 | 
						|
        cpqRackCommonEnclosureProductIdNext        DisplayString,
 | 
						|
        cpqRackCommonEnclosureUUID                 DisplayString,
 | 
						|
        cpqRackCommonEnclosureUUIDPrev             DisplayString,
 | 
						|
        cpqRackCommonEnclosureUUIDNext             DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 1 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this enclosure in the rack."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 2 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureModel OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The model name of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            model information."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 3 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureAssetTag OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The customer changeable asset identifier of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the system does not report this
 | 
						|
            function or if the asset tag has not been set."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 4 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosurePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The part number of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report this
 | 
						|
            function."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 5 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureSparePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The spare part number of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report this
 | 
						|
            function."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 6 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 7 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFWRev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The firmware revision of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            firmware revision or does not contain firmware."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 8 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 9 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureNeighborNamePrev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure immediately preceding or above this
 | 
						|
            enclosure.
 | 
						|
 | 
						|
            The string will be empty if the neighbor enclosure name could not be
 | 
						|
            determined or there is no enclosure preceding this one."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 10 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureNeighborNameNext OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure immediately following or below this
 | 
						|
            enclosure.
 | 
						|
 | 
						|
            The string will be empty if the neighbor enclosure name could not be
 | 
						|
            determined or there is no enclosure following this one."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 11 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureHeight OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The height dimension of the rack space taken by the
 | 
						|
            enclosure expressed in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 12 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureWidth OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The width dimension of the rack space taken by the
 | 
						|
            enclosure expressed in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 13 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureDepth OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The depth dimension of the rack space taken by the
 | 
						|
            enclosure expressed in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 14 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTrapSequenceNum OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The trap sequence number for the enclosure.
 | 
						|
 | 
						|
            This is used by the management application trap processing.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 15 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureCondition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            ok(2),
 | 
						|
            degraded(3),
 | 
						|
            failed(4)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The overall condition of the enclosure.
 | 
						|
 | 
						|
            This is the aggregate of the temperature sensors, fans, and
 | 
						|
            fuses within the enclosure.
 | 
						|
 | 
						|
            This value will be one of the following:
 | 
						|
 | 
						|
            other(1)
 | 
						|
              No temperature sensors, fans, or fuses in the enclosure or the
 | 
						|
              state could no be determined.
 | 
						|
 | 
						|
            ok(2)
 | 
						|
              All temperature sensors, fans, and fuses are within the normal
 | 
						|
              operating range.
 | 
						|
 | 
						|
            degraded(3)
 | 
						|
              One or more temperature sensors, fans, or fuses are outside of
 | 
						|
              the normal operating range.  None are failed.
 | 
						|
 | 
						|
            failed(4)
 | 
						|
              The temperature sensor exceeded the critical threshold value,
 | 
						|
              a required fan has failed, or a fuse has been tripped.
 | 
						|
 | 
						|
            The system will automatically shutdown if the failed(4) condition
 | 
						|
            results, so it is unlikely that this value will ever be returned
 | 
						|
            by the agent."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 16 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureHasServerBlades OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The enclosure can contain server blades.
 | 
						|
 | 
						|
            This will be true(2) is the enclosure can house server blades.  The
 | 
						|
            cpqRackServerEnclosureTable will contain server enclosure specific
 | 
						|
            information.
 | 
						|
 | 
						|
            Match the cpqRackCommonEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackServerEnclosureTable to get complete
 | 
						|
            information on the server enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 17 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureHasPowerSupplies OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The enclosure can contain power supplies.
 | 
						|
 | 
						|
            This will be true(2) is the enclosure can house power supplies.  The
 | 
						|
            cpqRackEnclosurePowerTable will contain power enclosure specific
 | 
						|
            information.
 | 
						|
 | 
						|
            Match the cpqRackCommonEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackEnclosurePowerTable to get complete
 | 
						|
            information on the power enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 18 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureHasNetConnectors OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The enclosure contains network connectivity.
 | 
						|
 | 
						|
            This will be true(2) is the enclosure contains network connectivity.
 | 
						|
            The cpqRackCommonEnclosureNetConnectorTable will contain network
 | 
						|
            connectivity specific information.
 | 
						|
 | 
						|
            Match the cpqRackCommonEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackCommonEnclosureNetConnectorTable to get complete
 | 
						|
            information on the network connector enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 19 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureHasTempSensors OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The enclosure contains temperature sensors.
 | 
						|
 | 
						|
            This will be true(2) is the enclosure contains
 | 
						|
            temperature sensors. The cpqRackCommonEnclosureTempTable will
 | 
						|
            contain temperature sensor specific information.
 | 
						|
 | 
						|
            Match the cpqRackCommonEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackCommonEnclosureTempTable to get complete
 | 
						|
            information on the enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 20 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureHasFans OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The enclosure contains fans.
 | 
						|
 | 
						|
            This will be true(2) is the enclosure contains fans.
 | 
						|
            The cpqRackCommonEnclosureFanTable will contain the fan
 | 
						|
            specific information.
 | 
						|
 | 
						|
            Match the cpqRackCommonEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackCommonEnclosureFanTable to get complete
 | 
						|
            information on the enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 21 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureHasFuses OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The enclosure contains fuses.
 | 
						|
 | 
						|
            This will be true(2) is the enclosure contains fuses.
 | 
						|
            The cpqRackCommonEnclosureFuseTable will contain the fuse
 | 
						|
            specific information.
 | 
						|
 | 
						|
            Match the cpqRackCommonEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackCommonEnclosureFuseTable to get complete
 | 
						|
            information on the enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 22 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureMgmtUID OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),            -- Unknown device or could not be determined
 | 
						|
            none(2),             -- No Unit Identifier LED present
 | 
						|
            ledOn(3),            -- Unit Identifier LED is On
 | 
						|
            ledOff(4)            -- Unit Identifier LED is Off
 | 
						|
            }
 | 
						|
        ACCESS  read-write
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The Unit Identifier LED.
 | 
						|
 | 
						|
            This value will be one of the following:
 | 
						|
 | 
						|
            other(1)
 | 
						|
              The state of the LED could not be determined.  Setting the
 | 
						|
              LED state is not allowed.
 | 
						|
 | 
						|
            none(2)
 | 
						|
              The LED is not present.  Setting LED state is not allowed.
 | 
						|
 | 
						|
            ledOn(3)
 | 
						|
              The LED is present and ON.  The LED can be turned off
 | 
						|
              by setting the cpqRackCommonEnclosureMgmtUID to ledOff(4).
 | 
						|
 | 
						|
            ledOff(4)
 | 
						|
              The LED is present and OFF.  The LED can be turned on
 | 
						|
              by setting the cpqRackCommonEnclosureMgmtUID to ledOn(3)."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 23 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureSerialNumPrev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure immediately preceding or
 | 
						|
            above this enclosure.
 | 
						|
 | 
						|
            The string will be empty if the neighbor enclosure serial number
 | 
						|
            could not be determined or there is no enclosure preceding this one."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 24 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureSerialNumNext OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure immediately following or
 | 
						|
            below this enclosure.
 | 
						|
 | 
						|
            The string will be empty if the neighbor enclosure serial number
 | 
						|
            could not be determined or there is no enclosure following this one."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 25 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureAddress OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The unique address of the enclosure within the rack.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 26 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureProductId OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The product id string of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            product id string."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 27 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureProductIdPrev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The product id string of the enclosure immediately preceding or
 | 
						|
            above this enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            product id string."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 28 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureProductIdNext OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The product id string of the enclosure immediately following or
 | 
						|
            below this enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            product id string."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 29 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureUUID OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The universal unique identifier string of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            UUID string."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 30 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureUUIDPrev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The universal unique identifier string of the enclosure
 | 
						|
            immediately preceding or above this enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            UUID string or if there is no preceding enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 31 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureUUIDNext OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The universal unique identifier string of the enclosure
 | 
						|
            immediately following or below this enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            UUID string or if there is no following enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureEntry 32 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Enclosure Common Temperature Sensor Table
 | 
						|
--   ==============================================
 | 
						|
--
 | 
						|
-- The compaq enterprise                     (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                    (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group              (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group             (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--         cpqRackCommonEnclosure Group      (1.3.6.1.4.1.232.22.2.3.1)
 | 
						|
--          cpqRackCommonEnclosureTempTable  (1.3.6.1.4.1.232.22.2.3.1.2)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackCommonEnclosureTempEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack enclosure temperature sensor information."
 | 
						|
        ::= { cpqRackCommonEnclosure 2 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackCommonEnclosureTempEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack enclosure temperature sensor description."
 | 
						|
        INDEX   { cpqRackCommonEnclosureTempRack,
 | 
						|
                  cpqRackCommonEnclosureTempChassis,
 | 
						|
                  cpqRackCommonEnclosureTempSensorIndex }
 | 
						|
        ::= { cpqRackCommonEnclosureTempTable 1 }
 | 
						|
 | 
						|
    CpqRackCommonEnclosureTempEntry ::= SEQUENCE {
 | 
						|
        cpqRackCommonEnclosureTempRack                      INTEGER,
 | 
						|
        cpqRackCommonEnclosureTempChassis                   INTEGER,
 | 
						|
        cpqRackCommonEnclosureTempSensorIndex               INTEGER,
 | 
						|
        cpqRackCommonEnclosureTempSensorEnclosureName       DisplayString,
 | 
						|
        cpqRackCommonEnclosureTempLocation                  DisplayString,
 | 
						|
        cpqRackCommonEnclosureTempCurrent                   INTEGER,
 | 
						|
        cpqRackCommonEnclosureTempThreshold                 INTEGER,
 | 
						|
        cpqRackCommonEnclosureTempCondition                 INTEGER,
 | 
						|
        cpqRackCommonEnclosureTempType                      INTEGER,
 | 
						|
        cpqRackCommonEnclosureTempSensorEnclosureSerialNum  DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 1 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempChassis OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this enclosure in the rack."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 2 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempSensorIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this temperature sensor within
 | 
						|
            this enclosure in the rack."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 3 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempSensorEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 4 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempLocation OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The location description of the temperature sensor within the
 | 
						|
            enclosure.
 | 
						|
 | 
						|
            The string will be empty if the location could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 5 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempCurrent OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This is the current temperature sensor reading in degrees
 | 
						|
            celsius.
 | 
						|
 | 
						|
            If this value cannot be determined by software, then a value
 | 
						|
            of -1 will be returned."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 6 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempThreshold OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This is the threshold temperature sensor setting
 | 
						|
            in degrees celsius.  This is the temperature in which the
 | 
						|
            sensor will be considered to be in a tripped state this
 | 
						|
            causing some action to occur depending on the type of
 | 
						|
            the sensor.  The action of temperature sensor threshold
 | 
						|
            will be indicated by the cpqRackCommonEnclosureTempType
 | 
						|
            item.  If the type is blowout(5), then the temperature sensor
 | 
						|
            will cause the fans to speed up.  If the type is caution(9),
 | 
						|
            then the temperature sensor is in a degraded state.  If the
 | 
						|
            type is critical(15), then the enclosure will be considered
 | 
						|
            as in a failed state.
 | 
						|
 | 
						|
            If this value cannot be determined by software, then a value
 | 
						|
            of -1 will be returned."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 7 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempCondition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            ok(2),
 | 
						|
            degraded(3),
 | 
						|
            failed(4)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The Temperature sensor condition.
 | 
						|
 | 
						|
            This value will be one of the following:
 | 
						|
 | 
						|
            other(1)
 | 
						|
              Temperature could not be determined.
 | 
						|
 | 
						|
            ok(2)
 | 
						|
              The temperature sensor is within the normal operating range.
 | 
						|
 | 
						|
            degraded(3)
 | 
						|
              The temperature sensor is outside of the normal operating range.
 | 
						|
 | 
						|
            failed(4)
 | 
						|
              The temperature sensor detects a condition that could
 | 
						|
              possibly damage the system.
 | 
						|
 | 
						|
            The system will automatically shutdown if the failed(4) condition
 | 
						|
            results, so it is unlikely that this value will ever be returned
 | 
						|
            by the agent."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 8 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempType OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            blowout(5),
 | 
						|
            caution(9),
 | 
						|
            critical(15)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies the type of this instance of temperature
 | 
						|
            sensor.
 | 
						|
 | 
						|
            This value will be one of the following:
 | 
						|
 | 
						|
            other(1)
 | 
						|
              Temperature threshold type could not be determined.
 | 
						|
 | 
						|
            blowout(5)
 | 
						|
              If a blowout(5) temperature sensor reaches its threshold,
 | 
						|
              the fan or fans in the area of the temperature sensor will
 | 
						|
              increase in speed in an attempt to reduce the temperature
 | 
						|
              before a caution or critical threshold is reached.
 | 
						|
 | 
						|
            caution(9)
 | 
						|
              If a caution(9) temperature sensor reaches its threshold, the
 | 
						|
              cpqRackCommonEnclosureTempCondition will be set to degraded(3)
 | 
						|
              and the system will either continue or shutdown depending
 | 
						|
              on the user preferences.
 | 
						|
 | 
						|
            critical(15)
 | 
						|
              If a critical(15) temperature sensor reaches its threshold,
 | 
						|
              the cpqHeTemperatureCondition will be set to failed(4)
 | 
						|
              and the system will shutdown."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 9 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureTempSensorEnclosureSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure containing this temperature
 | 
						|
            sensor.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number or it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureTempEntry 10 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Enclosure Common Fan Table
 | 
						|
--   ===============================
 | 
						|
--
 | 
						|
-- The compaq enterprise                     (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                    (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group              (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group             (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--         cpqRackCommonEnclosure Group      (1.3.6.1.4.1.232.22.2.3.1)
 | 
						|
--          cpqRackCommonEnclosureFanTable   (1.3.6.1.4.1.232.22.2.3.1.3)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackCommonEnclosureFanEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack enclosure fan information."
 | 
						|
        ::= { cpqRackCommonEnclosure 3 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackCommonEnclosureFanEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack enclosure fan description."
 | 
						|
        INDEX   { cpqRackCommonEnclosureFanRack,
 | 
						|
                  cpqRackCommonEnclosureFanChassis,
 | 
						|
                  cpqRackCommonEnclosureFanIndex }
 | 
						|
        ::= { cpqRackCommonEnclosureFanTable 1 }
 | 
						|
 | 
						|
    CpqRackCommonEnclosureFanEntry ::= SEQUENCE {
 | 
						|
        cpqRackCommonEnclosureFanRack                   INTEGER,
 | 
						|
        cpqRackCommonEnclosureFanChassis                INTEGER,
 | 
						|
        cpqRackCommonEnclosureFanIndex                  INTEGER,
 | 
						|
        cpqRackCommonEnclosureFanEnclosureName          DisplayString,
 | 
						|
        cpqRackCommonEnclosureFanLocation               DisplayString,
 | 
						|
        cpqRackCommonEnclosureFanPartNumber             DisplayString,
 | 
						|
        cpqRackCommonEnclosureFanSparePartNumber        DisplayString,
 | 
						|
        cpqRackCommonEnclosureFanPresent                INTEGER,
 | 
						|
        cpqRackCommonEnclosureFanRedundant              INTEGER,
 | 
						|
        cpqRackCommonEnclosureFanRedundantGroupId       INTEGER,
 | 
						|
        cpqRackCommonEnclosureFanCondition              INTEGER,
 | 
						|
        cpqRackCommonEnclosureFanEnclosureSerialNum     DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 1 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanChassis OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this enclosure in the rack."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 2 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this fan within this
 | 
						|
            enclosure in the rack."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 3 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 4 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanLocation OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The location description of the fan within the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the location could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 5 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanPartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The part number of the enclosure fan.
 | 
						|
 | 
						|
            The string will be empty if the part number could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 6 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanSparePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The spare part number of the enclosure fan.
 | 
						|
 | 
						|
            The string will be empty if the part number could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 7 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanPresent OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            absent(2),
 | 
						|
            present(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies if the fan described is present in the system."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 8 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanRedundant OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            notRedundant(2),
 | 
						|
            redundant(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies if the fan is in a redundant configuration."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 9 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanRedundantGroupId OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies the group number for redundant fans within this
 | 
						|
            enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 10 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanCondition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            ok(2),
 | 
						|
            degraded(3),
 | 
						|
            failed(4)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The condition of the fan.
 | 
						|
 | 
						|
            This value will be one of the following:
 | 
						|
 | 
						|
            other(1)
 | 
						|
              Fan status detection is not supported.
 | 
						|
 | 
						|
            ok(2)
 | 
						|
              The fan is operating properly.
 | 
						|
 | 
						|
            degraded(2)
 | 
						|
              A redundant fan is not operating properly.
 | 
						|
 | 
						|
            failed(4)
 | 
						|
              A non-redundant fan is not operating properly."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 11 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFanEnclosureSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure containing the fan.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number or it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFanEntry 12 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Enclosure Common Fuse Table
 | 
						|
--   ================================
 | 
						|
--
 | 
						|
-- The compaq enterprise                     (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                    (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group              (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group             (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--         cpqRackCommonEnclosure Group      (1.3.6.1.4.1.232.22.2.3.1)
 | 
						|
--          cpqRackCommonEnclosureFuseTable  (1.3.6.1.4.1.232.22.2.3.1.4)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackCommonEnclosureFuseEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack enclosure fuse information."
 | 
						|
        ::= { cpqRackCommonEnclosure 4 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackCommonEnclosureFuseEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack enclosure fuse description."
 | 
						|
        INDEX   { cpqRackCommonEnclosureFuseRack,
 | 
						|
                  cpqRackCommonEnclosureFuseChassis,
 | 
						|
                  cpqRackCommonEnclosureFuseIndex }
 | 
						|
        ::= { cpqRackCommonEnclosureFuseTable 1 }
 | 
						|
 | 
						|
    CpqRackCommonEnclosureFuseEntry ::= SEQUENCE {
 | 
						|
        cpqRackCommonEnclosureFuseRack             INTEGER,
 | 
						|
        cpqRackCommonEnclosureFuseChassis          INTEGER,
 | 
						|
        cpqRackCommonEnclosureFuseIndex            INTEGER,
 | 
						|
        cpqRackCommonEnclosureFuseEnclosureName    DisplayString,
 | 
						|
        cpqRackCommonEnclosureFuseLocation         DisplayString,
 | 
						|
        cpqRackCommonEnclosureFusePresent          INTEGER,
 | 
						|
        cpqRackCommonEnclosureFuseCondition        INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackCommonEnclosureFuseEntry 1 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseChassis OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this enclosure in the rack."
 | 
						|
        ::= { cpqRackCommonEnclosureFuseEntry 2 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies the fuse within this enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureFuseEntry 3 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFuseEntry 4 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseLocation OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The location description of the fuse within the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the location could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFuseEntry 5 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFusePresent OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            absent(2),
 | 
						|
            present(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies if the fuse described is present in the system."
 | 
						|
        ::= { cpqRackCommonEnclosureFuseEntry 6 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFuseCondition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            ok(2),
 | 
						|
            failed(4)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The condition of the fuse.
 | 
						|
 | 
						|
            This value will be one of the following:
 | 
						|
 | 
						|
            other(1)
 | 
						|
              Fuse status detection is not supported.
 | 
						|
 | 
						|
            ok(2)
 | 
						|
              The fuse is operating properly.
 | 
						|
 | 
						|
            failed(4)
 | 
						|
              A fuse has been tripped or is not operating properly."
 | 
						|
        ::= { cpqRackCommonEnclosureFuseEntry 7 }
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Enclosure Common FRU Table
 | 
						|
--   ===============================
 | 
						|
--
 | 
						|
-- The compaq enterprise                     (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                    (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group              (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group             (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--         cpqRackCommonEnclosure Group      (1.3.6.1.4.1.232.22.2.3.1)
 | 
						|
--          cpqRackCommonEnclosureFruTable   (1.3.6.1.4.1.232.22.2.3.1.5)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackCommonEnclosureFruEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack enclosure field replaceable units information."
 | 
						|
        ::= { cpqRackCommonEnclosure 5 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackCommonEnclosureFruEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack enclosure field replaceable unit description."
 | 
						|
        INDEX   { cpqRackCommonEnclosureFruRack,
 | 
						|
                  cpqRackCommonEnclosureFruChassis,
 | 
						|
                  cpqRackCommonEnclosureFruIndex }
 | 
						|
        ::= { cpqRackCommonEnclosureFruTable 1 }
 | 
						|
 | 
						|
    CpqRackCommonEnclosureFruEntry ::= SEQUENCE {
 | 
						|
        cpqRackCommonEnclosureFruRack                 INTEGER,
 | 
						|
        cpqRackCommonEnclosureFruChassis              INTEGER,
 | 
						|
        cpqRackCommonEnclosureFruIndex                INTEGER,
 | 
						|
        cpqRackCommonEnclosureFruEnclosureName        DisplayString,
 | 
						|
        cpqRackCommonEnclosureFruDescription          DisplayString,
 | 
						|
        cpqRackCommonEnclosureFruLocation             DisplayString,
 | 
						|
        cpqRackCommonEnclosureFruAssemblyPartNumber   DisplayString,
 | 
						|
        cpqRackCommonEnclosureFruSparePartNumber      DisplayString,
 | 
						|
        cpqRackCommonEnclosureFruAutoRev              DisplayString,
 | 
						|
        cpqRackCommonEnclosureFruSerialNum            DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 1 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruChassis OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this enclosure in the rack."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 2 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies the FRU within this enclosure."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 3 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 4 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruDescription OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A description of the FRU component.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            description information."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 5 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruLocation OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The location description of the FRU within the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the location could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 6 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruAssemblyPartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The assembly part number of the FRU within the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report this
 | 
						|
            information."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 7 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruSparePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The spare part number of the FRU within the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report this
 | 
						|
            information."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 8 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruAutoRev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The auto revision number of the FRU within the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report this
 | 
						|
            information."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 9 }
 | 
						|
 | 
						|
    cpqRackCommonEnclosureFruSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the FRU within the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number."
 | 
						|
        ::= { cpqRackCommonEnclosureFruEntry 10 }
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Enclosure for Servers Table
 | 
						|
--   ================================
 | 
						|
--
 | 
						|
-- The compaq enterprise                 (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group          (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group         (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--         cpqRackServerEnclosure Group  (1.3.6.1.4.1.232.22.2.3.2)
 | 
						|
--          cpqRackServerEnclosureTable  (1.3.6.1.4.1.232.22.2.3.2.1)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackServerEnclosureTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackServerEnclosureEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack enclosure information for servers."
 | 
						|
        ::= { cpqRackServerEnclosure 1 }
 | 
						|
 | 
						|
    cpqRackServerEnclosureEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackServerEnclosureEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A server enclosure description."
 | 
						|
        INDEX   { cpqRackServerEnclosureRack,
 | 
						|
                  cpqRackServerEnclosureIndex }
 | 
						|
        ::= { cpqRackServerEnclosureTable 1 }
 | 
						|
 | 
						|
    CpqRackServerEnclosureEntry ::= SEQUENCE {
 | 
						|
        cpqRackServerEnclosureRack                 INTEGER,
 | 
						|
        cpqRackServerEnclosureIndex                INTEGER,
 | 
						|
        cpqRackServerEnclosureName                 DisplayString,
 | 
						|
        cpqRackServerEnclosureMaxNumBlades         INTEGER,
 | 
						|
        cpqRackServerEnclosureMaxNumBladesX        INTEGER,
 | 
						|
        cpqRackServerEnclosureMaxNumBladesY        INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackServerEnclosureRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackServerEnclosureEntry 1 }
 | 
						|
 | 
						|
    cpqRackServerEnclosureIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this server enclosure in the rack."
 | 
						|
        ::= { cpqRackServerEnclosureEntry 2 }
 | 
						|
 | 
						|
    cpqRackServerEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the server enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackServerEnclosureEntry 3 }
 | 
						|
 | 
						|
    cpqRackServerEnclosureMaxNumBlades OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The maximum number of server blades the enclosure can contain.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackServerEnclosureEntry 4 }
 | 
						|
 | 
						|
    cpqRackServerEnclosureMaxNumBladesX OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The maximum number of server blades in x-direction (from left to right)
 | 
						|
            the enclosure can contain."
 | 
						|
 | 
						|
        ::= { cpqRackServerEnclosureEntry 5 }
 | 
						|
 | 
						|
    cpqRackServerEnclosureMaxNumBladesY OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The maximum number of server blades in y-direction (from top to bottom)
 | 
						|
            the enclosure can contain."
 | 
						|
 | 
						|
        ::= { cpqRackServerEnclosureEntry 6 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Enclosure for Power Supplies Table
 | 
						|
--   =======================================
 | 
						|
--
 | 
						|
-- The compaq enterprise                 (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group          (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackEnclosure Group         (1.3.6.1.4.1.232.22.2.3)
 | 
						|
--         cpqRackPowerEnclosure Group   (1.3.6.1.4.1.232.22.2.3.3)
 | 
						|
--          cpqRackPowerEnclosureTable   (1.3.6.1.4.1.232.22.2.3.3.1)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackPowerEnclosureTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackPowerEnclosureEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack power enclosure information."
 | 
						|
        ::= { cpqRackPowerEnclosure 1 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackPowerEnclosureEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack power enclosure description."
 | 
						|
        INDEX   { cpqRackPowerEnclosureRack,
 | 
						|
                  cpqRackPowerEnclosureIndex }
 | 
						|
        ::= { cpqRackPowerEnclosureTable 1 }
 | 
						|
 | 
						|
    CpqRackPowerEnclosureEntry ::= SEQUENCE {
 | 
						|
        cpqRackPowerEnclosureRack                  INTEGER,
 | 
						|
        cpqRackPowerEnclosureIndex                 INTEGER,
 | 
						|
        cpqRackPowerEnclosureName                  DisplayString,
 | 
						|
        cpqRackPowerEnclosureMgmtBoardSerialNum    DisplayString,
 | 
						|
        cpqRackPowerEnclosureRedundant             INTEGER,
 | 
						|
        cpqRackPowerEnclosureLoadBalanced          INTEGER,
 | 
						|
        cpqRackPowerEnclosureInputPwrType          INTEGER,
 | 
						|
        cpqRackPowerEnclosurePwrFeedMax            INTEGER,
 | 
						|
        cpqRackPowerEnclosureCondition             INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 1 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this power enclosure in the rack."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 2 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the power enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 3 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureMgmtBoardSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 4 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureRedundant OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            notRedundant(2),
 | 
						|
            redundant(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This indicates if the power supply enclosure is in a redundant
 | 
						|
            state."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 5 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureLoadBalanced OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            notLoadBalanced(2),
 | 
						|
            loadBalanced(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This indicates if the power supply enclosure is in a load
 | 
						|
            balanced state."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 6 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureInputPwrType OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            singlePhase(2),
 | 
						|
            threePhase(3),
 | 
						|
            directCurrent(4)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This indicates type of input facility power."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 7 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosurePwrFeedMax OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This is the maximum facility power in watts.
 | 
						|
 | 
						|
            The maximum facility power being fed to this power enclosure.
 | 
						|
 | 
						|
            The value will be -1 if the power enclosure does not report the
 | 
						|
            value or if the value is not known."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 8 }
 | 
						|
 | 
						|
    cpqRackPowerEnclosureCondition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            ok(2),
 | 
						|
            degraded(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This indicates current condition of the power enclosure.
 | 
						|
 | 
						|
            other(1)
 | 
						|
              The power enclosure condition could not be determined.
 | 
						|
 | 
						|
            ok(2)
 | 
						|
              The power enclosure is operating normally.
 | 
						|
 | 
						|
            degraded(3)
 | 
						|
              The power enclosure is in a degraded state.  The power subsystem
 | 
						|
              may not be load balanced or may have lost redundancy."
 | 
						|
        ::= { cpqRackPowerEnclosureEntry 9 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Server Blade Table
 | 
						|
--   =======================
 | 
						|
--
 | 
						|
-- The compaq enterprise                 (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group          (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackServer Group            (1.3.6.1.4.1.232.22.2.4)
 | 
						|
--         cpqRackServerBlade Group      (1.3.6.1.4.1.232.22.2.4.1)
 | 
						|
--          cpqRackServerBladeTable      (1.3.6.1.4.1.232.22.2.4.1.1)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackServerBladeTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackServerBladeEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack server blade information."
 | 
						|
        ::= { cpqRackServerBlade 1 }
 | 
						|
 | 
						|
    cpqRackServerBladeEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackServerBladeEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack server blade description."
 | 
						|
        INDEX   { cpqRackServerBladeRack,
 | 
						|
                  cpqRackServerBladeChassis,
 | 
						|
                  cpqRackServerBladeIndex }
 | 
						|
        ::= { cpqRackServerBladeTable 1 }
 | 
						|
 | 
						|
    CpqRackServerBladeEntry ::= SEQUENCE {
 | 
						|
        cpqRackServerBladeRack               INTEGER,
 | 
						|
        cpqRackServerBladeChassis            INTEGER,
 | 
						|
        cpqRackServerBladeIndex              INTEGER,
 | 
						|
        cpqRackServerBladeName               DisplayString,
 | 
						|
        cpqRackServerBladeEnclosureName      DisplayString,
 | 
						|
        cpqRackServerBladePartNumber         DisplayString,
 | 
						|
        cpqRackServerBladeSparePartNumber    DisplayString,
 | 
						|
        cpqRackServerBladePosition           INTEGER,
 | 
						|
        cpqRackServerBladeHeight             INTEGER,
 | 
						|
        cpqRackServerBladeWidth              INTEGER,
 | 
						|
        cpqRackServerBladeDepth              INTEGER,
 | 
						|
        cpqRackServerBladePresent            INTEGER,
 | 
						|
        cpqRackServerBladeHasFuses           INTEGER,
 | 
						|
        cpqRackServerBladeEnclosureSerialNum DisplayString,
 | 
						|
        cpqRackServerBladeSlotsUsed          INTEGER,
 | 
						|
        cpqRackServerBladeSerialNum          DisplayString,
 | 
						|
        cpqRackServerBladeProductId          DisplayString,
 | 
						|
        cpqRackServerBladeUid                DisplayString,
 | 
						|
        cpqRackServerBladeSlotsUsedX         INTEGER,
 | 
						|
        cpqRackServerBladeSlotsUsedY         INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackServerBladeRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackServerBladeEntry 1 }
 | 
						|
 | 
						|
    cpqRackServerBladeChassis OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this enclosure in the rack."
 | 
						|
        ::= { cpqRackServerBladeEntry 2 }
 | 
						|
 | 
						|
    cpqRackServerBladeIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this server blade within the enclosure."
 | 
						|
        ::= { cpqRackServerBladeEntry 3 }
 | 
						|
 | 
						|
    cpqRackServerBladeName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the server blade.
 | 
						|
 | 
						|
            The string will be empty if it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 4 }
 | 
						|
 | 
						|
    cpqRackServerBladeEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the enclosure which contains the blade.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 5 }
 | 
						|
 | 
						|
    cpqRackServerBladePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The part number of the server blade.
 | 
						|
 | 
						|
            The string will be empty if the part number could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 6 }
 | 
						|
 | 
						|
    cpqRackServerBladeSparePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The spare part number of the server blade.
 | 
						|
 | 
						|
            The string will be empty if the part number could not be
 | 
						|
            determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 7 }
 | 
						|
 | 
						|
    cpqRackServerBladePosition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The position or slot number of the server blade within the
 | 
						|
            server enclosure.
 | 
						|
 | 
						|
            This will be -1 if the server enclosure does not report the
 | 
						|
            information or it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 8 }
 | 
						|
 | 
						|
    cpqRackServerBladeHeight OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The height dimension of the rack space taken by the server
 | 
						|
            blade expressed in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 9 }
 | 
						|
 | 
						|
    cpqRackServerBladeWidth OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The width dimension of the rack space taken by the server
 | 
						|
            blade expressed in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 10 }
 | 
						|
 | 
						|
    cpqRackServerBladeDepth OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The depth dimension of the rack space taken by the server
 | 
						|
            blade expressed in millimeters.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 11 }
 | 
						|
 | 
						|
    cpqRackServerBladePresent OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            absent(2),
 | 
						|
            present(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies if the server blade described is present in the
 | 
						|
            enclosure."
 | 
						|
        ::= { cpqRackServerBladeEntry 12 }
 | 
						|
 | 
						|
    cpqRackServerBladeHasFuses OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The server blade contains fuses.
 | 
						|
 | 
						|
            This will be true(2) is the server blade contains fuses.
 | 
						|
            The cpqRackCommonEnclosureFuseTable will contain the fuse
 | 
						|
            specific information.
 | 
						|
 | 
						|
            Match the cpqRackServerBladeEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackCommonEnclosureFanTable to get complete
 | 
						|
            information on the fuses."
 | 
						|
        ::= { cpqRackServerBladeEntry 13 }
 | 
						|
 | 
						|
    cpqRackServerBladeEnclosureSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure which contains the blade.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number or it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 14 }
 | 
						|
 | 
						|
    cpqRackServerBladeSlotsUsed OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The number of slot positions occupied by this server blade.  This
 | 
						|
            is used to indicate a server blade which may obscure an adjacent
 | 
						|
            blade slot.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 15 }
 | 
						|
 | 
						|
    cpqRackServerBladeSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the server blade.
 | 
						|
 | 
						|
            The string will be empty if the system does not report the
 | 
						|
            serial number function."
 | 
						|
        ::= { cpqRackServerBladeEntry 16 }
 | 
						|
 | 
						|
    cpqRackServerBladeProductId OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The product id string of the server blade.
 | 
						|
 | 
						|
            The string will be empty if the system does not report the
 | 
						|
            product id function."
 | 
						|
        ::= { cpqRackServerBladeEntry 17 }
 | 
						|
 | 
						|
    cpqRackServerBladeUid OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The server blade unique identifier.
 | 
						|
 | 
						|
            The string will be empty if the blade does not report the
 | 
						|
            UID or if it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 18 }
 | 
						|
 | 
						|
    cpqRackServerBladeSlotsUsedX OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The number of slot positions in x-direction (from left to right)
 | 
						|
            occupied by this server blade.  This is used to indicate a server blade
 | 
						|
            which may obscure an adjacent blade slot.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 19 }
 | 
						|
 | 
						|
    cpqRackServerBladeSlotsUsedY OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The number of slot positions in y-direction (from top to bottom)
 | 
						|
            occupied by this server blade.  This is used to indicate a server blade
 | 
						|
            which may obscure an adjacent blade slot.
 | 
						|
 | 
						|
            This will be -1 if the rack does not report the information or
 | 
						|
            it could not be determined."
 | 
						|
        ::= { cpqRackServerBladeEntry 20 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Power Supply Table
 | 
						|
--   =======================
 | 
						|
--
 | 
						|
-- The compaq enterprise                 (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group          (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackPower Group             (1.3.6.1.4.1.232.22.2.5)
 | 
						|
--         cpqRackPowerSupply Group      (1.3.6.1.4.1.232.22.2.5.1)
 | 
						|
--          cpqRackPowerSupplyTable      (1.3.6.1.4.1.232.22.2.5.1.1)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackPowerSupplyTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackPowerSupplyEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack power supply information."
 | 
						|
        ::= { cpqRackPowerSupply 1 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackPowerSupplyEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack power supply description."
 | 
						|
        INDEX   { cpqRackPowerSupplyRack,
 | 
						|
                  cpqRackPowerSupplyChassis,
 | 
						|
                  cpqRackPowerSupplyIndex }
 | 
						|
        ::= { cpqRackPowerSupplyTable 1 }
 | 
						|
 | 
						|
    CpqRackPowerSupplyEntry ::= SEQUENCE {
 | 
						|
        cpqRackPowerSupplyRack                  INTEGER,
 | 
						|
        cpqRackPowerSupplyChassis               INTEGER,
 | 
						|
        cpqRackPowerSupplyIndex                 INTEGER,
 | 
						|
        cpqRackPowerSupplyEnclosureName         DisplayString,
 | 
						|
        cpqRackPowerSupplySerialNum             DisplayString,
 | 
						|
        cpqRackPowerSupplyPartNumber            DisplayString,
 | 
						|
        cpqRackPowerSupplySparePartNumber       DisplayString,
 | 
						|
        cpqRackPowerSupplyFWRev                 DisplayString,
 | 
						|
        cpqRackPowerSupplyMaxPwrOutput          INTEGER,
 | 
						|
        cpqRackPowerSupplyCurPwrOutput          INTEGER,
 | 
						|
        cpqRackPowerSupplyPosition              INTEGER,
 | 
						|
        cpqRackPowerSupplyIntakeTemp            INTEGER,
 | 
						|
        cpqRackPowerSupplyExhaustTemp           INTEGER,
 | 
						|
        cpqRackPowerSupplyStatus                INTEGER,
 | 
						|
        cpqRackPowerSupplyInputLineStatus       INTEGER,
 | 
						|
        cpqRackPowerSupplyPresent               INTEGER,
 | 
						|
        cpqRackPowerSupplyCondition             INTEGER,
 | 
						|
        cpqRackPowerSupplyEnclosureSerialNum    DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackPowerSupplyRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 1 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyChassis OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this power enclosure in the rack."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 2 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this power supply in the enclosure."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 3 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the power supply enclosure in which this power supply
 | 
						|
            resides.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 4 }
 | 
						|
 | 
						|
    cpqRackPowerSupplySerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the power supply.
 | 
						|
 | 
						|
            The string will be empty if the power supply does not report the
 | 
						|
            serial number."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 5 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyPartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The part number of the power supply.
 | 
						|
 | 
						|
            The string will be empty if the power supply does not report this
 | 
						|
            function."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 6 }
 | 
						|
 | 
						|
    cpqRackPowerSupplySparePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The spare part number of the power supply.
 | 
						|
 | 
						|
            The string will be empty if the power supply does not report this
 | 
						|
            function."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 7 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyFWRev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The firmware revision of the power supply.
 | 
						|
 | 
						|
            The string will be empty if the power supply does not report the
 | 
						|
            firmware revision."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 8 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyMaxPwrOutput OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The maximum power output of the power supply in watts.
 | 
						|
 | 
						|
            The value will be -1 if the power supply does not report the
 | 
						|
            value."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 9 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyCurPwrOutput OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The current power output of the power supply in watts.
 | 
						|
 | 
						|
            The value will be -1 if the power supply does not report the
 | 
						|
            value."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 10 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyPosition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The position of the power supply within the power enclosure.
 | 
						|
 | 
						|
            This will be -1 if the power enclosure does not report the
 | 
						|
            power supply information or it could not be determined."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 11 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyIntakeTemp OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The current air temperature at the intake of the power supply
 | 
						|
            in degrees celsius.
 | 
						|
 | 
						|
            The value will be -1 if the power supply does not report the
 | 
						|
            value."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 12 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyExhaustTemp OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The current air temperature at the exhaust of the power supply
 | 
						|
            in degrees celsius.
 | 
						|
 | 
						|
            The value will be -1 if the power supply does not report the
 | 
						|
            value."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 13 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyStatus OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            noError(1),
 | 
						|
            generalFailure(2),
 | 
						|
            bistFailure(3),
 | 
						|
            fanFailure(4),
 | 
						|
            tempFailure(5),
 | 
						|
            interlockOpen(6),
 | 
						|
            epromFailed(7),
 | 
						|
            vrefFailed(8),
 | 
						|
            dacFailed(9),
 | 
						|
            ramTestFailed(10),
 | 
						|
            voltageChannelFailed(11),
 | 
						|
            orringdiodeFailed(12),
 | 
						|
            brownOut(13),
 | 
						|
            giveupOnStartup(14),
 | 
						|
            nvramInvalid(15),
 | 
						|
            calibrationTableInvalid(16)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The status of the power supply."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 14 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyInputLineStatus OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            noError(1),
 | 
						|
            lineOverVoltage(2),
 | 
						|
            lineUnderVoltage(3),
 | 
						|
            lineHit(4),
 | 
						|
            brownOut(5),
 | 
						|
            linePowerLoss(6)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The status of line input power."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 15 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyPresent OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            absent(2),
 | 
						|
            present(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies if the power supply described is present in the
 | 
						|
            enclosure."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 16 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyCondition OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            ok(2),
 | 
						|
            degraded(3),
 | 
						|
            failed(4)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The condition of the power supply.
 | 
						|
 | 
						|
            This value will be one of the following:
 | 
						|
 | 
						|
            other(1)
 | 
						|
              The status could not be determined or not present.
 | 
						|
 | 
						|
            ok(2)
 | 
						|
              The power supply is operating normally.
 | 
						|
 | 
						|
            degraded(3)
 | 
						|
              A temperature sensor, fan or other power supply component is
 | 
						|
              outside of normal operating range.
 | 
						|
 | 
						|
            failed(4)
 | 
						|
              A power supply component detects a condition that could
 | 
						|
              possibly damage the system."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 17 }
 | 
						|
 | 
						|
    cpqRackPowerSupplyEnclosureSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the power supply enclosure in which this
 | 
						|
            power supply resides.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number or it could not be determined."
 | 
						|
        ::= { cpqRackPowerSupplyEntry 18 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack Network Connector Table
 | 
						|
--   ============================
 | 
						|
--
 | 
						|
-- The compaq enterprise                 (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackComponent Group          (1.3.6.1.4.1.232.22.2)
 | 
						|
--        cpqRackNetwork Group           (1.3.6.1.4.1.232.22.2.6)
 | 
						|
--         cpqRackNetConnector Group     (1.3.6.1.4.1.232.22.2.6.1)
 | 
						|
--          cpqRackNetConnectorTable     (1.3.6.1.4.1.232.22.2.6.1.1)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackNetConnectorTable OBJECT-TYPE
 | 
						|
        SYNTAX  SEQUENCE OF CpqRackNetConnectorEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A table of rack network connector information."
 | 
						|
        ::= { cpqRackNetConnector 1 }
 | 
						|
 | 
						|
    cpqRackNetConnectorEntry OBJECT-TYPE
 | 
						|
        SYNTAX  CpqRackNetConnectorEntry
 | 
						|
        ACCESS  not-accessible
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A rack network connector description."
 | 
						|
        INDEX   { cpqRackNetConnectorRack,
 | 
						|
                  cpqRackNetConnectorChassis,
 | 
						|
                  cpqRackNetConnectorIndex }
 | 
						|
        ::= { cpqRackNetConnectorTable 1 }
 | 
						|
 | 
						|
    CpqRackNetConnectorEntry ::= SEQUENCE {
 | 
						|
        cpqRackNetConnectorRack                 INTEGER,
 | 
						|
        cpqRackNetConnectorChassis              INTEGER,
 | 
						|
        cpqRackNetConnectorIndex                INTEGER,
 | 
						|
        cpqRackNetConnectorEnclosureName        DisplayString,
 | 
						|
        cpqRackNetConnectorName                 DisplayString,
 | 
						|
        cpqRackNetConnectorModel                DisplayString,
 | 
						|
        cpqRackNetConnectorSerialNum            DisplayString,
 | 
						|
        cpqRackNetConnectorPartNumber           DisplayString,
 | 
						|
        cpqRackNetConnectorSparePartNumber      DisplayString,
 | 
						|
        cpqRackNetConnectorFWRev                DisplayString,
 | 
						|
        cpqRackNetConnectorType                 INTEGER,
 | 
						|
        cpqRackNetConnectorLocation             DisplayString,
 | 
						|
        cpqRackNetConnectorPresent              INTEGER,
 | 
						|
        cpqRackNetConnectorHasFuses             INTEGER,
 | 
						|
        cpqRackNetConnectorEnclosureSerialNum   DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
    cpqRackNetConnectorRack OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this rack."
 | 
						|
        ::= { cpqRackNetConnectorEntry 1 }
 | 
						|
 | 
						|
    cpqRackNetConnectorChassis OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this server enclosure in the rack."
 | 
						|
        ::= { cpqRackNetConnectorEntry 2 }
 | 
						|
 | 
						|
    cpqRackNetConnectorIndex OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "A number that uniquely specifies this network connector in the rack."
 | 
						|
        ::= { cpqRackNetConnectorEntry 3 }
 | 
						|
 | 
						|
    cpqRackNetConnectorEnclosureName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the network connector enclosure.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackNetConnectorEntry 4 }
 | 
						|
 | 
						|
    cpqRackNetConnectorName OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The name of the network connector.
 | 
						|
 | 
						|
            The string will be empty if the network connector does not report the
 | 
						|
            name or it could not be determined."
 | 
						|
        ::= { cpqRackNetConnectorEntry 5 }
 | 
						|
 | 
						|
    cpqRackNetConnectorModel OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The model name of the network connector.
 | 
						|
 | 
						|
            The string will be empty if the network connector does not report the
 | 
						|
            model information."
 | 
						|
        ::= { cpqRackNetConnectorEntry 6 }
 | 
						|
 | 
						|
    cpqRackNetConnectorSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the network connector.
 | 
						|
 | 
						|
            The string will be empty if the network connector does not report the
 | 
						|
            serial number."
 | 
						|
        ::= { cpqRackNetConnectorEntry 7 }
 | 
						|
 | 
						|
    cpqRackNetConnectorPartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The part number of the network connector.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report this
 | 
						|
            function."
 | 
						|
        ::= { cpqRackNetConnectorEntry 8 }
 | 
						|
 | 
						|
    cpqRackNetConnectorSparePartNumber OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The spare part number of the network connector.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report this
 | 
						|
            function."
 | 
						|
        ::= { cpqRackNetConnectorEntry 9 }
 | 
						|
 | 
						|
    cpqRackNetConnectorFWRev OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The firmware revision of the network connector.
 | 
						|
 | 
						|
            The string will be empty if the network connector does not report the
 | 
						|
            firmware revision."
 | 
						|
        ::= { cpqRackNetConnectorEntry 10 }
 | 
						|
 | 
						|
    cpqRackNetConnectorType OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            passive(2),
 | 
						|
            active(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The type of network connector within the enclosure."
 | 
						|
        ::= { cpqRackNetConnectorEntry 11 }
 | 
						|
 | 
						|
    cpqRackNetConnectorLocation OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The location of the network connector within the enclosure."
 | 
						|
        ::= { cpqRackNetConnectorEntry 12 }
 | 
						|
 | 
						|
    cpqRackNetConnectorPresent OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            other(1),
 | 
						|
            absent(2),
 | 
						|
            present(3)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "This specifies if the network connector described is present in the
 | 
						|
            enclosure."
 | 
						|
        ::= { cpqRackNetConnectorEntry 13 }
 | 
						|
 | 
						|
    cpqRackNetConnectorHasFuses OBJECT-TYPE
 | 
						|
        SYNTAX  INTEGER {
 | 
						|
            false(1),
 | 
						|
            true(2)
 | 
						|
            }
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The network connector contains fuses.
 | 
						|
 | 
						|
            This will be true(2) is the network connector contains fuses.
 | 
						|
            The cpqRackCommonEnclosureFuseTable will contain the fuse
 | 
						|
            specific information.
 | 
						|
 | 
						|
            Match the cpqRackNetworkEnclosureSerialNum in this table to the
 | 
						|
            serial number in the cpqRackCommonEnclosureFusTable to get complete
 | 
						|
            information on the fuses."
 | 
						|
        ::= { cpqRackNetConnectorEntry 14 }
 | 
						|
 | 
						|
    cpqRackNetConnectorEnclosureSerialNum OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The serial number of the enclosure containing the network connector.
 | 
						|
 | 
						|
            The string will be empty if the enclosure does not report the
 | 
						|
            serial number or it could not be determined."
 | 
						|
        ::= { cpqRackNetConnectorEntry 15 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--   Rack System Object Identification
 | 
						|
--   =================================
 | 
						|
--
 | 
						|
-- The compaq enterprise                 (1.3.6.1.4.1.232)
 | 
						|
--      cpqRackInfo Group                (1.3.6.1.4.1.232.22)
 | 
						|
--       cpqRackSysObjID Group           (1.3.6.1.4.1.232.22.3)
 | 
						|
--
 | 
						|
-- ****************************************************************************
 | 
						|
 | 
						|
    cpqRackSystemObjectIdentification OBJECT-TYPE
 | 
						|
        SYNTAX  DisplayString (SIZE (0..64))
 | 
						|
        ACCESS  read-only
 | 
						|
        STATUS  mandatory
 | 
						|
        DESCRIPTION
 | 
						|
            "The hardware identification string.
 | 
						|
 | 
						|
            The string will reported by the rack firmware."
 | 
						|
        ::= { cpqRackSysObjID 1 }
 | 
						|
 | 
						|
 | 
						|
-- ****************************************************************************
 | 
						|
--  Rack Information Trap Definitions
 | 
						|
--  =================================
 | 
						|
--
 | 
						|
--  The SNMP trap messages must not be bigger than 484 octets (bytes).
 | 
						|
--
 | 
						|
--  Trap support in an SNMP agent implementation is optional.  An SNMP
 | 
						|
--  agent implementation may support all, some, or none of the traps.
 | 
						|
--  If traps are supported, The user should be provided with the option of
 | 
						|
--  disabling traps.
 | 
						|
-- **************************************************************************
 | 
						|
 | 
						|
    cpqRackNameChanged TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackSerialNum,
 | 
						|
                     cpqRackTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Rack name has changed.
 | 
						|
 | 
						|
            This trap signifies that an agent or utility has changed the name
 | 
						|
            of the rack.  Each of the server blades in each of the enclosure
 | 
						|
            within the rack will be updated to reflect the new rack name.
 | 
						|
 | 
						|
            It may take several minutes for the rack name change to be
 | 
						|
            propagated throughout the entire rack.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Rack name changed (22001)"
 | 
						|
        --#SUMMARY "The rack name has changed to %s."
 | 
						|
        --#ARGUMENTS {2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22001
 | 
						|
 | 
						|
    cpqRackEnclosureNameChanged TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureModel,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure name has changed.
 | 
						|
 | 
						|
            This trap signifies that an agent or utility has changed the name
 | 
						|
            of an enclosure within the rack.  Each of the components
 | 
						|
            within the rack will be updated to reflect the new enclosure name.
 | 
						|
 | 
						|
            It may take several minutes for the enclosure name change to be
 | 
						|
            propagated throughout the entire enclosure.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Enclosure name changed (22002)"
 | 
						|
        --#SUMMARY "The enclosure name has changed to %s in rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22002
 | 
						|
 | 
						|
    cpqRackEnclosureRemoved TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureModel,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure has been removed.
 | 
						|
 | 
						|
            This trap signifies that an enclosure has been removed from
 | 
						|
            the rack.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Enclosure removed (22003)"
 | 
						|
        --#SUMMARY "The enclosure %s has been removed from rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22003
 | 
						|
 | 
						|
    cpqRackEnclosureInserted TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureModel,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure has been inserted.
 | 
						|
 | 
						|
            This trap signifies that an enclosure has been inserted into
 | 
						|
            the rack.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Enclosure inserted (22004)"
 | 
						|
        --#SUMMARY "The enclosure %s has been inserted into rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22004
 | 
						|
 | 
						|
    cpqRackEnclosureTempFailed TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTempLocation,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure temperature status has been set to failed.
 | 
						|
 | 
						|
            This trap signifies that a enclosure temperature sensor has
 | 
						|
            been tripped indicating an overheat condition.
 | 
						|
 | 
						|
            User Action: Shutdown the enclosure and possibly the rack
 | 
						|
            as soon as possible.  Insure all fans are working properly and
 | 
						|
            that air flow in the rack has not been blocked."
 | 
						|
 | 
						|
        --#TYPE "Enclosure temperature failed (22005)"
 | 
						|
        --#SUMMARY "The enclosure %s temperature sensor in rack %s has been set to failed."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22005
 | 
						|
 | 
						|
    cpqRackEnclosureTempDegraded TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTempLocation,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure temperature status has been set to degraded.
 | 
						|
 | 
						|
            This trap signifies that an enclosure temperature sensor has
 | 
						|
            been tripped indicating a possible overheat condition.
 | 
						|
 | 
						|
            User Action: Shutdown the enclosure and possibly the rack
 | 
						|
            as soon as possible.  Insure all fans are working properly and
 | 
						|
            that air flow in the rack has not been blocked."
 | 
						|
 | 
						|
        --#TYPE "Enclosure temperature degraded (22006)"
 | 
						|
        --#SUMMARY "The enclosure %s temperature sensor in rack %s has been set to degraded."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22006
 | 
						|
 | 
						|
    cpqRackEnclosureTempOk TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTempLocation,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure temperature status has been set to ok.
 | 
						|
 | 
						|
            This trap signifies that an enclosure temperature sensor has
 | 
						|
            returned to normal.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Enclosure temperature ok (22007)"
 | 
						|
        --#SUMMARY "The enclosure %s temperature sensor in rack %s has been set to ok."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22007
 | 
						|
 | 
						|
    cpqRackEnclosureFanFailed TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureFanLocation,
 | 
						|
                     cpqRackCommonEnclosureFanSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure fan status has been set to failed.
 | 
						|
 | 
						|
            This trap signifies that an enclosure fan has failed and
 | 
						|
            no other fans in the redundant fan group are operating.
 | 
						|
            This may result in overheating of the enclosure.
 | 
						|
 | 
						|
            User Action: Replace the fan as soon as possible."
 | 
						|
 | 
						|
        --#TYPE "Enclosure fan failed (22008)"
 | 
						|
        --#SUMMARY "The enclosure %s fan in rack %s has been set to failed."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22008
 | 
						|
 | 
						|
    cpqRackEnclosureFanDegraded TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureFanLocation,
 | 
						|
                     cpqRackCommonEnclosureFanSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure fan status has been set to degraded.
 | 
						|
 | 
						|
            This trap signifies that an enclosure fan has failed but
 | 
						|
            other fans in the redundant fan group are still operating.
 | 
						|
            This may result in overheating of the enclosure.
 | 
						|
 | 
						|
            User Action: Replace the fan as soon as possible."
 | 
						|
 | 
						|
        --#TYPE "Enclosure fan degraded (22009)"
 | 
						|
        --#SUMMARY "The enclosure %s fan in rack %s has been set to degraded."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22009
 | 
						|
 | 
						|
    cpqRackEnclosureFanOk TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureFanLocation,
 | 
						|
                     cpqRackCommonEnclosureFanSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure fan status has been set to ok.
 | 
						|
 | 
						|
            This trap signifies that an enclosure fan has returned
 | 
						|
            to normal operation.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Enclosure fan ok (22010)"
 | 
						|
        --#SUMMARY "The enclosure %s fan in rack %s has been set to ok."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22010
 | 
						|
 | 
						|
 | 
						|
    cpqRackEnclosureFanRemoved TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureFanLocation,
 | 
						|
                     cpqRackCommonEnclosureFanSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure fan has been removed.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Enclosure fan removed (22011)"
 | 
						|
        --#SUMMARY "The enclosure %s fan in rack %s has been removed."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MINOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22011
 | 
						|
 | 
						|
    cpqRackEnclosureFanInserted TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureFanLocation,
 | 
						|
                     cpqRackCommonEnclosureFanSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The enclosure fan has been inserted.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Enclosure fan inserted (22012)"
 | 
						|
        --#SUMMARY "The enclosure %s fan in rack %s has been inserted."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22012
 | 
						|
 | 
						|
    cpqRackPowerSupplyFailed TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerSupplyEnclosureName,
 | 
						|
                     cpqRackPowerSupplySerialNum,
 | 
						|
                     cpqRackPowerSupplyPosition,
 | 
						|
                     cpqRackPowerSupplyFWRev,
 | 
						|
                     cpqRackPowerSupplySparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The power supply status has been set to failed.
 | 
						|
 | 
						|
            This trap signifies that a power supply has failed.
 | 
						|
 | 
						|
            User Action: Replace the power supply as soon as possible."
 | 
						|
 | 
						|
        --#TYPE "Rack power supply failed (22013)"
 | 
						|
        --#SUMMARY "The power supply %s in enclosure %s in rack %s has been set to failed."
 | 
						|
        --#ARGUMENTS {6, 4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22013
 | 
						|
 | 
						|
    cpqRackPowerSupplyDegraded TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerSupplyEnclosureName,
 | 
						|
                     cpqRackPowerSupplySerialNum,
 | 
						|
                     cpqRackPowerSupplyPosition,
 | 
						|
                     cpqRackPowerSupplyFWRev,
 | 
						|
                     cpqRackPowerSupplySparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The power supply status has been set to degraded.
 | 
						|
 | 
						|
            This trap signifies that a power supply has degraded.
 | 
						|
 | 
						|
            User Action: Replace the power supply as soon as possible."
 | 
						|
 | 
						|
        --#TYPE "Rack power supply degraded (22014)"
 | 
						|
        --#SUMMARY "The power supply %s in enclosure %s in rack %s has been set to degraded."
 | 
						|
        --#ARGUMENTS {6, 4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22014
 | 
						|
 | 
						|
    cpqRackPowerSupplyOk TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerSupplyEnclosureName,
 | 
						|
                     cpqRackPowerSupplySerialNum,
 | 
						|
                     cpqRackPowerSupplyPosition,
 | 
						|
                     cpqRackPowerSupplyFWRev,
 | 
						|
                     cpqRackPowerSupplySparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The power supply status has been set to ok.
 | 
						|
 | 
						|
            This trap signifies that a power supply has returned to normal
 | 
						|
            operation.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Rack power supply ok (22015)"
 | 
						|
        --#SUMMARY "The power supply %s in enclosure %s in rack %s has been set to ok."
 | 
						|
        --#ARGUMENTS {6, 4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22015
 | 
						|
 | 
						|
    cpqRackPowerSupplyRemoved TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerSupplyEnclosureName,
 | 
						|
                     cpqRackPowerSupplySerialNum,
 | 
						|
                     cpqRackPowerSupplyPosition,
 | 
						|
                     cpqRackPowerSupplyFWRev,
 | 
						|
                     cpqRackPowerSupplySparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The power supply has been removed.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Rack power supply removed (22016)"
 | 
						|
        --#SUMMARY "The power supply %s in enclosure %s in rack %s has been removed."
 | 
						|
        --#ARGUMENTS {6, 4, 2}
 | 
						|
        --#SEVERITY MINOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22016
 | 
						|
 | 
						|
    cpqRackPowerSupplyInserted TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerSupplyEnclosureName,
 | 
						|
                     cpqRackPowerSupplySerialNum,
 | 
						|
                     cpqRackPowerSupplyPosition,
 | 
						|
                     cpqRackPowerSupplyFWRev,
 | 
						|
                     cpqRackPowerSupplySparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The power supply has been inserted.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Rack power supply inserted (22017)"
 | 
						|
        --#SUMMARY "The power supply %s in enclosure %s in rack %s has been inserted."
 | 
						|
        --#ARGUMENTS {6, 4, 2}
 | 
						|
        --#SEVERITY INFORMATIONAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE OPERATIONAL
 | 
						|
 | 
						|
        ::= 22017
 | 
						|
 | 
						|
    cpqRackPowerSubsystemNotRedundant TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The rack power subsystem is no longer in a redundant state.
 | 
						|
 | 
						|
            User Action: Replace any failed power supplies as soon as possible
 | 
						|
            to return the system to a redundant state."
 | 
						|
 | 
						|
        --#TYPE "Rack power subsystem not redundant (22018)"
 | 
						|
        --#SUMMARY "The power subsystem in enclosure %s in rack %s is no longer redundant."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22018
 | 
						|
 | 
						|
    cpqRackPowerSubsystemLineVoltageProblem TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerSupplyEnclosureName,
 | 
						|
                     cpqRackPowerSupplyPosition,
 | 
						|
                     cpqRackPowerSupplyFWRev,
 | 
						|
                     cpqRackPowerSupplyInputLineStatus,
 | 
						|
                     cpqRackPowerSupplySparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The rack power supply detected an input line voltage problem.
 | 
						|
 | 
						|
            User Action: Check the power input for the power supply or replace
 | 
						|
            any failed power supplies as soon as possible."
 | 
						|
 | 
						|
        --#TYPE "Rack power supply input voltage problem (22019)"
 | 
						|
        --#SUMMARY "The rack power supply detected an input line voltage problem in power supply %s, enclosure %s, rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22019
 | 
						|
 | 
						|
    cpqRackPowerSubsystemOverloadCondition TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackPowerEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "The rack power subsystem overload condition.
 | 
						|
 | 
						|
            User Action: Replace any failed power supplies as soon as possible
 | 
						|
            to return the system to a redundant state."
 | 
						|
 | 
						|
        --#TYPE "Rack power subsystem overload condition (22020)"
 | 
						|
        --#SUMMARY "The power subsystem in enclosure %s in rack %s is in an overload condition."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22020
 | 
						|
 | 
						|
    cpqRackPowerShedAutoShutdown TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Server shutdown due to power shedding.
 | 
						|
 | 
						|
            The server blade was shutdown due to a lack of power.
 | 
						|
 | 
						|
            User Action: Check power connections or add power supplies."
 | 
						|
 | 
						|
        --#TYPE "Server shutdown due to power shedding (22021)"
 | 
						|
        --#SUMMARY "The server shutdown due to lack of power blade %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22021
 | 
						|
 | 
						|
    cpqRackServerPowerOnFailedNotRedundant TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Server power on prevented to preserve redundancy.
 | 
						|
 | 
						|
            There is not enough power to power on the server blade and
 | 
						|
            maintain redundancy for the other blades in the enclosure.
 | 
						|
 | 
						|
            User Action: Check power connections or add power supplies."
 | 
						|
 | 
						|
        --#TYPE "Server power on prevented to preserve redundancy (22022)"
 | 
						|
        --#SUMMARY "Server power on prevented to preserve redundancy in blade %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22022
 | 
						|
 | 
						|
    cpqRackServerPowerOnFailedNotEnoughPower TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Inadequate power to power on.
 | 
						|
 | 
						|
            There is not enough power to power on the server blade.
 | 
						|
 | 
						|
            User Action: Check power connections or add power supplies."
 | 
						|
 | 
						|
        --#TYPE "Inadequate power to power on (22023)"
 | 
						|
        --#SUMMARY "Inadequate power to power on blade %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22023
 | 
						|
 | 
						|
    cpqRackServerPowerOnFailedEnclosureNotFound TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Inadequate power to power on.
 | 
						|
 | 
						|
            There is not enough power to power on the server blade.  The
 | 
						|
            server enclosure micro-controller was not found.
 | 
						|
 | 
						|
            User Action: Check server enclosure connections or add power supplies."
 | 
						|
 | 
						|
        --#TYPE "Inadequate power to power on (22024)"
 | 
						|
        --#SUMMARY "Inadequate power to power on blade %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22024
 | 
						|
 | 
						|
    cpqRackServerPowerOnFailedPowerChassisNotFound TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Inadequate power to power on.
 | 
						|
 | 
						|
            There is not enough power to power on the server blade.  The
 | 
						|
            power enclosure micro-controller was not found.
 | 
						|
 | 
						|
            User Action: Check power enclosure connections or add power supplies."
 | 
						|
 | 
						|
        --#TYPE "Inadequate power to power on (22025)"
 | 
						|
        --#SUMMARY "Inadequate power to power on blade %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY CRITICAL
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE NONOPERATIONAL
 | 
						|
 | 
						|
        ::= 22025
 | 
						|
 | 
						|
    cpqRackServerPowerOnManualOverride TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Server power on via manual override.
 | 
						|
 | 
						|
            The server blade was powered on by a manual override.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Server power on via manual override (22026)"
 | 
						|
        --#SUMMARY "Server power on via manual override on blade %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22026
 | 
						|
 | 
						|
    cpqRackFuseOpen TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureFuseLocation,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Fuse open.
 | 
						|
 | 
						|
            The fuse has been tripped.
 | 
						|
 | 
						|
            User Action: Check enclosure and / or blade power connections and
 | 
						|
            reset the fuse."
 | 
						|
 | 
						|
        --#TYPE "Fuse open (22027)"
 | 
						|
        --#SUMMARY "Fuse open fuse %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22027
 | 
						|
 | 
						|
 | 
						|
    cpqRackServerBladeRemoved TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladeName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Server blade removed.
 | 
						|
 | 
						|
            The server blade has been removed from the enclosure.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Server blade removed (22028)"
 | 
						|
        --#SUMMARY "Server blade %s removed from position %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 6, 4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22028
 | 
						|
 | 
						|
    cpqRackServerBladeInserted TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackServerBladeEnclosureName,
 | 
						|
                     cpqRackServerBladeName,
 | 
						|
                     cpqRackServerBladePosition,
 | 
						|
                     cpqRackServerBladeSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Server blade inserted.
 | 
						|
 | 
						|
            The server blade has been inserted into the enclosure.
 | 
						|
 | 
						|
            User Action: None."
 | 
						|
 | 
						|
        --#TYPE "Server blade inserted (22029)"
 | 
						|
        --#SUMMARY "Server blade %s inserted into position %s, in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {5, 6, 4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22029
 | 
						|
 | 
						|
    cpqRackPowerChassisNotLoadBalanced TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Power subsystem not load balanced.
 | 
						|
 | 
						|
            The power subsystem is out of balance for this power enclosure.
 | 
						|
 | 
						|
            User Action: Check the power enclosure and power supplies.  Replace
 | 
						|
            any failed or degraded power supplies.  Add additional power supplies
 | 
						|
            if needed."
 | 
						|
 | 
						|
        --#TYPE "Power subsystem not load balanced (22030)"
 | 
						|
        --#SUMMARY "Power subsystem not load balanced in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22030
 | 
						|
 | 
						|
    cpqRackPowerChassisDcPowerProblem TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Power subsystem DC power problem.
 | 
						|
 | 
						|
            There is a power subsystem DC power problem for this power enclosure.
 | 
						|
 | 
						|
            User Action: Check the power enclosure and power supplies.  Replace
 | 
						|
            any failed or degraded power supplies."
 | 
						|
 | 
						|
        --#TYPE "Power subsystem DC power problem (22031)"
 | 
						|
        --#SUMMARY "Power subsystem DC power problem in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22031
 | 
						|
 | 
						|
    cpqRackPowerChassisAcFacilityPowerExceeded TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Power subsystem AC facility input power exceeded.
 | 
						|
 | 
						|
            There is a power subsystem Power subsystem AC facility input power
 | 
						|
            exceeded for this power enclosure.
 | 
						|
 | 
						|
            User Action: Check the power enclosure and power supplies.  Replace
 | 
						|
            any failed or degraded power supplies."
 | 
						|
 | 
						|
        --#TYPE "Power subsystem AC facility input power exceeded (22032)"
 | 
						|
        --#SUMMARY "Power subsystem AC facility input power exceeded in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22032
 | 
						|
 | 
						|
 | 
						|
 | 
						|
    cpqRackPowerUnknownPowerConsumption TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Unknown power consumption.
 | 
						|
 | 
						|
            There is an unknown power consumer drawing power.
 | 
						|
 | 
						|
            User Action: Check the power enclosure and power supplies.  Replace
 | 
						|
            any failed or degraded power supplies."
 | 
						|
 | 
						|
        --#TYPE "Unknown power consumption (22033)"
 | 
						|
        --#SUMMARY "Unknown power consumption in rack %s."
 | 
						|
        --#ARGUMENTS {2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22033
 | 
						|
 | 
						|
    cpqRackPowerChassisLoadBalancingWireMissing TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Power subsystem load balancing wire missing.
 | 
						|
 | 
						|
            The power subsystem load balancing wire missing.
 | 
						|
 | 
						|
            User Action: Connect the load balancing wire."
 | 
						|
 | 
						|
        --#TYPE "Power subsystem load balancing wire missing (22034)"
 | 
						|
        --#SUMMARY "Power subsystem load balancing wire missing for enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22034
 | 
						|
 | 
						|
    cpqRackPowerChassisTooManyPowerChassis TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Power subsystem has too may power enclosures.
 | 
						|
 | 
						|
            The maximum number of power enclosures has been exceeded.
 | 
						|
 | 
						|
            User Action: Remove the extra power enclosure."
 | 
						|
 | 
						|
        --#TYPE "Power subsystem has too may power enclosures (22035)"
 | 
						|
        --#SUMMARY "Power subsystem has too may power enclosures %s, in rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22035
 | 
						|
 | 
						|
    cpqRackPowerChassisConfigError TRAP-TYPE
 | 
						|
        ENTERPRISE compaq
 | 
						|
        VARIABLES  { sysName,
 | 
						|
                     cpqHoTrapFlags,
 | 
						|
                     cpqRackName,
 | 
						|
                     cpqRackUid,
 | 
						|
                     cpqRackCommonEnclosureName,
 | 
						|
                     cpqRackCommonEnclosureSerialNum,
 | 
						|
                     cpqRackCommonEnclosureSparePartNumber,
 | 
						|
                     cpqRackCommonEnclosureTrapSequenceNum }
 | 
						|
        DESCRIPTION
 | 
						|
           "Power subsystem improperly configured.
 | 
						|
 | 
						|
            The power subsystem has been improperly configured.
 | 
						|
 | 
						|
            User Action: Check the cabling of the power enclosure."
 | 
						|
 | 
						|
        --#TYPE "Power subsystem improperly configured (22036)"
 | 
						|
        --#SUMMARY "Power subsystem has been improperly configured in enclosure %s, in rack %s."
 | 
						|
        --#ARGUMENTS {4, 2}
 | 
						|
        --#SEVERITY MAJOR
 | 
						|
        --#TIMEINDEX 99
 | 
						|
        --#STATE DEGRADED
 | 
						|
 | 
						|
        ::= 22036
 | 
						|
 | 
						|
END
 | 
						|
 |